Default Settings for Electronic Modular Control Panel
EMCP Default Settings
Show/hide table
    | XQ1000 (1)     | XQ2000     | XQ1250G     | ||||
---|---|---|---|---|---|---|---|
    | 208 V 60Hz     | 240 V 60Hz     | 400 V 50Hz     | 480 V 60Hz     | 400 V 50Hz     | 480 V 60Hz     | 480 V 60Hz     |
Engine Start Fault Protection Activation Delay Time     | 30 sec     | ||||||
Crank Duration     | 10 sec     | ||||||
Crank Cycle Rest Interval     | 10 sec     | ||||||
Engine Purge Cycle Time     | 0 sec     | ||||||
Maximum Number of Crank Cycles     | 5     | ||||||
Cooldown Duration     | 5 min     | ||||||
Start Aid Activation Time     | 0 sec     | ||||||
Crank Alert Activation Time     | 0 sec     | ||||||
Crank Terminate RPM     | 400 RPM     | ||||||
Engine Fuel Type Configuration     | Diesel     | Gas     | |||||
Fuel Shutoff Solenoid Type Configuration     | Energized to Run     | ||||||
Engine Type Configuration     | Electronic     | ||||||
Engine Controller J1939 Datalink Support Configuration     | Proprietary J1939 Support     | ||||||
Engine Cooldown Speed Configuration     | Rated Speed     | ||||||
Engine Operating State Input Configuration     | Can Input     | Hardwired Input     | |||||
Fuel Priming Feature Enable Status     | Disabled     | ||||||
Engine Forced Idle Feature Enable Status     | Enabled     | ||||||
    | |||||||
Maximum Generator Voltage Output Bias Percentage     | 15%     | ||||||
Generator Nominal Output Voltage     | 208 V     | 240 V     | 400 V     | 480 V     | 400 V     | 480 V     | 480 V     |
    | |||||||
High Battery Voltage Warning Event Threshold     | 29.4 V     | ||||||
High Battery Voltage Warning Event Notification Delay Time     | 30 sec     | ||||||
High Battery Voltage Shutdown Event Threshold     | 32.0 V     | ||||||
High Battery Voltage Shutdown Event Notification Delay Time     | 2 sec     | ||||||
Low Battery Voltage Warning Event Threshold     | 18.0 V     | ||||||
Low Battery Voltage Warning Event Notification Delay Time     | 10 sec     | ||||||
Low Battery Charging System Voltage Warning Event Threshold     | 26.0 V     | ||||||
Low Battery Charging System Voltage Warning Event Notification Delay Time     | 30 sec     | ||||||
Low Cranking Voltage Warning Event Threshold     | 20 V     | ||||||
Low Cranking Voltage Warning Event Notification Delay Time     | 2 sec     | ||||||
Customer Password Security Level to Reset Crank/Start Counters     | 3 Factory, Single Use     | ||||||
SCADA Data Link Baud Rate     | 19200 baud     | ||||||
SCADA Data Link Parity     | None     | ||||||
SCADA Data Link Slave Address     | 1     | ||||||
SCADA Data Link Access Password     | 00000000     | ||||||
SCADA Data Link Connection Timeout Interval     | 30 sec     | ||||||
RS-485 Bias Resistor Enable Status     | Enabled     | ||||||
    | |||||||
Digital Input 1 Active State Configuration     | High     | ||||||
Digital Input 2 Active State Configuration     | Low     | ||||||
Digital Input 3 Active State Configuration     | Low     | ||||||
Digital Input 4 Active State Configuration     | Low     | ||||||
Digital Input 5 Active State Configuration     | Low     | ||||||
Digital Input 6 Active State Configuration     | Low     | ||||||
Digital Input 7 Active State Configuration     | Low     | ||||||
Digital Input 8 Active State Configuration     | Low     | ||||||
    | |||||||
Digital Output 1 Active State Configuration     | High     | ||||||
Digital Output 2 Active State Configuration     | High     | ||||||
    | |||||||
Digital Selector 1 Source Configuration     | Disabled     | ||||||
Digital Selector 2 Source Configuration     | Input4     | ||||||
Digital Selector 3 Source Configuration     | Input4     | ||||||
Digital Selector 4 Source Configuration     | Disabled     | ||||||
Digital Selector 5 Source Configuration     | Disabled     | Input 10     | |||||
Digital Selector 6 Source Configuration     | Disabled     | ||||||
Digital Selector 7 Source Configuration     | Input 1     | ||||||
Digital Selector 8 Source Configuration     | Disabled     | ||||||
Digital Selector 9 Source Configuration     | Disabled or Not Installed     | ||||||
Digital Selector 10 Source Configuration     | Disabled or Not Installed     | ||||||
    | |||||||
Engine Coolant Temperature Sensor Configuration     | Data Link     | ||||||
High Engine Coolant Temperature Warning Event Threshold     | 216 degree F     | ||||||
High Engine Coolant Temperature Warning Event Notification Delay Time     | 2 sec     | ||||||
High Engine Coolant Temperature Shutdown Event Threshold     | 225 degree F     | ||||||
