Illustration 1 | g01277292 |
Controls Cabinet Left Panel (17) Breaker and Contactor Status Board (18) Remote EPO Terminal Block (19) T8 Modem Power Transformer (20) T6 Transformer (21) General Purpose Interface Board (22) Fan Power Fuse Block (23) Fuses F29-F32 (24) Fuses F20-F22 (25) Fuses F25-F28 (26) EPO Reset (27) Neutral Distribution Terminal (28) K1 Motor Power Relay (K9) |
Illustration 2 | g01277295 |
Controls Cabinet Back Panel (29) Customer Contacts Interface Board #2 (Optional) (30) DC Bus Pre-charge Circuit Resistors (31) T1 - T4 Transformers (32) Power Supply Board (PWS) (33) Customer Contacts Interface Board #1 (34) Power Supply Board (PWS) (35) Thermistor (36) Fuse F69 (37) Fuses F88-F90 F70-F72 (38) Zig-Zag Transformer (39) K7 Pre-charge Contactor (40) K6 Pre-charge Contactor |
Illustration 3 | g01277491 |
Controls Cabinet AC Capacitor Fuses (41) AC Filter Fuses (F34-F36) (42) AC Filter Fuses (F37-F39) |
Illustration 4 | g01277564 |
Controls Cabinet Left Panel Fuse Wire Connections |
Refer to Systems Operation, Testing and Adjusting, "General Information (Controls Cabinet)" for the location of the left panel in the cabinet. Refer to Systems Operation, Testing and Adjusting, "General Information (Controls Cabinet)" for the locations of the rear panel in the cabinet. Refer to Illustration 1 for the location of the fuse blocks on the left panel. Refer to Illustration 2 for the location of the fuse blocks on the rear panel. Refer to Illustration 4 and Illustration 4 for specific fuse locations.
There is also a set of fuses for the three fans in the system. These fuses are located on the left panel to the right of the System Fuse Block for F25-F28. Refer to Illustration 1 for the fan fuse location.
Control Cabinet System Fuses     | ||
---|---|---|
Fuse     | Amperes     | Protects     |
F20     | 30     | High Voltage AC Output via Wire Way for CSHV Control Power     |
F21     | 30     | High Voltage AC Output via Wire Way for CSHV Control Power     |
F22     | 30     | High Voltage AC Output via Wire Way for CSHV Control Power     |
F25     | 1     | T5 Secondary - T8 External Modem. Optional.     |
F26     | 1     | K11 Zig-Zag Relay 230 in the Static Switch cabinet     |
F27     | 10     | T6 Secondary - Control Cabinet Fans and Fan Fuse Block     |
F28     | 10     | T6 Secondary - BCS (J4-3 via SW1) 230V Control Power in Controls Cabinet     |
F29     | 7     | T6 Transformer     |
F30     | 7     | T6 Transformer     |
F31     | 12     | T7 Transformer     |
F32     | 12     | T7 Transformer     |
F34     | 200     | AC Filter Capacitors Bank 1 Phase A     |
F35     | 200     | AC Filter Capacitors Bank 1 Phase B     |
F36     | 200     | AC Filter Capacitors Bank 1 Phase C     |
F37     | 200     | AC Filter Capacitors Bank 2 Phase A     |
F38     | 200     | AC Filter Capacitors Bank 2 Phase B     |
F39     | 200     | AC Filter Capacitors Bank 2 Phase C     |
F69     | 10     | Two PWS Boards 24Vdc (J8-1) in Controls Cabinet     |
F70     | 8     | Zig-Zag Transformer Phase A in Controls Cabinet     |
F71     | 8     | Zig-Zag Transformer Phase B in Controls Cabinet     |
F72     | 8     | Zig-Zag Transformer Phase C in Controls Cabinet     |
F88     | 3     | DC Bus Pre-charge Circuit Resistors Phase A     |
F89     | 3     | DC Bus Pre-charge Circuit Resistors Phase B     |
F90     | 3     | DC Bus Pre-charge Circuit Resistors Phase C     |
Controls Cabinet Fan Fuses     | ||
---|---|---|
Fuse     | Amperes     | Protects     |
CC-TB1-F1     | 3.15     | Fan 1 (Left)     |
CC-TB1-F2     | 3.15     | Fan 2 (Middle)     |
CC-TB1-F3     | 3.15     | Fan 3 (Right)     |
Illustration 5 | g01277563 |
Controls Cabinet Rear Panel Fuse Wire Connections |
Illustration 6 | g01277576 |
AC Filter Capacitor Fuse Wire Connections |