UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Caterpillar


Transfer to Bypass Mode (MMS)

Usage:

UPS 250 APZ

MMS Internal and Maintenance Bypass

------ WARNING! ------

When servicing or repairing electric power generation equipment:

  • Make sure the unit is either locked out or tagged DO NOT OPERATE.

  • Remove all fuses.

  • Make sure the generator engine is stopped.

  • Make sure all batteries are disconnected.

  • Make sure all capacitors are discharged.

  • Make sure residual voltage in the rotor, stator and the generator is discharged.

Failure to do so could result in personal injury or death.


System Internal Bypass Procedure

The system Internal bypass is used when the following is required:

The system needs to use voltage to regulate the power to the load but not protect the load in a utility outage.

  1. Turn the key switch to BYPASS position at the system cabinet.

  2. Turn the key switch to BYPASS position at the MMUs.

The system is now in BYPASS.



Illustration 1g01272005

(1) LCD display

(2) Key switch

System Configurations for Maintenance Bypass

Follow the instructions in the system configuration for the proper machine.

Single Input without Switches

Refer to Systems Operation, Testing and Adjusting, RENR9988, "Single Input without Switches".

Dual Input with Two Switches

Refer to Systems Operation, Testing and Adjusting, RENR9988, "Dual Input with Two Switches".

Dual Input with Three Switches

Refer to Systems Operation, Testing and Adjusting, RENR9988, "Dual Input with Three Switches".

Single Input with Three Switches

Refer to Systems Operation, Testing and Adjusting, RENR9988, "Single Input with Three Switches".

Dual Input with NO Switches

Refer to Systems Operation, Testing and Adjusting, RENR9988, "Dual Input with No Switches".

Caterpillar Information System:

UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Front Door Status Indicator Panel
C15 On-Highway Engine Air Inlet and Exhaust System - Inspect
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys System Fuse (4 Wire Transformer Cabinet)
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys UPS Operating Parameters
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Transfer to Bypass Mode (SMS)
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Flywheel Bearing - Replace
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies AC Interface PWA (MMS System Cabinet)
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Power Distribution PWA (MMS System Cabinet)
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Parallel Cabinet Interface PWA
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Parallel Cabinet Controller PWA
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Fan Monitor PWA (MMS System Cabinet)
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies EPO Reset Switch (MMS System Cabinet)
2006/10/09 New Test Kits for the Coolant {1395}
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys General Purpose Interface PWA (4 Wire Transformer Cabinet)
3500 Generator Sets with Dynamic Gas Blending Air Shutoff - Test
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Thermal Switch Monitor PWA
SPF343 and SPF343C Trailer Mounted Pumpers Air Shutoff - Replace
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Controller Board Battery - Replace
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Transformer (T12 to T16 )
C11 and C13 Engines for Caterpillar Built Machines Inlet Manifold - Install
C11 and C13 Engines for Caterpillar Built Machines Inlet Manifold - Remove
C9 Engine for Caterpillar Built Machines Flywheel Housing - Remove and Install
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies System Voltage - Calibrate
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Current Transformers (Primary, Secondary)
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.