High Engine Coolant Temperature Shutdown Event Notification Delay Time     | 10 seconds     | ||||||
Low Engine Coolant Temperature Warning Event Threshold     | 70 degree F     | ||||||
Low Engine Coolant Temperature Warning Event Notification Delay Time     | 2 seconds     | ||||||
Engine Coolant Temperature Sensor Configuration Code     | Map 1     | ||||||
Engine Oil Pressure Sensor Configuration     | Data Link     | ||||||
Low Engine Oil Pressure Warning Event Threshold     | 35 psi     | ||||||
Low Idle Low Engine Oil Pressure Warning Event Threshold     | 15 psi     | ||||||
Low Engine Oil Pressure Warning Event Notification Delay Time     | 0 seconds     | ||||||
Low Engine Oil Pressure Shutdown Event Threshold     | 30 psi     | ||||||
Low Idle Low Engine Oil Pressure Shutdown Event Threshold     | 10 psi     | ||||||
Low Engine Oil Pressure Shutdown Event Notification Delay Time     | 10 seconds     | ||||||
Low Engine Oil Pressure Step Speed     | 1200 RPM     | ||||||
Engine Oil Pressure Sensor Configuration Code     | Map 1     | ||||||
Flywheel Teeth     | 136     | 183     | |||||
Engine Overspeed Setpoint     | 2120 RPM     | 1770 RPM     | 2120 RPM     | 1770 RPM     | 2120 RPM     | ||
Engine Underspeed Warning Event Threshold     | 1550 RPM     | 1290 RPM     | 1550 RPM     | 1290 RPM     | 1550 RPM     | ||
Engine Underspeed Warning Event Notification Delay Time     | 2.0 seconds     | ||||||
Engine Underspeed Shutdown Event Threshold     | 1480 RPM     | 1230 RPM     | 1480 RPM     | 1230 RPM     | 1480 RPM     | ||
Engine Underspeed Shutdown Event Notification Delay Time     | 2.0 seconds     | ||||||
Engine Speed Sensor Configuration     | Sensor     | ||||||
Engine Cylinder Temperature Sensor Installation Status     | Not Installed     | ||||||
Number of Engine Cylinders     | 12     | 16     | |||||
Generator Winding Temperature Sensor Installation Status     | Not Installed     | ||||||
Generator Bearing Temperature Sensor Installation Configuration     | Not Installed     | ||||||
    | |||||||
Event Input Function #1 Suspect Parameter Number     | Custom Event     | ||||||
Event Input Function #1 Failure Mode Identifier     | Condition Exists     | ||||||
Event Input Function #1 Event Notification Delay Time     | 0.0 seconds     | ||||||
Event Input Function #1 Active State Configuration     | High     | ||||||
Event Input Function #2 Suspect Parameter Number     | Custom Event     | ||||||
Event Input Function # 2 Failure Mode Identifier     | Condition Exists     | ||||||
Event Input Function #2 Event Notification Delay Time     | 0.0 seconds     | ||||||
Event Input Function #2 Active State Configuration     | High     | ||||||
Event Input Function #3 Suspect Parameter Number     | Custom Event     | ||||||
Event Input Function #3 Failure Mode Identifier     | Condition Exists     | ||||||
Event Input Function #3 Event Notification Delay Time     | 0.0 seconds     | ||||||
Event Input Function #3 Active State Configuration     | High     | ||||||
Event Input Function #4 Suspect Parameter Number     | Custom Event     | ||||||
Event Input Function #4 Failure Mode Identifier     | Condition Exists     | ||||||
Event Input Function #4 Event Notification Delay Time     | 0.0 seconds     | ||||||
Event Input Function #4 Active State Configuration     | High     | ||||||
Event Input Function #5 Suspect Parameter Number     | Custom Event     | ||||||
Event Input Function #5 Failure Mode Identifier     | Condition Exists     | ||||||
Event Input Function #5 Event Notification Delay Time     | 0.0 seconds     | ||||||
Event Input Function #5 Active State Configuration     | High     | ||||||
Event Input Function #6 Suspect Parameter Number     | Custom Event     | ||||||
Event Input Function #6 Failure Mode Identifier     | Condition Exists     | ||||||
Event Input Function #6 Event Notification Delay Time     | 0.0 seconds     | ||||||
Event Input Function #6 Active State Configuration     | High     | ||||||
Event Input Function #7 & #8     | Disabled     | ||||||
Event Output Functions ALL     | Disabled     | ||||||
    | |||||||
Event Warning Condition Response Auto Reset Enable Status     | Enabled     | ||||||
Event Audible Alert Response Auto Reset Enable Status     | Enabled     | ||||||
Event Loss Of Utility Response Auto Reset Enable Status     | Enabled     | ||||||
Event Breaker #1 Trip Response Auto Reset Enable Status     | Enabled     | ||||||
Event Breaker #2 Trip Response Auto Reset Enable Status     | Enabled     | ||||||
    | |||||||
Generator Connection Configuration     | Wye (or Star) Connection     | ||||||
