UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Caterpillar


General Information (4 Wire Transformer Cabinet)

Usage:

ES12F CZE
The 4-Wire Transformer Cabinet is needed in applications when a 4-wire utility service is required.

The 4-Wire Transformer Cabinet transforms the 3-wire utility input and flywheel discharge output to a 4-wire service.

Cabinet Description

The 4-Wire Transformer Cabinet is an optional 42-inch wide cabinet that is located to the left of the Maintenance Bypass Cabinet, if the Maintenance Bypass Cabinet is present in the system. If the Maintenance Bypass Cabinet is not present, the 4-Wire Transformer Cabinet will be located to the left of the Input/Output Cabinet.

The 4-Wire Transformer Cabinet contains a large transformer that has a 4-wire Wye output.

There are two versions of the 4-wire cabinet hardware:

  • Version 1

  • Version 2

Locate and identify the proper hardware installation steps and images for the cabinet version on which you are working.

Hardware Version 1

The left panel of the 4-Wire Transformer Cabinet contains the T12 and T13 fan control power transformers.

The right panel contains the T14 and T15 control power transformers. The T14 transformer is used to power fan number three and the T15 transformer is used to power the 4-Wire Thermal Switch Monitor Board that is located on the fan plenum shield.

The three fans are located at the bottom of the cabinet and located above is the fan plenum shield.

The fan plenum shield contains three boards, the secondary current transformers, and the system fuses.

The following boards are on the fan plenum shield: General Purpose Interface Board, External Source Sync Board and 4-Wire Thermal Switch Monitor Board.

Hardware Version 2

The top section of the 4-Wire Transformer Cabinet contains the T12 to T16 control power transformers.

The T12, T13, T14, and T16 control power transformers are used to power the four fans at the bottom of the cabinet. The T15 transformer is used to Power the 4-Wire Thermal Switch Monitor Board that is located on the top panel.

The top panel contains three boards, the secondary current transformers, and the system fuses.

The three boards on the top panel are the General Purpose Interface Board, the External Source Sync Board and the 4-Wire Thermal Switch Monitor Board.

Both

The General Purpose Interface Board receives data from the fan speed sensors and the temperature thermistors on the 4-Wire Transformer.

The External Source Sync Board digitizes the transformer output voltage and currents and sends it to the APC2 controller for monitoring purposes. There is also an additional voltage feedback that is used for the external source sync option.

Note: In a UPS configuration with a 3-wire output, the External Source Sync Board option is located in the Input/Output Cabinet.

The Thermal Switch Monitor Board takes inputs thermal switches that are located on the 4-Wire Transformer and illuminates the Over Temperature Notice Indicator on the front door of the cabinet. The Thermal Switch Monitor Board also has customer contacts that are wired to a terminal strip that is located in the 4-Wire Output Cabinet for thermal fault monitoring.

The locations of the following components are in the upper part of the cabinet: 3-Wire Input Bus Bars, 4-Wire Output Bus Bars and Primary Current Transformers.

The primary voltage for the transformer, either from the UPS source or from the discharging flywheels, enters the cabinet from the right side bus bars and connects to the three inputs of the 4-Wire Transformer at the rear of the cabinet.

The secondary voltage of the transformer exits the 4-Wire Transformer from the three outputs at the front of the Transformer. There is one for each phase (A, B, and C).

The four outputs bus bars that are located in the front of the cabinet pass through the left side of the cabinet into the 4-Wire Output Cabinet.

Cabinet Diagrams

4-Wire Transformer Cabinet (Version 1)




Illustration 1g01271508

4-Wire Transformer Cabinet - Front Doors - Version 1 and 2 Hardware

(1) Front Door Status Indicator

(2) Air Filters

(3) Ground




Illustration 2g01271510

4-Wire Transformer Cabinet - Left View - Version 1

(6) Left Panel

(7) 4-Wire Transformer

(8) Ground

(9) Fans

(10) Fan Plenum Panel




Illustration 3g01271512

4-Wire Transformer Cabinet - Right View - Version 1

(7) 4-Wire Transformer

(9) Fans

(10) Fan Plenum Panel

(11) Right Panel




Illustration 4g01271514

4-Wire Transformer Cabinet Left Panel - Version 1




Illustration 5g01271517

4-Wire Transformer Cabinet Right Panel - Version 1




Illustration 6g01271519

4-Wire Transformer Cabinet Fan Plenum Panel - Version 1

(16) General Purpose Interface Board

(17) External Source Sync Board

(18) 4-Wire Thermal Switch Monitor Board

(19) Fuses F96, F97

(20) Secondary Current Transformers (CTs)

(21) Fuses F58-F60 (ESS) F61-F63

(22) Fuses F73-F76, F94, F95

4-Wire Transformer Cabinet - (Version 2)




Illustration 7g01271508

4-Wire Transformer Cabinet - Front Doors - Version 1 and 2 Hardware

(25) Front Door Status Indicator

(26) Air Filters

(27) Ground




Illustration 8g01271521

4-Wire Transformer Cabinet - No Doors - Version 2

(30) Top Panel

(31) Front Shield

(32) Ground

(33) Fans




Illustration 9g01271522

4-Wire Transformer Cabinet - Right View - Version 2

(33) Fans

(34) Transformers T12-T16

(35) 4-Wire Transformer (behind shield)




Illustration 10g01271523

4-Wire Transformer Cabinet Upper Panel - Version 2 Hardware

(16) General Purpose Interface Board

(17) External Source Sync Board

(18) 4-Wire Thermal Switch Monitor Board

(19) Fuses F96, F97

(20) Secondary Current Transformers (CTs)

(41) Fuses F61-F63 F103

(42) Fuses F73-F76, F94, F95, F104,105

(43) Fuses F64-F66

Caterpillar Information System:

UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Front Panel Display (MMS System Cabinet)
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Thermal Switch Terminal Block
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys UPS Shutdown
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Terminal Block (ESS)
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies System Fuses (MMS System Cabinet)
C13 On-highway Engine Connecting Rod Bearing Journal
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Cable Landing (4 Wire Output Cabinet)
3044C Industrial Engine Fuel Shutoff
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Capacitor (4 Wire Output Cabinet)
3044C Industrial Engine After Starting Engine
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Internal Component Preremoval Steps (MMS System Cabinet)
VR6 Or K65-12B Voltage Regulators Require An External Jumper Wire When Used With A Permanent Magnet Generator{4467} VR6 Or K65-12B Voltage Regulators Require An External Jumper Wire When Used With A Permanent Magnet Generator{4467}
TA22-4WD Agricultural Transmission Plate Locations and Film Locations
G3408C and G3412C Engines Accumulator
G3408C and G3412C Engines Accumulator Pressure - Test
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Specifications
G3408C and G3412C Engines Accumulator
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Internal Component Preremoval Steps (4 Wire Transformer Cabinet)
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys 4 Wire Transformer
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies General Purpose Interface PWA (MMS System Cabinet)
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies EPO Reset Switch (MMS System Cabinet)
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Fan Monitor PWA (MMS System Cabinet)
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Parallel Cabinet Controller PWA
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Parallel Cabinet Interface PWA