UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Caterpillar


MOV Circuit Breaker (K10)

Usage:

ES12F CZE



Illustration 1g01342924

MOV Circuit Breaker, Rear Panel

(1) MOV Surge Protector

(2) MOV Circuit Breaker (K10)

(3) Wire Terminal

The MOV Circuit Breaker (K10) is located on the back panel of the Input/Output cabinet beneath the input cable landings.

The MOV Circuit Breaker is a 480V 30A breaker that monitors input current and will trip if the MOV Surge Protector pulls more than 30A, thus protecting the MOV.

If the MOV Circuit Breaker trips, the breaker will send a signal to the General Purpose Interface Board on the J7 connector in the Static Switch cabinet. There is no action taken from this signal.

Removal

  1. Perform steps in the Systems Operation, Testing and Adjusting, "Internal Component Preremoval Steps (Input/Output Cabinet)" in order to de-energize the system and gain access to internal components.



    Illustration 2g01274320

    Circuit Breaker, Top View




    Illustration 3g01274323

    MOV Circuit Breaker Attachment and Connections




    Illustration 4g01274330

    MOV Circuit Breaker Attachments

  1. Disconnect wires leading to and from the circuit breaker.

    The locations of the wires are labeled. Verify the labels on the cables for subsequent reinstallation. The wires are removed by inserting, through the front of the breaker, a small flat head screwdriver and unscrewing the wire terminals located at the top and bottom of the breaker. Refer to Illustration 4.

  1. Disconnect the two wires from the wire terminal above the breaker. Refer to Illustration 3.

  1. Remove the four screws that secure the breaker to the rear of the cabinet.

    Refer to Illustration 4.

Installation




    Illustration 5g01274330

    MOV Circuit Breaker Attachments

  1. Attach the MOV Circuit Breaker to the back of the cabinet in the position that is indicated in Illustration 1. Use four long cross tip screws to attach the circuit breaker, one at each corner. Refer to the locations of the screws in Illustration 4.

  1. Connect the two violet and black wires coming from the back of the circuit breaker to the wire terminal above the breaker.

    Refer to Illustration 3.

  1. Connect the wires coming from the MOV surge protector to the top of the breaker. Additionally, connect the wires coming from the cable landings to the bottom of the breaker. The wires locations have been labeled. Refer to Illustration 3 and the following steps.

  1. Unscrew each cable connector screw, using a small flat head screwdriver, through the front of the breaker. Refer to Illustration 3.

  1. Insert the wire into the following locations:

    • the top of the breaker or the bottom of the breaker

    • between the connector plates

  1. Tighten the cable connector screws in order to hold the wires in place.

Caterpillar Information System:

CD44B and CD54B Vibratory Asphalt Compactors High Pressure Fuel Lines
C18 Petroleum Generator Sets Cooling System Coolant (ELC) - Change
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Circuit Breaker (K1, K5)
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Cable Landing (Input/Output Cabinet)
C15 and C18 Petroleum Generator Sets Fuel System Primary Filter/Water Separator - Drain
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Breaker Bell Alarm Supervisor Board
TH48-E70 Petroleum Transmission Specifications
C11 and C13 Petroleum Engines Fuel System Secondary Filter - Replace
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Reset Pushbutton
797F Off-Highway Truck Steering System Steering Accumulator
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys System Fuse (Input/Output Cabinet)
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Internal Component Preremoval Steps (Input/Output Cabinet)
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Service Tools
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys MOV Surge Protector
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Discharge Resistor
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys External Source Sync PWA (Input/Output Cabinet)
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Storage
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys External Source Sync Terminal Block
3508 EUI Engine for Off-Highway Truck/Tractors Gear Group (Rear)
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Gen Set Module Circuit Breaker
UPS 120, UPS 150, UPS 250 and UPS 300 Uninterruptible Power Supplies Vacuum Pump Startup - Required Procedure After Extended Storage
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys 4 Wire Transformer Sensors
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Capacitor (Input/Output Cabinet)
G3600 Engines Fuel Lines
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.