Generator Potential Transformer Primary Winding Rating     | 1 v     | ||||||
Generator Potential Transformer Secondary Winding Rating     | 1 V     | ||||||
Generator Current Transformer Primary Winding Rating     | 3000 Amps     | 3000 Amps     | 3000 Amps     | ||||
Generator Current Transformer Secondary Winding Rating     | 5 Amps     | ||||||
Number of Generator Poles     | 4 Poles     | ||||||
Generator Rated Frequency     | 60 Hz     | 60 Hz     | 50 Hz     | 60 Hz     | 50 Hz     | 60 Hz     | 60 Hz     |
Generator Rated Voltage     | 208 V     | 240 V     | 400 V     | 480 V     | 400 V     | 480 V     | 480 V     |
Generator Rated Power     | 865 kW     | 1000 kW     | 1000 kW     | 1000 kW     | 1440 kW     | 2000 kW     | 1250 kW     |
Generator Rated Apparent Power     | 1080 kVA     | 1250 kVA     | 1250 kVA     | 1250 kVA     | 1800 kVA     | 2500 kVA     | 1563 kVA     |
Customer Password Security Level to Reset Generator Energy Meters     | 3 Factory, Single Use     | ||||||
Generator Breaker Closing Pulse Active Time     | Disabled or Not Installed     | ||||||
Generator Breaker Closing Pulse Rest Interval     | Disabled or Not Installed     | ||||||
Generator Breaker Maximum Closing Time     | Disabled or Not Installed     | ||||||
Generator Breaker Maximum Opening Time     | Disabled or Not Installed     | ||||||
Generator Breaker Lockout Configuration     | Disabled or Not Installed     | ||||||
Generator Breaker Type Configuration     | Disabled or Not Installed     | ||||||
Automatic Generator Breaker Control Source Configuration     | Disabled or Not Installed     | ||||||
Generator Definite Time Overcurrent Warning Event Percentage Threshold     | 105%     | ||||||
Generator Inverse Time Overcurrent Shutdown Event Time Multiplier     | 0.27     | ||||||
Generator Definite Time Overcurrent Shutdown Event Percentage Threshold     | 110%     | ||||||
Generator Definite Time Overcurrent Shutdown Event Notification Delay Time     | 10.0 seconds     | ||||||
Generator Over Frequency Warning Event Percentage Threshold     | 105%     | ||||||
Generator Over Frequency Warning Event Notification Delay Time     | 10 seconds     | ||||||
Generator Over Frequency Shutdown Event Percentage Threshold     | 110%     | ||||||
Generator Over Frequency Shutdown Event Notification Delay Time     | 10 seconds     | ||||||
Generator Under Frequency Warning Event Percentage Threshold     | 95%     | ||||||
Generator Under Frequency Warning Event Notification Delay Time     | 10 seconds     | ||||||
Generator Under Frequency Shutdown Event Percentage Threshold     | 90%     | ||||||
Generator Under Frequency Shutdown Event Notification Delay Time     | 15 seconds     | ||||||
Generator Over Voltage Warning Event Percentage Threshold     | 105%     | ||||||
Generator Over Voltage Warning Event Notification Delay Time     | 10 seconds     | ||||||
Generator Over Voltage Shutdown Event Percentage Threshold     | 110%     | ||||||
Generator Over Voltage Shutdown Event Notification Delay Time     | 10 seconds     | ||||||
Generator Under Voltage Warning Event Percentage Threshold     | 90%     | ||||||
Generator Under Voltage Warning Event Notification Delay Time     | 10 seconds     | ||||||
Generator Under Voltage Shutdown Event Percentage Threshold     | 85%     | ||||||
Generator Under Voltage Shutdown Event Notification Delay Time     | 15 seconds     | ||||||
Generator Reverse Power Warning Event Percentage Threshold     | 5%     | ||||||
Generator Reverse Power Warning Event Notification Delay Time     | 10 seconds     | 2 seconds     | |||||
Generator Reverse Power Shutdown Event Percentage Threshold     | 15%     | 8%     | |||||
Generator Reverse Power Shutdown Event Notification Delay Time     | 10 seconds     | 3 seconds     | |||||
Maximum Engine Speed Bias     | 400 RPM     | ||||||
Generator Nominal Output Frequency     | 60 Hz     | 60 Hz     | 50 Hz     | 60 Hz     | 50 Hz     | 60 Hz     | 60 Hz     |
    | |||||||
Programmable Cycle Timer     | Not Used     | ||||||
    | |||||||
Electronic Control Module Reduced Power Mode Enable Status     | Disabled     | ||||||
Electronic Control Module Reduced Power Mode Delay Time     | 30     | ||||||
    | |||||||
Relay Output     | High     | ||||||
    | |||||||
Maintenance Cycle     | Configured by Dealer     | ||||||
    | |||||||
Spare Analog Input Enable Status     | Enabled     | Disabled     | |||||
Spare Analog Input Type Configuration     | Level     | ||||||
Spare Analog Input Suspect Parameter Number     | Fuel Level     | ||||||
