XQ Auto Paralleling Caterpillar


Default Settings for Generator Paralleling Control

Usage:

PMG3516 KAD

Generator Paralleling Control (GPC) Default Settings

Table 1
Parameter     XQ1000     XQ2000     XQ1250G    
208V, 60Hz 240V, 60Hz     400V, 50Hz     480V, 60Hz     400V, 50Hz     480V, 60Hz     480V, 50Hz    
CONFIGURE GENERAL PARAMETERS    
SPRACHE/LANGUAGE     English     English     English     English     English     English     English    
Software Version     N/A     N/A     N/A     N/A     N/A     N/A     N/A    
Enter Code     0001/0002     0001/0002     0001/0002     0001/0002     0001/0002     0001/0002     0001/0002    
Password Protection     On     On     On     On     On     On     On    
Direct Parameter     Yes     Yes     Yes     Yes     Yes     Yes     Yes    

Table 2
Parameter     XQ1000     XQ2000     XQ1250G    
208V, 60Hz 240V, 60Hz     400V, 50Hz     480V, 60Hz     400V, 50Hz     480V, 60Hz     480V, 50Hz    
CONFIGURE BASIC SETTINGS    
Rated Frequency fn     60 Hz     60 Hz     50.0 Hz     60 Hz     50.0 Hz     60 Hz     60 Hz    
Generator freq. Set point     60 Hz     60 Hz     50.0 Hz     60 Hz     50.0 Hz     60 Hz     60 Hz    
Gen. voltage secondary     120V     120V     100 V     120V     100 V     120V     120V    
Mains voltage secondary     120V     120V     100 V     120V     100 V     120V     120V    
Gen. voltage primary     .208 kV     .240 kV     .400 kV     .480 kV     .400 kV     .480 kV     .480 kV    
Mains voltage primary     .208 kV     .240 kV     .400 kV     .480 kV     .400 kV     .480 kV     .480 kV    
Rated voltage Vn     120V     120V     100 V     120V     100 V     120V     120V    
Gen. voltage Set point     120V     120V     100 V     120V     100 V     120V     120V    
Current transf. Generator     3000/5     3000/5     3000/5 (1)     3000/5 (1)     3000/5     3000/5     3000/5    
Connection type Gen.     1W2     1W2     1W2     1W2     1W2     1W2     1W2    
Angle adjustment Gen. Current     000°     000°     000°     000°     000°     000°     000°    
Rated power Gen.     865 kW     1000 kW     1000 kW     1000 kW     1440 kW     2000 kW     1250 kW    
( 1 ) XQ1000 without a link board will have 1600:5 CTs

