Troubleshooting for the Hydraulic System
- "The AccuGrade system will not engage in automatic mode and the hydraulics icon is flashing with a bar through the icon."
- "Poor Performance"
Note: TheAccuGrade system is programmed to disengage from the auto mode if the machine implements are not moved in 60 seconds and the machine is in neutral.
- The parking brake is on.
- Disengage the parking brake.
- Electrical system fault
- Use Caterpillar Electronic Technician (ET) in order to check for any system faults.
- Check the Caterpillar Monitoring System for any system faults.
- Check the display for the AccuGrade system for any system faults.
Reference: Refer to the Troubleshooting, "Determining Detected Faults (Display)" for more information.
- The lockout for the hydraulic system is engaged on the M-Series Motor Grader.
- Disengage the lockout for the hydraulic system.
- The operator is not in the seat on a M-Series Motor Grader.
- Return to the seat.
- The software enabled attachment has not been turned on for the M-Series Motor Grader.
Reference: Refer to Special Instruction, REHS3253, "Installation of the AccuGrade 2D System for Motor Graders".
- Improper setting of the valve speed.
Reference: Refer to Testing and Adjusting , "Blade Reaction Time - Adjust (Valve Speed)" for more information on this procedure.
- The valves have been improperly calibrated.
Note: Ensure that the calibration for the solenoids on the machine has been completed before performing the valve calibration for the AccuGrade system on a M-Series Motor Grader.
Reference: Refer to Testing and Adjusting , "Linked Elevation (Dual Mast) - Calibrate" and Testing and Adjusting , "Bank (Grade Control) - Calibrate" for more information on this procedure.
- Improper setup for the laser transmitter
Reference: Refer to Operation and Maintenance, SEBU8276, "Laser Transmitter Setup Information (Dual Mast System)" for more information on setup of the laser transmitter.
- Improper setup of the laser receiver
Reference: Refer to Operation and Maintenance, SEBU8276, "Startup (Dual Mast System)" for more information on the setup of the laser receiver.
- There is excessive air in the hydraulic system.
- Bleed the air from the hydraulic system.
- Operating conditions are not suitable for the AccuGrade system.
Reference: Refer to Operation and Maintenance, SEBU8276, "General Information" for more information on usage of the AccuGrade - Grade Control System.
- Hydraulic oil temperature is too low.
- Warm up the machine's hydraulic oil.