Spare Analog Input High Warning Event Percentage Threshold     | 88%     | ||||||
Spare Analog Input High Temperature Warning Event Threshold     | 216 degree F     | ||||||
Spare Analog Input High Pressure Warning Event Threshold     | 131 psi     | ||||||
Spare Analog Input High Warning Event Notification Delay Time     | 2 seconds     | ||||||
Spare Analog Input High Shutdown Event Percentage Threshold     | 90%     | ||||||
Spare Analog Input High Temperature Shutdown Event Threshold     | 225 degree F     | ||||||
Spare Analog Input High Pressure Shutdown Event Threshold     | 146 psi     | ||||||
Spare Analog Input High Shutdown Event Notification Delay Time     | 10 seconds     | ||||||
Spare Analog Input Low Warning Event Percentage Threshold     | 25%     | ||||||
Spare Analog Input Low Temperature Warning Event Threshold     | 68 degree F     | ||||||
Spare Analog Input Low Pressure Warning Event Threshold     | 15 psi     | ||||||
Spare Analog Input Low Warning Event Notification Delay Time     | 15 seconds     | ||||||
Spare Analog Input Low Shutdown Event Percentage Threshold     | 10%     | ||||||
Spare Analog Input Low Temperature Shutdown Event Threshold     | 32 degree F     | ||||||
Spare Analog Input Low Pressure Shutdown Event Threshold     | 11 psi     | ||||||
Spare Analog Input Low Shutdown Event Notification Delay Time     | 30 seconds     | ||||||
Spare Analog Input Sensor Configuration Code     | Map 1     | ||||||
    | |||||||
Programmable Trip Point Function     | Not Used     | ||||||
    | |||||||
DIO Event Input Function     | Disabled or Not Installed     | ||||||
DIO Event Output Function     | Disabled or Not Installed     | ||||||
DIO Digital Selector     | Disabled or Not Installed     | ||||||
Generator/Utility Automatic Transfer Enable Status     | Disabled or Not Installed     | ||||||
Loss of Utility Event Notification Delay Time     | Disabled or Not Installed     | ||||||
Utility to Generator Transfer Delay Time     | Disabled or Not Installed     | ||||||
Generator to Utility Transfer Delay     | Disabled or Not Installed     | ||||||
Generator to Utility Fast Transfer Delay Time     | Disabled or Not Installed     | ||||||
Utility to Generator Transfer Failure Warning Event Threshold     | Disabled or Not Installed     | ||||||
Utility to Generator Transfer Failure Shutdown Event Threshold     | Disabled or Not Installed     | ||||||
Generator to Utility Transfer Failure Warning Event Threshold     | Disabled or Not Installed     | ||||||
Generator/Utility Automatic Transfer Unpowered Load Time     | Disabled or Not Installed     | ||||||
Generator Ready to Load Threshold Percentage     | Disabled or Not Installed     | ||||||
Generator Ready to Load Delay Time     | Disabled or Not Installed     | ||||||
Generator to Utility Transfer Mode     | Disabled or Not Installed     | ||||||
Utility Breaker Closing Pulse Active Time     | Disabled or Not Installed     | ||||||
Utility Breaker Closing Pulse Rest Interval     | Disabled or Not Installed     | ||||||
Utility Breaker Maximum Closing Time     | Disabled or Not Installed     | ||||||
Utility Breaker Maximum Opening Time     | Disabled or Not Installed     | ||||||
Utility Breaker Lockout Configuration     | Disabled or Not Installed     | ||||||
Utility Breaker Type Configuration     | Disabled or Not Installed     | ||||||
Automatic Utility Breaker Control Source Configuration     | Disabled or Not Installed     | ||||||
Engine Serial Number     | Not Programmed     | ||||||
Display Pressure Units Configuration     | psi     | ||||||
Display Temperature Units Configuration     | Degrees Fahrenheit     | ||||||
Display Volume Units Configuration     | US gallons     |
Show/hide table
( 1 ) | XQ1000 without a link board will have 1600:5 CTs |
Table 2 lists diagnostic events that have a programmed response. The diagnostic response can be configured as follows:
- Warning
- Hard shutdown
- Soft shutdown
- Disable
- Active
The diagnostic response can be set to cause the following:
- Audible alert (yes/no)
- Breaker #1 trip (yes/no)
- Breaker #2 trip (yes/no)
- Fault protection timer (yes/no)
Table 2 lists the information for the programmed response. The responses be listed from left to right as diagnostic response, audible alert, breaker 1 trip, breaker 2 trip and fault protection timer. As an example, a "Soft Shutdown, Y, N, N" means the following:
- The diagnostic event will cause a soft shutdown
- An audible alert is active
- No breaker 1 trip
- No breaker 2 trip
Note: Some diagnostic events have a fifth parameter, the fault protection timer.
