UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Caterpillar


Transformer (Maintenance Bypass Cabinet)

Usage:

ES12F CZE
Three transformers supply the controllers and auxiliary contacts of the Maintenance Bypass circuit breaker, the Maintenance Bypass Controller Board, the Maintenance Bypass Power Supply Board and other cabinet components.

Transformer (T9) and Transformer (T10) are 480V/230V transformers. Transformer (T9) feeds the Maintenance Bypass Controller Board from the input of the Maintenance Bypass Controller Board. Transformer (T10) feeds the Maintenance Bypass Controller Board from the system output in the System Input/Output Cabinet. Transformer (T11) is a 480V/21V transformer that supplies the Maintenance Bypass Board.

The transformers are installed on a panel on the top right side of the cabinet.




Illustration 1g01337685

Right Panel (Maintenance Bypass Cabinet) Components

(1) Transformer (T9)

(2) Transformer (T10)

(3) Transformer (T11)

(4) Fuse Block F52-F54, F57, F67, F68

The thermistors for Transformer (T9) and Transformer (T11) are located on the upper side of the transformer, as installed. The thermistor for Transformer (T10) is located on the bottom side of the transformer, as installed. All thermistors are connected to the "H1" connector of the transformer.

The Thermistors limit the in-rush of current on power-up.

Table 1
Thermistor Specifications    
    Size     Ohm    
Transformer (T9)     35mm     10    
Transformer (T10)     35mm     10    
Transformer (T11)     32mm     20    

Table 2
Transformer Specifications    
    Input (V)     Output (V)     Wire Gauge (AWG)    
Transformer (T9)     380, 400, 415, 440, 480     230     10-22    
Transformer (T10)     380, 400, 415, 440, 480     230     10-22    
Transformer (T11)     380, 400, 415, 440, 480     21     H=12-22 X=10-18    

Thermistor Removal

  1. Perform steps in the Systems Operation, Testing and Adjusting, "Internal Component Preremoval Steps (Maintenance Bypass Cabinet)" in order to de-energize the system and gain access to internal components.

  1. Loosen the two screws and pull the thermistor free of the terminal block. Each thermistor is attached by two screws to the transformer terminal block. One to the "H1" connector and one to the "COM", or unlabeled connector.

Thermistor Installation

  1. Loosen the screw of the "H1" connector and the "COM" or the adjacent unlabeled connector.

  1. Place one lead of the thermistor (5) into the "H1" connector and place one lead into the "COM" connector next to the "H1" connector.

  1. Tighten the screws to attach the thermistor (5) firmly.

Transformer Removal

  1. Perform steps in the Systems Operation, Testing and Adjusting, "Internal Component Preremoval Steps (Maintenance Bypass Cabinet)" in order to de-energize the system and gain access to internal components.

  1. Remove all four wires or wire pairs from the transformer by loosening the screws holding the wires in the terminal block.

  1. Remove the 4 hex screws at the corners of the transformer that hold the transformer to the cabinet panel. Use a 76 mm (3/16 inch) hex key.

Transformer Installation




Illustration 2g01273641

MBP Transformers

  1. Situate the transformer in position on the right cabinet panel as indicated in Illustration 2.

  1. Attach the transformer using 4 hex bolts to the right panel.

    Use a 76 mm (3/16 inch) hex key.

  1. Connect the four wires or wire pairs to the transformer.

    Each wire location is labeled. Transformer (T9) and Transformer (T10) will connect with wires labeled "COM". These wires are connected to the underside of the unlabeled connector next to "H1".

Caterpillar Information System:

UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Time Delay Relay
2006/06/01 New Connecting Rod and Main Bearings {1203, 1218, 1230}
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Remote Input/Output Dry Contact - Setup
2006/05/29 Radiator pedestal on 1104C-TAG engines: Smaller engine mounting holes for improved accuracy of the fan position in the radiator cowl. {1353}
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Maintenance Power Supply PWA
C7 and C9 On-Highway Engines Engine Monitoring Parameters
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Ethernet - Configure
2006/06/01 Do Not Reuse the Hold Down Bolts for the Fuel Injector {1290}
2014/08/14 Do Not Reuse the Hold Down Bolts for the Fuel Injectors On All Products that Contain C9 Through C32 Engines {1290}
2006/05/29 Do Not Reuse the Hold Down Bolts for the Fuel Injector {1290}
C4.4 Industrial Engine Air Inlet and Exhaust System - Inspect
Filtration Procedure for Transmission Oil on Motor Graders Without Ecology Drain {0680, 0768, 3030} Filtration Procedure for Transmission Oil on Motor Graders Without Ecology Drain {0680, 0768, 3030}
TA19-M2WD and TA19-M4WD Agricultural Transmissions Transmission Oil Sample - Obtain
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Cable Landing (Maintenance Bypass Cabinet)
C9 Engine for Caterpillar Built Machines Camshaft - Remove
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Emergency Power Off - Reset
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Remote Notification - Setup
C9 Engine for Caterpillar Built Machines Camshaft - Install
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Circuit Breaker (Maintenance Bypass Cabinet)
TA22-4WD Agricultural Transmission Capacities (Refill)
2006/05/22 Revised Product Support Update {0374}
C4.4 Industrial Engine Alternator - Test
C4.4 Industrial Engine Crankshaft Pulley - Check
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Modem - Configure
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.