UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Caterpillar


System Fuse (4 Wire Transformer Cabinet)

Usage:

ES12F CZE

Version 1 Hardware

The fan plenum holds the fuses that protect the following devices: fans, transformers and boards in the cabinet.




Illustration 1g01271923

4-Wire Transformer Cabinet System Fuse Location - Version 1 Hardware

(1) Fuses F73-F76 F94, F95

(2) Fuses F73-F76 F94, F95

(3) Fuses F96, F97

Refer to Illustration 1 for the location of the fuses on the fan plenum that is located above the fans in the cabinet.




Illustration 2g01271958

4-Wire Transformer Cabinet Fuse Wire Connections - Version 1 Hardware

(1) Fuses F73-F76 F94, F95

(2) Fuses F73-F76 F94, F95

(3) Fuses F96, F97

Wire diagrams for fuses are shown in Illustration 2.

Table 1
Fuse     Amperes     Protects    
F58     1     ESS Board Output Volts A (ESS Option only)    
F59     1     ESS Board Output Volts B (ESS Option only)    
F60     1     ESS Board Output Volts C (ESS Option only)    
F61     1     ESS Board Output Volts A    
F62     1     ESS Board Output Volts B    
F63     1     ESS Board Output Volts C    
F73     3     T12 Transformer    
F74     3     T12 Transformer COM    
F75     3     T13 Transformer    
F76     3     T13 Transformer COM    
F94     3     T14 Transformer    
F95     3     T14 Transformer COM    
F96     2.5     T15 Transformer    
F97     2.5     T15 Transformer COM    

Version 2 Hardware

The top panel holds the fuses that protect the fans, transformers, and Boards in the cabinet.




Illustration 3g01271926

4-Wire Transformer Cabinet System Fuse Location - Version 2 Hardware

(4) Fuses F73-F76 F94, F95 F104,105

(5) Fuses F96, F97

(6) Fuses F61-F63 F103

(7) Fuses F64-F66

Refer to Illustration 3 for the location of the fuses on the fan plenum located above the fans in the cabinet.




Illustration 4g01271961

4-Wire Transformer Cabinet Fuse Wire Connections - Version 2 Hardware

(4) Fuses F73-F76 F94, F95 F104,105

(5) Fuses F96, F97

(6) Fuses F61-F63 F103

(7) Fuses F64-F66

Wire diagrams for fuses are shown in Illustration 4.

Table 2
Fuse     Amperes     Protects    
F61     1     ESS Board Output Volts A    
F62     1     ESS Board Output Volts B    
F63     1     ESS Board Output Volts C    
F64     1     ESS Board Sync Volt. In A (ESS Option only)    
F65     1     ESS Board Sync Volt. In B (ESS Option only)    
F66     1     ESS Board Sync Volt. in C (ESS Option only)    
F73     2     T12 Transformer    
F74     2     T12 Transformer COM    
F75     2     T13 Transformer    
F76     2     T13 Transformer COM    
F94     2     T14 Transformer    
F95     2     T14 Transformer COM    
F96     2.5     T15 Transformer    
F97     2.5     T15 Transformer COM    
F103     1     ESS Board Neutral    
F104     2     T16 Transformer    
F105     2     T16 Transformer COM    

Caterpillar Information System:

UPS 1000S/ UPS 1200S Uninterruptible Power Supplys UPS Operating Parameters
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Transfer to Bypass Mode (SMS)
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Flywheel Bearing - Replace
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies AC Interface PWA (MMS System Cabinet)
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Power Distribution PWA (MMS System Cabinet)
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Parallel Cabinet Interface PWA
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Parallel Cabinet Controller PWA
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Fan Monitor PWA (MMS System Cabinet)
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies EPO Reset Switch (MMS System Cabinet)
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies General Purpose Interface PWA (MMS System Cabinet)
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys 4 Wire Transformer
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Internal Component Preremoval Steps (4 Wire Transformer Cabinet)
C15 On-Highway Engine Air Inlet and Exhaust System - Inspect
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Front Door Status Indicator Panel
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Transfer to Bypass Mode (MMS)
2006/10/09 New Test Kits for the Coolant {1395}
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys General Purpose Interface PWA (4 Wire Transformer Cabinet)
3500 Generator Sets with Dynamic Gas Blending Air Shutoff - Test
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Thermal Switch Monitor PWA
SPF343 and SPF343C Trailer Mounted Pumpers Air Shutoff - Replace
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Controller Board Battery - Replace
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Transformer (T12 to T16 )
C11 and C13 Engines for Caterpillar Built Machines Inlet Manifold - Install
C11 and C13 Engines for Caterpillar Built Machines Inlet Manifold - Remove
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.