Show/hide table
    | XQ1000 (1)     | XQ2000     | XQ1250G     | ||||
---|---|---|---|---|---|---|---|
    | 208 V 60Hz     | 240 V 60Hz     | 400 V 50Hz     | 480 V 60Hz     | 400 V 50Hz     | 480 V 60Hz     | 480 V 60Hz     |
Diagnostic Event     | Diagnostic Response, audible alert, breaker #1 trip, breaker #2 trip, fault protection timer     | ||||||
Accessory Data Link     | Warning, N, N, N     | ||||||
Air Filter Differential Pressure Sensor     | Warning, N, N, N     | ||||||
Ambient Air Temperature Sensor     | Warning, N, N, N     | ||||||
Digital Output 1     | Warning, N, N, N     | ||||||
Digital Output 2     | Warning, N, N, N     | ||||||
Engine Coolant Level Sensor     | Warning, N, N, N     | ||||||
Engine Coolant Temperature Sensor     | Warning, N, N, N     | ||||||
Engine Oil Level Sensor     | Warning, N, N, N     | ||||||
Engine Oil Pressure Sensor     | Warning, N, N, N     | ||||||
Engine Oil Temperature Sensor     | Warning, N, N, N     | ||||||
Engine Speed Sensor     | Hard Shutdown, Y, N, N     | ||||||
Exhaust Temperature Sensor     | Warning, N, N, N     | ||||||
Right Exhaust Temperature Sensor     | Warning, N, N, N     | ||||||
Left Exhaust Temperature Sensor     | Warning, N, N, N     | ||||||
Fire Extinguisher Pressure Sensor     | Warning, N, N, N     | ||||||
Fuel Filter Differential Pressure Sensor     | Warning, N, N, N     | ||||||
Fuel Level Sensor     | Warning, N, N, N     | Disable, N, N, N     | |||||
External Tank Fuel Level Sensor     | Warning, N, N, N     | Disable, N, N, N     | |||||
Generator Bearing #1 Temperature Sensor     | Warning, N, N, N     | ||||||
Generator Output Sensing System     | Warning, N, N, N     | ||||||
Engine Oil Filter Differential Pressure Sensor     | Warning, N, N, N     | ||||||
Primary Data Link Diagnostic     | Warning, N, N, N     | ||||||
SCADA Data Link Diagnostic     | Warning, N, N, N, N     | ||||||
Starting Air Pressure Sensor     | Warning, N, N, N     | ||||||
Battery Charger Failure     | Warning, N     | ||||||
Engine Controller Not Responding     | Warning, N, N, N     | ||||||
Air Damper Closed     | Disable, N     | ||||||
High Air Filter Differential Pressure Warning     | Warning, N, N, N     | ||||||
High Air Filter Differential Pressure Shutdown     | Hard Shutdown, Y, N, N     | ||||||
Low Air Filter Differential Pressure Warning     | Warning, N, N, N     | ||||||
Low Air Filter Differential Pressure Shutdown     | Hard Shutdown, Y, N, N     | ||||||
Emergency Stop Activated     | Hard Shutdown, Y, N, N     | ||||||
High Engine Coolant Level Warning     | Warning, N, N, N, N     | ||||||
High Engine Coolant Level Shutdown     | Hard Shutdown, Y, N, N, N     | ||||||
Low Engine Coolant Level Warning     | Warning, N, N, N, N     | ||||||
Low Engine Coolant Level Shutdown     | Hard Shutdown, Y, N, N, N     | ||||||
High Engine Coolant Temperature Warning     | Warning, N, N, N, N     | ||||||
High Engine Coolant Temperature Shutdown     | Hard Shutdown, Y, N, N, N     | ||||||
Low Engine Coolant Temperature Warning     | Warning, N, N, N, N     | ||||||
Engine Failure To Start Shutdown     | Hard Shutdown, Y, N, N     | ||||||
High Engine Oil Level Warning     | Warning, N, N, N     | ||||||
High Engine Oil Level Shutdown     | Hard Shutdown, Y, N, N     | ||||||
Low Engine Oil Level Warning     | Warning, N, N, N     | ||||||
Low Engine Oil Level Shutdown     | Hard Shutdown, Y, N, N     | ||||||
Low Engine Oil Pressure Warning     | Warning, N, N, N, N     | ||||||
Low Engine Oil Pressure Shutdown     | Hard Shutdown, Y, N, N, N     | ||||||
High Engine Oil Temperature Warning     | Warning, N, N, N, N     | ||||||
High Engine Oil Temperature Shutdown     | Hard Shutdown, Y, N, N, N     | ||||||
Low Engine Oil Temperature Warning     | Warning, N, N, N, N     | ||||||
