Configuring the Active Power Control (APC) Parameter for the Uninterruptible Power Supply ( UPS ){4480} Caterpillar


Configuring the Active Power Control (APC) Parameter for the Uninterruptible Power Supply ( UPS ){4480}

Usage:

UPS 250 APZ
Uninterruptible Power Supply:
UPS 120 (S/N: CNK102-UP)
ES12F (S/N: CZE217-UP)
UPS 1000S (S/N: CZS110-UP)
UPS 1200S (S/N: CZT131-UP)
UPS 150 (S/N: CPC130-UP)
UPS 250 (S/N: CNM240-UP; APZ350-UP)
UPS 300 (S/N: CNJ430-UP; CPZ371-UP)
UPS 500 (S/N: CSE155-UP)
UPS 600 (S/N: CTX319-UP)
UPS 750 (S/N: CPM172-UP)
UPS 900 (S/N: CRY381-UP)

Introduction

This Special Instruction provides information about configuring the Active Power Control (APC) operating parameter that is called "APC Not Configured". The "APC Not Configured" operating parameter was not used previously.

The operating parameter will be set to "1" as the default. The default setting of "1" means that the APC will not be configured when the unit is shipped from the factory. Due to this change, a service technician will need to contact Caterpillar in order to obtain a "engineering level password". The password is required for the starting procedure of the unit and in order to change the operating parameter.

Important Safety Information

Work safely. Most accidents that involve product operation, maintenance, and repair are caused by failure to observe basic safety rules or precautions. An accident can often be avoided by recognizing potentially hazardous situations before an accident occurs.

A person must be alert to potential hazards. This person should also have the necessary training, skills, and tools in order to perform these functions properly.

Safety precautions and warnings are provided in this instruction and on the product. If these hazard warnings are not heeded, bodily injury or death could occur to you or to other persons. Caterpillar cannot anticipate every possible circumstance that might involve a potential hazard.

Therefore, the warnings in this publication and the warnings that are on the product are not all inclusive. If a tool, a procedure, a work method, or operating technique that is not specifically recommended by Caterpillar is used, ensure that it is safe for you and for other people to use.

Ensure that the product will not be damaged or the product will be made unsafe by the operation, lubrication, maintenance, or the repair procedures that are used.

Connect a Personal Computer (PC) to the UPS

The following instructions explain the process in order to establish a serial connection from a PC to the UPS.

Single Module System (SMS)

  1. Place the system in a de-energized state. Refer to the shutdown procedure that is in Systems Operation Testing and Adjusting, RENR2476, "SMS System Shutdown".

  1. Open the left cabinet door (2) and the right (3) cabinet door.

    Refer to Illustration 1 and Illustration 2.




    Illustration 1g01798433

    System Cabinet

    (1) Bypass, Input, and 0utput Cabinet

    (2) System Cabinet User Interface

    (3) System Cabinet




    Illustration 2g01806594

    Doors Removed from the System Cabinet

    (6) Parallel Cabinet Interface Board

    (7) AC Interface Board

    (8) Transformer T3

    (9) System Input/Output Isolation Board

  1. Connect a PC to the RS232/RS485 "J1" port (18) that is located on the System Input/Output and Isolation Board. Refer to Illustration 3.

    Note: Ensure that jumper "Jmp 1" (17), that is located on the System Input/Output and Isolation Board, is in the correct position. The lower side must be used for RS232 applications and the higher side must be used for RS485 applications. Refer to Illustration 3 and Illustration 4.




    Illustration 3g02891719

    System Input/Output and Isolation Board

    (11) "J6" "Remote Output Contacts"

    (12) "J7" "Remote Input Contacts"

    (13) "J14" "Remote EPO Contacts"

    (14) "J2" "ACP I/O"

    (15) "J3" "ACP I/O"

    (16) "J4" "24 VDC Power In"

    (17) "Jmp 1" "RS232/RS485"

    (18) "J1" "RS-232/RS-485"

    (19) "J12" "CAN B"

    (20) "J8""UPSNET/CAN A"

    (21) "J9" "Ethernet"

    (22) "J10""Modem"




    Illustration 4g01799600

    (17) "Jmp 1" "RS232/RS485"

  1. Refer to the following "Common" section for more instructions.

Multiple Module Unit (MMU)

  1. Place the system in a de-energized state. Refer to the shutdown procedure that is in Systems Operation Testing and Adjusting, RENR2476, "MMS System Shutdown".



    Illustration 5g01807475

    (30) Bypass, Input, and 0utput Cabinet

    (31) System Cabinet

    (32) MMU1 Cabinet

    (33) MMU2 Cabinet

    (34) MMUX Cabinet

  1. Connect a PC (35) to the "Parallel Cabinet Interface" (PCI) board (6). The PCI board (6) is located in the system cabinet. Refer to Illustration 2 and to Illustration 6.