Table 3
Parameter     XQ1000     XQ2000     XQ1250G    
208V, 60Hz 240V, 60Hz     400V, 50Hz     480V, 60Hz     400V, 50Hz     480V, 60Hz     480V, 50Hz    
CONFIGURE CONTROLLER    
Automatic idle - Running     Off     Off     Off     Off     Off     Off     Off    
Terminal #6     Set Point Power     Set Point Power     Set Point Power     Set Point Power     Set Point Power     Set Point Power     Set Point Power    
f control type     PWM     PWM     PWM     PWM     PWM     PWM     Analog    
f control output Level PWM     10.0 V     10.0 V     10.0 V     10.0 V     10.0 V     10.0 V     10.0 V    
PWM signal Logic     positive     positive     positive     positive     positive     positive     positive    
f control output Init. state     50%     50%     50%     50%     50%     50%     45%    
Freq. controller     On     On     On     On     On     On     On    
Freq. controller Isolated oper.     Off     Off     Off     Off     Off     Off     On    
Freq. controller Ramp.     5.0 Hz/s     5.0 Hz/s     5.0 Hz/s     5.0 Hz/s     5.0 Hz/s     5.0 Hz/s     5.0 Hz/s    
f control output (max.)     85%     85%     85%     85%     85%     85%     100%    
f control output (min.)     55%     55%     55%     55%     55%     55%     0%    
Freq. controller Gain Kp     10     10     10     10     10     10     21    
Freq. controller Reset Tn     3.0 s     3.0 s     3.0 s     3.0 s     3.0 s     3.0 s     18.0 s    
Freq. controller Derivate.Tv     0.00 s     0.00 s     0.00 s     0.00 s     0.00 s     0.00 s     0.50 s    
V control type     Analog     Analog     Analog     Analog     Analog     Analog     Analog    
V control output     +/-10 V     +/-10 V     +/-10 V     +/-10 V     +/-10 V     +/-10 V     +/-10 V    
V control output Init. state     50%     50%     50%     50%     50%     50%     50%    
Volt. controller     On     On     On     On     On     On     On    
Volt. Controller Isolation operation     Off     Off     Off     Off     Off     Off     On    
Volt. controller Ramp     15V/Sec     15V/Sec     15V/Sec     15V/Sec     15V/Sec     15V/Sec     15V/Sec    
V control output (max.)     100%     100%     100%     100%     100%     100%     100%    
V control output (min.)     0%     0%     0%     0%     0%     0%     0%    
Volt. controller Gain Kp     30     30     30     30     15     15     30    
Volt. controller Reset Tn     4.1 s     4.1 s     4.1 s     4.1 s     2.5 s     2.5 s     3.0 s    
Volt. controller Derivate.Tv     0.0 s     0.0 s     0.0 s     0.0 s     0.0 s     0.0 s     0.0 s    
Power factor control     On     On     On     On     On     On     On    
Power factor controls set point     i0.95     i0.95     i0.95     i0.95     i0.95     i0.95     i0.95    
Power factor control Ramp     0.01 / s     0.01 / s     0.01 / s     0.01 / s     0.01 / s     0.01 / s     0.01 / s    
Power factor control Gain Kp     15     15     15     15     15     15     15    
Power factor control Reset Tn     2.5 s     2.5 s     2.5 s     2.5 s     2.5 s     2.5 s     2.5 s    
Power factor control Derivate.Tv     0.02 s     0.02 s     0.02 s     0.02 s     0.02 s     0.02 s     0.02 s    
Power controller     On     On     On     On     On     On     On    
Power controller P max     92%     92%     92%     92%     92%     92%     92%    
Power controller P min     5%     5%     5%     5%     5%     5%     5%    
Warm up load Set point     5%     5%     5%     5%     5%     5%     5%    
Warm up load time     000 s     000 s     000 s     000 s     000 s     000 s     000 s    
Download and open GCB     ON     ON     ON     ON     ON     ON     ON    
Power controller "P set 1 ="     790 kW     910 kW     910 kW     910 kW     1310 kW     1825 kW     1250 kW    
Power controller "P set2 ="     N/A     N/A     N/A     N/A     N/A     N/A     N/A    
Power set point External     On     On     On     On     On     On     On    
Analog input     4 - 20 mA     4 - 20 mA     4 - 20 mA     4 - 20 mA     4 - 20 mA     4 - 20 mA     0 - 20 mA    
External set point 0mA, 4mA     0 kW     0 kW     0 kW     0 kW     0 kW     0 kW     0 kW    
External set point 20mA     790 kW     910 kW     910 kW     910 kW     1310 kW     1825 kW     1250 kW    
Power controller Ramp     10 kW/s     10 kW/s     10 kW/s     10 kW/s     10 kW/s     10 kW/s     10 kW/s    
Power controller Gain Kp     7     7     7     7     7     7     11    
Power controller Reset Tn     2.5 s     2.5 s     2.5 s     2.5 s     2.5 s     2.5 s     60.0 s    
Power controller Derivate.Tv     0.02 s     0.02 s     0.02 s     0.02 s     0.02 s     0.02 s     0.00 s    
Generator active power Monitoring     Off     Off     Off     Off     Off     Off     Off    
Active power Load share     On     On     On     On     On     On     On    
Active load share Factor     30%     30%     30%     30%     30%     30%     10%    
Reactive power Load share (2)     Off     Off     Off     Off     Off     Off     Off    
Reactive load share Factor     50%     50%     50%     50%     50%     50%     50%    
( 2 ) Turn on and off reactive power load share as needed for site configuration.

Table 4
Parameter     XQ1000     XQ2000     XQ1250G    
208V, 60Hz 240V, 60Hz     400V, 50Hz     480V, 60Hz     400V, 50Hz     480V, 60Hz     480V, 50Hz    
CONFIGURE SYNCHRONIZATION    
Synchronizing functions     On     On     On     On     On     On     On    
Synchronization df max     0.1 Hz     0.1 Hz     0.1 Hz     0.1 Hz     0.1 Hz     0.1 Hz     0.1 Hz    
Synchronization df min     -0.05 Hz     -0.05 Hz     -0.05 Hz     -0.05 Hz     -0.05 Hz     -0.05 Hz     -0.02 Hz    
Synchronization dV max     2V     2V     2V     2V     2V     2V     2V    
Synchronization "Breaker hold T>"     0.5s     0.5s     0.5s     0.5s     0.5s     0.5s     0.5s    
Phase matching     On     On     On     On     On     On     On    
Phase matching "Max phase <"     10 °     10 °     10 °     10 °     10 °     10 °     10 °    
Phase matching dwell time     0.5 s     0.5 s     0.5 s     0.5 s     0.5 s     0.5 s     0.5 s    
Phase matching gain     5     5     5     5     5     5     4    
Phase matching df start     0.2 Hz     0.2 Hz     0.2 Hz     0.2 Hz     0.2 Hz     0.2 Hz     0.1 Hz    