Low Engine Oil Temperature Shutdown     | Hard Shutdown, Y, N, N, N     | ||||||
Unexpected Engine Shutdown Event     | Hard Shutdown, Y, N, N     | ||||||
Engine Overspeed Shutdown     | Hard Shutdown, Y, N, N     | ||||||
Engine Underspeed Warning     | Warning, N, N, N, N     | ||||||
Engine Underspeed Shutdown     | Hard Shutdown, Y, N, N, N     | ||||||
High Exhaust Temperature Warning     | Warning, N, N, N, N     | ||||||
High Exhaust Temperature Shutdown     | Hard Shutdown, Y, N, N, N     | ||||||
Low Exhaust Temperature Warning     | Warning, N, N, N, N     | ||||||
Low Exhaust Temperature Shutdown     | Hard Shutdown, Y, N, N, N     | ||||||
High Right Exhaust Temperature Warning     | Warning, N, N, N, N     | ||||||
High Right Exhaust Temperature Shutdown     | Hard Shutdown, Y, N, N, N     | ||||||
Low Right Exhaust Temperature Warning     | Warning, N, N, N, N     | ||||||
Low Right Exhaust Temperature Shutdown     | Hard Shutdown, Y, N, N, N     | ||||||
High Left Exhaust Temperature Warning     | Warning, N, N, N, N     | ||||||
High Left Exhaust Temperature Shutdown     | Hard Shutdown, Y, N, N, N     | ||||||
Low Left Exhaust Temperature Warning     | Warning, N, N, N, N     | ||||||
Low Left Exhaust Temperature Shutdown     | Hard Shutdown, Y, N, N, N     | ||||||
High Fuel Filter Differential Pressure Warning     | Warning, N, N, N     | ||||||
High Fuel Filter Differential Pressure Shutdown     | Hard Shutdown, Y, N, N     | ||||||
Low Fuel Filter Differential Pressure Warning     | Warning, N, N, N, N     | ||||||
Low Fuel Filter Differential Pressure Shutdown     | Hard Shutdown, Y, N, N, N     | ||||||
High Fuel Level Warning     | Warning, N, N, N     | ||||||
High Fuel Level Shutdown     | Disable, N, N, N     | ||||||
Low Fuel Level Warning     | Warning, N, N, N     | ||||||
Low Fuel Level Shutdown     | Hard Shutdown, Y, N, N     | ||||||
External Tank High Fuel Level Warning     | Disable, N, N, N     | ||||||
External Tank High Fuel Level Shutdown     | Disable, N, N, N     | ||||||
External Tank Low Fuel Level Warning     | Disable, N, N, N     | ||||||
External Tank Low Fuel Level Shutdown     | Disable, N, N, N     | ||||||
Fuel Leak     | Warning, N, N, N     | ||||||
High Engine Oil Filter Differential Pressure Warning     | Warning, N, N, N     | ||||||
High Engine Oil Filter Differential Pressure Shutdown     | Hard Shutdown, Y, N, N     | ||||||
Low Engine Oil Filter Differential Pressure Warning     | Warning, N, N, N     | ||||||
Low Engine Oil Filter Differential Pressure Shutdown     | Hard Shutdown, Y, N, N     | ||||||
Service Maintenance Interval Warning     | Warning, N     | ||||||
High Starting Air Pressure Warning     | Disable, N, N, N     | ||||||
High Starting Air Pressure Shutdown     | Disable, N, N, N     | ||||||
Low Starting Air Pressure Warning     | Disable, N, N, N     | ||||||
Low Starting Air Pressure Shutdown     | Disable, N, N, N     | ||||||
High Gas Pressure Warning     | Disable, N, N, N     | ||||||
High Gas Pressure Shutdown     | Disable, N, N, N     | ||||||
Low Gas Pressure Warning     | Disable, N, N, N     | ||||||
Low Gas Pressure Shutdown     | Disable, N, N, N     | ||||||
Engine Intake Manifold Charge Combustion     | Hard Shutdown, Y, N, N, N     | ||||||
High Generator Bearing #1 Temperature Warning     | Disable, N, N, N, N     | ||||||
High Generator Bearing #1 Temperature Shutdown     | Disable, N, N, N, N     | ||||||
Low Generator Bearing #1 Temperature Warning     | Disable, N, N, N, N     | ||||||
Low Generator Bearing #1 Temperature Shutdown     | Disable, N, N, N, N     | ||||||
Generator Overcurrent Warning     | Warning, N, N, N     | ||||||
Generator Overcurrent Shutdown     | Hard Shutdown, Y, N, N     | ||||||
Generator Over Frequency Warning     | Warning, N, N, N     | ||||||
