Illustration 1 | g01276193 |
(1) EPO Reset Switch |
The Emergency Power Off (EPO) reset switch is located behind the locked left door of the MMU cabinet or Flywheel cabinet.
The switch resets the functionality of the Emergency Power Off after the following events occur:
- The Emergency Power Off button on the front door has been pushed.
- The system is shutdown.
The EPO reset breaker disconnects 230 VAC from the system in order for the circuit breaker "K3" to close.
This switch is attached to the board for the AC Interface (ACI) that is located on the left panel.
Refer to Systems Operation, Testing and Adjusting, RENR9988, "Internal Component Preremoval Steps (Flywheel Cabinet)" in order to shut down the system and gain access to internal components.
- Check the labeling of the wires to the EPO reset switch (1). Verify the labeling on the wires to the EPO reset switch (1).
- Disconnect the wires from the EPO reset switch (1).
- Remove the EPO reset switch (1) from the metal bracket that connects the switch to the left panel. Compress the rear tabs and orient the "ON" to the top. Pull the switch straight through the hole in the front of the bracket.
Illustration 2 | g01272344 |
Wire Connections of the "Style 1" EPO Reset Switch |
Illustration 3 | g01272343 |
Wire Connections of "Style 2" EPO Reset Switch |
There are two styles of reset switch that are present in the flywheel cabinet. Refer to Illustration 2 and Illustration 3 for the appropriate wire diagram.
- Attach the EPO reset switch (1) to the metal bracket that connects the switch to the left panel.
- Connect the wires to the back of the EPO reset switch (1).