UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Caterpillar


System Fuse (Static Switch Cabinet)

Usage:

ES12F CZE



Illustration 1g01344725

Static Switch Left Panel

(1) Fan Fuses F1-F3

(2) Fuse Block F23, F24

(3) Zig-Zag Circuit Breaker K13

(4) Zig-Zag Overload Relay K11

(5) Zig-Zag Transformer

The Static Switch Cabinet contains the control power fuses for the power coming to the Static Switch Cabinet. The left panel of the cabinet holds one two-fuse block. Additionally, there are seven fuses at the bottom of the cabinet. Refer to Illustration 1 for the location of the left panel in the cabinet.




Illustration 2g01275357

Bottom Panel Fuse Location (Static Switch Cabinet)

(6) Fuse Block, F4-F6, F13-F16

Refer to Illustration 2 for the locations of the fuses at the bottom of the cabinet. Refer to Illustration 1 for the location of the fuses on the left panel. Refer to Illustration 3 for specific fuse locations.

There is also a set of fuses for the three fans in the system. These fuses are located on the left panel above the System Fuse Block for F23 and F24. Refer to Illustration 1 for the fan fuse location.

Table 1
Static Switch Cabinet System Fuses    
Fuse     Amperes     Protects    
F4     1     HVI Output Voltage Phase A (J6-11)    
F5     1     HVI Output Voltage Phase B (J6-4)    
F6     1     HVI Output Voltage Phase C (J6-7)    
F13     2.5     T3 Transformer in the Controls cabinet    
F14     2.5     T3 Transformer in the Controls cabinet    
F15     2.5     T4 Transformer in the Controls cabinet    
F16     2.5     T4 Transformer in the Controls cabinet    
F23     10     T5 Secondary - Static Switch Fans and Fan Fuse Block    
F24     10     T5 Secondary - BCS (J4-1 via SW1) 230V Control Power in CC    

Table 2
Static Switch Cabinet Fan Fuses    
Fuse     Type     Protects    
F1     SLO BLO, 3.15 AMPS, 1500A     Fan 1 (Left)    
F2     SLO BLO, 3.15 AMPS, 1500A     Fan 2 (Middle)    
F3     SLO BLO, 3.15 AMPS, 1500A     Fan 3 (Right)    



Illustration 3g01275420

Caterpillar Information System:

UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Internal Component Preremoval Steps (Static Switch Cabinet)
TH48-E80 Petroleum Transmission Burn Prevention
G3600 Engines Exhaust Bypass Valve
C27 Industrial Engine and C27 Locomotive Engine Fuel System - Prime
TA19-M2WD and TA19-M4WD Agricultural Transmissions Relief Valve (Charge Pressure)
TA19-M2WD and TA19-M4WD Agricultural Transmissions Modulating Valve
TA22-4WD Agricultural Transmission Transmission Clutch
TA22-4WD Agricultural Transmission Pressure for Transmission Lubrication - Test
TA19-M2WD and TA19-M4WD Agricultural Transmissions General Troubleshooting Information
TA19-M2WD and TA19-M4WD Agricultural Transmissions Operational Checks
SPF343 and SPF343C Trailer Mounted Pumpers Fuel System Primary Filter (Water Separator) Element - Replace
3500 Generator Sets with Dynamic Gas Blending Engine Speed/Timing Sensor - Clean/Inspect
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Universal Static Switch Interface PWA
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Static Switch
Machine Start Switch Key May Not Fit Properly{1416} Machine Start Switch Key May Not Fit Properly{1416}
G3600 Engines Aftercooler
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Snubber Assembly
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Zig Zag Circuit Breaker
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Zig Zag Overload Relay
C9 On-highway Engine Valve Actuator
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Zig Zag Transformer
C280 Marine Auxiliary Engines System Configuration Parameters
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Current Transformer (Static Switch Cabinet)
C7 On-Highway Engine Camshaft - Remove
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.