Generator Over Frequency Shutdown     | Soft Shutdown, Y, N, N     | ||||||
Generator Under Frequency Warning     | Warning, N, N, N     | ||||||
Generator Under Frequency Shutdown     | Soft Shutdown, Y, N, N     | ||||||
Generator Reverse Power Warning     | Warning, N, N, N     | ||||||
Generator Reverse Power Shutdown     | Soft Shutdown, Y, N, N     | ||||||
Generator Over Voltage Warning     | Warning, N, N, N     | ||||||
Generator Over Voltage Shutdown     | Soft Shutdown, Y, N, N     | ||||||
Generator Under Voltage Warning     | Warning, N, N, N     | ||||||
Generator Under Voltage Shutdown     | Soft Shutdown, Y, N, N     | ||||||
Earth Fault     | Hard Shutdown, Y, N, N     | ||||||
Generator Winding #1 High Temperature Warning     | Disable, N, N, N, N     | ||||||
Generator Winding #2 High Temperature Warning     | Disable, N, N, N, N     | ||||||
Generator Winding #3 High Temperature Warning     | Disable, N, N, N, N     | ||||||
Generator Winding #1 High Temperature Shutdown     | Hard Shutdown, Y, N, N, N     | ||||||
Generator Winding #2 High Temperature Shutdown     | Hard Shutdown, Y, N, N, N     | ||||||
Generator Winding #3 High Temperature Shutdown     | Hard Shutdown, Y, N, N, N     | ||||||
Generator High Power Warning     | Warning, N, N, N     | ||||||
High Ambient Air Temperature Warning     | Warning, N, N, N, N     | ||||||
High Ambient Air Temperature Shutdown     | Hard Shutdown, Y, N, N, N     | ||||||
Low Ambient Air Temperature Warning     | Warning, N, N, N, N     | ||||||
Low Ambient Air Temperature Shutdown     | Hard Shutdown, Y, N, N, N     | ||||||
Automatic Transfer Switch In Normal     | Disable, N     | ||||||
Automatic Transfer Switch In Emergency     | Disable, N     | ||||||
High Battery Voltage Warning     | Warning, N, N, N     | ||||||
High Battery Voltage Shutdown     | Soft Shutdown, Y, N, N     | ||||||
Low Battery Voltage Warning     | Warning, N, N, N     | ||||||
Low Battery Charging System Voltage Warning     | Disable, N, N, N     | ||||||
Generator Breaker Failure To Open     | Disable, N, N, N     | ||||||
Generator Breaker Failure To Close     | Disable, N, N, N     | ||||||
Generator Breaker Open     | Active, N     | ||||||
Generator Breaker Closed     | Active, N     | ||||||
Utility Breaker Failure To Open     | Disable, N, N, N     | ||||||
Utility Breaker Failure To Close     | Disable, N, N, N     | ||||||
Utility Breaker Open     | Disable, N     | ||||||
Utility Breaker Closed     | Disable, N     | ||||||
Emergency Shutdown Override Mode     | Warning, N     | ||||||
Engine In Cooldown     | Active, N     | ||||||
Engine Speed-Generator Output Freq Mismatch     | Warning, N, N, N     | ||||||
High Fire Extinguisher Pressure Warning     | Disable, N, N, N     | ||||||
High Fire Extinguisher Pressure Shutdown     | Disable, N, N, N     | ||||||
Low Fire Extinguisher Pressure Warning     | Disable, N, N, N     | ||||||
Low Fire Extinguisher Pressure Shutdown     | Disable, N, N, N     | ||||||
Generator Control Not in Automatic Warning     | Warning, N     | ||||||
Generator Breaker Locked Out Warning     | Disable, N, N, N     | ||||||
Utility Breaker Locked Out Warning     | Disable, N, N, N     | ||||||
Loss of Utility Event     | Disable, N     | ||||||
Utility to Generator Transfer Failure Warning     | Disable, N, N, N     | ||||||
Utility to Generator Transfer Failure Shutdown     | Disable, N, N, N     | ||||||
Generator to Utility Transfer Failure Warning     | Disable, N, N, N     | ||||||
Earth Leakage     | Hard Shutdown, Y, N, N     | ||||||
Utility Breaker System Fault     | Disable, N, N, N     | ||||||
Emergency Power System Supplying Load     | Active, N     | ||||||
Low Cranking Voltage Warning     | Warning, N, N, N     | ||||||
Custom Event #1 High Warning     | Disable, N, N, N     | ||||||