Table 5
Parameter     XQ1000     XQ2000     XQ1250G    
208V, 60Hz 240V, 60Hz     400V, 50Hz     480V, 60Hz     400V, 50Hz     480V, 60Hz     480V, 50Hz    
CONFIGURE SYNCHRONIZATION TIME    
Synchronization time control     Off     Off     Off     Off     Off     Off     Off    

Table 6
Parameter     XQ1000     XQ2000     XQ1250G    
208V, 60Hz 240V, 60Hz     400V, 50Hz     480V, 60Hz     400V, 50Hz     480V, 60Hz     480V, 50Hz    
CONFIGURE DEAD BUS    
Gen. circ.break. Dead bus op.     ON     ON     ON     ON     ON     ON     ON    
Dead bus op. GCB df max     0.25 Hz     0.25 Hz     0.25 Hz     0.25 Hz     0.25 Hz     0.25 Hz     0.25 Hz    
Dead bus op. GCB dV max     12V     12V     12V     12V     12V     12V     12V    

Table 7
Parameter     XQ1000     XQ2000     XQ1250G    
208V, 60Hz 240V, 60Hz     400V, 50Hz     480V, 60Hz     400V, 50Hz     480V, 60Hz     480V, 50Hz    
CONFIGURE WATCHDOGS    
Reverse/min.pow. Monitoring     Off     Off     Off     Off     Off     Off     Off    
Gen. overload Monitoring     Off     Off     Off     Off     Off     Off     Off    
Gen.frequency- Monitoring     Off     Off     Off     Off     Off     Off     Off    
Gen.voltage- Monitoring     Off     Off     Off     Off     Off     Off     Off    
Auto-acknowledge Messages     On     On     On     On     On     On     On    
Acknowledge Message aft.     3s     3s     3s     3s     3s     3s     3s    

Table 8
Parameter     XQ1000     XQ2000     XQ1250G    
208V, 60Hz 240V, 60Hz     400V, 50Hz     480V, 60Hz     400V, 50Hz     480V, 60Hz     480V, 50Hz    
CONFIGURE PASSWORDS    
Define level #1 code     n/a     n/a     n/a     n/a     n/a     n/a     n/a    
Define level #2 code     5712     5712     5712     5712     5712     5712     5712    

Caterpillar Information System:

XQ Auto Paralleling Default Settings for Mode of Operation
XQ Auto Paralleling Generator Load Connections
XQ Auto Paralleling Handling
XQ Auto Paralleling Installation
XQ Auto Paralleling Initial Startup Procedure
3516C Locomotive Engines Selective Catalytic Reduction Module - Disassemble
3512C Oil Well Service Engines Product Lifting
120 and 120 AWD Motor Grader Drawbar Ball and Socket End Play - Check/Adjust
2010/12/06 A New Injector Wiring Harness Kit Is Available to Make Repairs on Certain Commercial Engines {1254, 1290, 1408}
2011/01/10 A New Wiring Harness Kit Is Available in Order to Make Repairs on Certain Truck Engines {1254, 1290, 1408}
3512C Oil Well Service Engines Safety Messages
120 and 120 AWD Motor Grader Drawbar Ball and Socket - Lubricate
XQ Auto Paralleling Default Settings for Engine Electronic Control Module
XQ Auto Paralleling Default Settings for Electronic Modular Control Panel
XQ Auto Paralleling Storage
XQ Auto Paralleling Default Settings for Discrete Input/Output Module
XQ Auto Paralleling Receiving Inspection
XQ Auto Paralleling Default Settings for Cat Digital Voltage Regulator
XQ Auto Paralleling Advanced Control Jumpers
XQ Auto Paralleling Power Module Controls - Check
G3306B Gas Engines Fuel Filter
C7.1 Industrial Engine Diagnostic Flash Code Retrieval
2010/09/01 Changes to the Usage and Cleaning of the Contamination Monitor Group {0645, 0680, 1280, 1348, 3080, 429F, 5095}
3500B and 3500C Marine Propulsion Engines E048 Backup ECM Took Control
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.