Flywheel Operating Parameters
Flywheel Operating Parameters
Flywheel Common Operating Parameters
DEFAULT VALUES ARE FOR GENERAL INFORMATION ONLY. ACTUAL DEFAULTS MAY DIFFER DEPENDING ON SYSTEM CONFIGURATIONS, INSTALLATION SITES AND LOCAL CODES. CHECK EACH INDIVIDUAL UNIT FOR PROPER DEFAULTS.
Show/hide table
Name     | Min     | Max     | Default     | 50 Hz Default     | Modify from GUI?     | Definitions     |
DC Regulation Voltage     | 200     | 1125     | 735     | 685     | Yes     | Sets the DC bus voltage during discharge.     |
DC Hi Volt Shutdown     | 500     | 1125     | 1125     | 1125     | No     | Sets the high DC bus voltage shutdown level.     |
DC Low Volt Shutdown     | 200     | 1125     | 600     | 550     | No     | Sets the low DC bus voltage shutdown level.     |
Motor Ramp Down Factor     | 0     | 10     | 5     | 5     | No     | Defines the end-of-motoring ramp-down. A lower number produces a faster ramp down (steeper step unload) at the end of motoring.     |
Number Of Flywheel Cabinets     | 1     | 4     | 2     | 2     | No     | (Product configuration parameter) Defines the number of Flywheel Cabinets of the UPS system.     |
Def. Data Log Rate     | 1     | 7200     | 600     | 600     | Yes     | Sets the time in seconds that telemetry will be written to the UPS View data log files if a computer is connected.     |
Flywheel Unique Operating Parameters
Show/hide table
Vacuum Warning Enable     | 0     | 1     | 0     |     | Yes     | Determines whether the vacuum warning message is green (0) or yellow (1)     |
A,B: Mtring Bearing Force     | 100     | 650     | 350     |     | No     | Sets the amount of magnetic lifting force that is applied to the rotor of the flywheel when the flywheel is being motored.     |
Vac. Sensor on Top FW     | 0     | 1     | 1     |     | No     | Indicates which flywheel interface PWA (FWI) has the vacuum sensor connected to which flywheel.     |
Stndalne. Avl. Charg. Cur     | 10     | 1000     | 200     |     | No     | This parameter is no longer valid.     |
ALT Stdaln Avl. Chrg. Cur     | 10     | 465     | 330     |     | No     | This parameter is no longer valid.     |
CS View Baud Rate     | 9600     | 115200     | 38400     |     | Yes     | Set the UPSView serial baud rate for the Flywheel Cabinet service port.     |
Internal CAN Enable     | 0     | 1     | 0     |     | No     | Enables the CAN network which is used for communication between APCs. (UPS and Flywheel Cabinets) This parameter should always be set to "1".     |
Internal CAN Node ID     | 1     | 4     | 1     |     | No     | Sets the unique network number for each Flywheel Cabinet. Each Flywheel Cabinet requires a unique ID and should be numbered sequentially from 1 to the total (2,3,4) number of Flywheel Cabinets in the UPS system.     |
CSNet Enable     | 0     | 1     | 1     |     | No     | Enables the UPSNet network which is used for communication between APCs. (UPS and Flywheel Cabinets) This parameter should always be set to "1".     |
Disable + or -15V PS Check     | 0     | 1     | 0     |     | No     | Disables the 15 vdc power supply checking. Newer APCs have some enhanced power supply checks. This checks may need disabled on older APCs     |
[A,B]:Load Cell Serial Num.     | 0     | 100000 0000     |
0     |     | No     | This number comes from the load cell certificate and is unique to each load cell.     |
[A,B]:Load Cell Cal. Factor     | 1.8     | 2.2     | 2     |     | No     | This number comes from the load cell certificate and is unique to each load cell.     |
[A,B]:Load Cell Offset     | -0.9     | 0.9     | 0     |     | No     | This number comes from the load cell certificate and is unique to each load cell.     |
Caterpillar Information System:
C9 Engine for Caterpillar Built Machines Vibration Damper and Pulley - Remove and Install
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Current Transformers (Primary, Secondary)
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies System Voltage - Calibrate
C9 Engine for Caterpillar Built Machines Flywheel Housing - Remove and Install
C11 and C13 Engines for Caterpillar Built Machines Inlet Manifold - Remove
C11 and C13 Engines for Caterpillar Built Machines Inlet Manifold - Install
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Transformer (T12 to T16 )
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Controller Board Battery - Replace
SPF343 and SPF343C Trailer Mounted Pumpers Air Shutoff - Replace
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Thermal Switch Monitor PWA
3500 Generator Sets with Dynamic Gas Blending Air Shutoff - Test
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys General Purpose Interface PWA (4 Wire Transformer Cabinet)
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys UPS Messages
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Graphical User Interface Messages
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Flywheel Messages
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys UPS View Commands and Hot Keys
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Fan (4 Wire Transformer Cabinet)
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys External Source Sync PWA (4 Wire Transformer Cabinet)
TA19-M2WD and TA19-M4WD Agricultural Transmissions Transmission - Assemble
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies General Information (Cabinet Hardware)
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Door
C280 Marine Auxiliary Engines System Overview
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Door Pull and Retaining Ring
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Door Latch