Custom Event #1 High Shutdown     | Disable, N, N, N     | ||||||
Custom Event #1 Low Warning     | Disable, N, N, N     | ||||||
Custom Event #1 Low Shutdown     | Disable, N, N, N     | ||||||
Custom Event #1 Condition Exists     | Disable, N, N, N     | ||||||
Custom Event #2 High Warning     | Disable, N, N, N     | ||||||
Custom Event #2 High Shutdown     | Disable, N, N, N     | ||||||
Custom Event #2 Low Warning     | Disable, N, N, N     | ||||||
Custom Event #2 Low Shutdown     | Disable, N, N, N     | ||||||
Custom Event #2 Condition Exists     | Hard Shutdown, Y, N, N     | ||||||
Custom Event #3 High Warning     | Disable, N, N, N     | ||||||
Custom Event #3 High Shutdown     | Disable, N, N, N     | ||||||
Custom Event #3 Low Warning     | Disable, N, N, N     | ||||||
Custom Event #3 Low Shutdown     | Disable, N, N, N     | ||||||
Custom Event #3 Condition Exists     | Soft Shutdown, Y, N, N     | ||||||
Custom Event #4 High Warning     | Disable, N, N, N     | ||||||
Custom Event #4 High Shutdown     | Disable, N, N, N     | ||||||
Custom Event #4 Low Warning     | Disable, N, N, N     | ||||||
Custom Event #4 Low Shutdown     | Disable, N, N, N     | ||||||
Custom Event #4 Condition Exists     | Disable, N, N, N     | ||||||
Custom Event #5 High Warning     | Disable, N, N, N     | ||||||
Custom Event #5 High Shutdown     | Disable, N, N, N     | ||||||
Custom Event #5 Low Warning     | Disable, N, N, N     | ||||||
Custom Event #5 Low Shutdown     | Disable, N, N, N     | ||||||
Custom Event #5 Condition Exists     | Disable, N, N, N     | ||||||
Custom Event #6 High Warning     | Disable, N, N, N     | ||||||
Custom Event #6 High Shutdown     | Disable, N, N, N     | ||||||
Custom Event #6 Low Warning     | Disable, N, N, N     | ||||||
Custom Event #6 Low Shutdown     | Disable, N, N, N     | ||||||
Custom Event #6 Condition Exists     | Disable, N, N, N     | ||||||
Custom Event #7 & #8 ALL     | Disable, N, N, N, N     | ||||||
DIO1 Custom Events     | Disable, N, N, N, N     | ||||||
DIO2 Custom Events     | Disable, N, N, N, N     | ||||||
DIO3 Custom Events     | Disable, N, N, N, N     | ||||||
DIO4 Custom Events     | Disable, N, N, N, N     |
Show/hide table
( 1 ) | XQ1000 without a link board will have 1600:5 CTs |
Caterpillar Information System:
XQ Auto Paralleling Default Settings for Engine Electronic Control Module
XQ Auto Paralleling Default Settings for Generator Paralleling Control
XQ Auto Paralleling Default Settings for Mode of Operation
XQ Auto Paralleling Generator Load Connections
XQ Auto Paralleling Handling
XQ Auto Paralleling Installation
XQ Auto Paralleling Initial Startup Procedure
3516C Locomotive Engines Selective Catalytic Reduction Module - Disassemble
3512C Oil Well Service Engines Product Lifting
120 and 120 AWD Motor Grader Drawbar Ball and Socket End Play - Check/Adjust
2010/12/06 A New Injector Wiring Harness Kit Is Available to Make Repairs on Certain Commercial Engines {1254, 1290, 1408}
2011/01/10 A New Wiring Harness Kit Is Available in Order to Make Repairs on Certain Truck Engines {1254, 1290, 1408}
XQ Auto Paralleling Storage
XQ Auto Paralleling Default Settings for Discrete Input/Output Module
XQ Auto Paralleling Receiving Inspection
XQ Auto Paralleling Default Settings for Cat Digital Voltage Regulator
XQ Auto Paralleling Advanced Control Jumpers
XQ Auto Paralleling Power Module Controls - Check
G3306B Gas Engines Fuel Filter
C7.1 Industrial Engine Diagnostic Flash Code Retrieval
2010/09/01 Changes to the Usage and Cleaning of the Contamination Monitor Group {0645, 0680, 1280, 1348, 3080, 429F, 5095}
3500B and 3500C Marine Propulsion Engines E048 Backup ECM Took Control
C27 and C32 Engines for Caterpillar Built Machines Exhaust Cooler (NRS) - Remove and Install
2010/08/26 Service Tips for the Hydraulic Electronic Unit Injector HEUI Pump {1714}