    Illustration 6g01820775

    (6) Parallel Cabinet Interface (PCI) Board

    (35) PC Cable Connected to the PCI) Board

  1. Place the CSView/UPSView selector switch (40) to the required position for the desired MMU.



    Illustration 7g01799553

  1. Refer to the following "Common" section for more instructions.

Common

  1. Energize the system according to the "SMS System Startup" or the "MMS System Startup" procedures that are in Systems Operation Testing and Adjusting, RENR2476.

  1. Turn on the PC.

  1. Double click the CSView/UPSView icon that is on the PC desktop in order to start the CSView/UPSView software.

  1. Click "PC Settings" on the menu bar. A drop-down menu will appear.

  1. Click "Settings". The "CSView/UPS View Connection Settings" dialog will open.

  1. Select the "Direct Connect (serial)" button.

  1. Select the PC COM port for the serial connection. Check the baud rate. The "Detailed MMU telemetry" button must be checked.

  1. Select the "Serial/Modem Port Number" that is appropriate for the PC.

  1. Select the desired "Serial/Modem Baud Rate". The default baud rate is 38400.

  1. Ensure that the "Detailed Telemetry" button is selected.

  1. Click the "OK".

  1. Click "Connection" on the menu bar. A drop-down menu will appear.

  1. Click "Connect". The PC should now be connected to the UPS. Telemetry signals will not be available until the "APC Not Configured" parameter is set to "0" (zero). Information that is stored in the text log will be displayed.

  1. Press "Ctrl+F" in order to access the serial number and the "seed value" information.

    Note: In order to obtain a "engineering level password", the technical communicator must be provided with the following information.

    • MMU serial number

    • Seed value

    • Confirmation that the system been stored at an ambient temperature of 15° C (59° F) or higher for at least the last 72 hours

    • Confirmation that the system was installed while the ambient temperature was 15° C (59° F) or higher for at least the last 72 hours

    • Confirmation that the power to the flywheel (armature and field coils) has been turned off for the last 72 hours

  1. Once a connection is established, click "Enter Password" on the menu bar. The "Enter User Name/Password" dialog will appear. Refer to Illustration 8.



    Illustration 8g01801533

  1. Enter a "User Name". Enter a "Password".

  1. Click "OK". After the "User Name" and the "Password" have been accepted by the UPS, then the menu bar will change to include "Op. Params.", "Calibrate", and "Clear Password".

  1. Place the mouse pointer for the PC over "Op. Params." in order to access the drop-down menu options for "Op. Params.". Select the "System Config" group. A drop-down menu will appear for the "System Config" group. Click the "APC Not configured" parameter. Refer to Illustration 9.



    Illustration 9g01801534

  1. The "Request Operating Parameter Change" dialog will open. Refer to Illustration 10.



    Illustration 10g01801535

  1. Set the "APC Not configured" parameter value to "0".

  1. Click "Apply". Click "OK".

  1. Press "CTRL-R" in order to reset the processor.

  1. Press "Y" in order to acknowledge the reset of the processor.

Caterpillar Information System:

345D, 349D and 349D2 Excavators and 345D MHPU, 349D MHPU and 349D2 MHPU Mobile Hydraulic Power Units Machine Electronic Control System System Operation
390D Excavator Machine System Specifications Track
345D, 349D and 349D2 Excavator Machine System Specifications Main Control Valve
C175-16 and C175-20 Engines for Off-Highway Trucks Histogramming
345D, 349D and 349D2 Excavators and 345D MHPU, 349D MHPU and 349D2 MHPU Mobile Hydraulic Power Units Machine Electronic Control System General Information
2009/01/26 Pushrods {1102, 1121, 1123, 1209}
390D Excavator Machine System Specifications Sprocket
3516C Generator Set Engines Engine Mount
C27 and C32 Generator Set Engines Fan Drive
3516C Generator Set Engines Water Lines
3500 Engines Water Lines
C7 Engines for Combat and Tactical Vehicles Noise from Injectors with Keyswitch ON
2009/01/26 An Operating Parameter Is Now Required During Start-up {4480}
345D MHPU and 349D MHPU Mobile Hydraulic Power Units Machine System Return Lines (Boom Lowering Control)
3500 Engines for Caterpillar Built Generator Sets Fuel Injector
349F and 352F Excavators Machine System Specifications Counterweight Cylinder
G3508B, G3512B, G3512B, G3516B and G3520B Petroleum Engines Accumulator - Remove
C27 and C32 Generator Sets Belts - Inspect/Adjust/Replace
345D, 349D and 349D2 Excavators and 345D MHPU, 349D MHPU and 349D2 MHPU Mobile Hydraulic Power Units Machine Electronic Control System Diagnostic Operation
793F Off-Highway Truck Braking System - Test
G3508B, G3512B, G3512B, G3516B and G3520B Petroleum Engines Accumulator - Install
2009/02/09 A New Connecting Rod Bearing is Available {1218, 1219, 1225}
G3516 Petroleum Engines Accumulator - Disassemble
345D, 349D and 349D2 Excavator Machine System Specifications Counterweight Lifting Chain
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.