Illustration 1 | g01275261 |
View of the 4-Wire Zig Zag Transformer (1) Zig Zag Transformer |
Illustration 2 | g01275262 |
View of the 3-Wire Zig Zag Transformer Rear Panel (2) Zig Zag Transformer |
The Zig Zag Transformer (T5) is located on the floor of the MMS System Cabinet in a 4-wire installation. The Zig Zag Transformer (T5) is located on the rear panel in a 3-wire installation.
The transformer is required for establishing the neutral point of the UPS 3-phase output when the following conditions occur:
- discharge mode of the system
- disconnection of the utility input
Removal Procedure and Installation Procedure for the Zig Zag Transformer (T5)
NOTICE |
---|
Removal of the Zig Zag Transformer (T5) and installation of the Zig Zag Transformer (T5) are not field service procedures. Contact your Caterpillar technical support. |
Each of the three Zig Zag transformer cables has a 1500:5 current transformer (CT) installed on each of the cables. The CTs are located at the bottom of the cabinet in a 4-wire installation. The current transformers relay the flywheel telemetry to the board for the Zig Zag Controller.