UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Caterpillar


Internal Component Preremoval Steps (4 Wire Output Cabinet)

Usage:

ES12F CZE
Note: These steps are defined for electrical high risk maintenance of the cabinet components that are located behind the locked doors. Follow these steps before performing maintenance on internal components. Shutting down all inputs to the UPS for this operation is necessary. Typically the shutdown will necessitate de-energizing the customer load.

  1. Brake the flywheel.

    Brake the flywheel if the unit is going to be shut down over 20 minutes. Simultaneously press the "Ctrl" key and the "X" key on a PC that is connected to the UPS through UPS View.

  1. Shut down the UPS.

    The UPS needs shut down before any work is done to the cabinet. Refer to the information in the Systems Operation, Testing and Adjusting, "UPS Shutdown".

    ------ WARNING! ------

    When servicing or repairing electric power generation equipment:

    • Make sure the unit is either locked out or tagged DO NOT OPERATE.

    • Remove all fuses.

    • Make sure the generator engine is stopped.

    • Make sure all batteries are disconnected.

    • Make sure all capacitors are discharged.

    • Make sure residual voltage in the rotor, stator and the generator is discharged.

    Failure to do so could result in personal injury or death.

    ----------------------

    ------ WARNING! ------

    When servicing or repairing electric power generation equipment:

    Make sure the unit is off-line (disconnected from utility and/or other generators power service), and either locked out or tagged DO NOT OPERATE. Remove all fuses.

    ----------------------

  1. De-energize the UPS.

    All inputs to the UPS need de-energized. There are two possible inputs to the UPS, one in the Input/Output Cabinet (IOC) and one in the optional Maintenance Bypass Cabinet (MBP).

    Open upstream breakers to these two cabinets.

    Note: Opening the upstream breakers to the Input/Output Cabinet and MBP will de-energize the customer load.

  1. Discharge the capacitors.

    Allow the capacitor banks in the UPS to purge for 10 minutes.

  1. Unlock the doors and open the doors.

    Open the doors of the cabinet using a 127.00 mm (5/16 inch) hex key on the upper and lower latches.

  1. Remove the metal safety shields.

    There are two metal safety shields covering the components in the cabinet. Remove the shields, if necessary.

Caterpillar Information System:

UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Maintenance
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys General Information (4 Wire Output Cabinet)
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Service Tools
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Flywheel Preheat Modes
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Transfer to Online Mode
Troubleshooting the Fuel Injection System For 3054 and 3056 Engines {1251, 1252} Troubleshooting the Fuel Injection System For 3054 and 3056 Engines {1251, 1252}
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Transfer to Bypass Mode
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Gen Set Module Circuit Breaker (Input/Output Cabinet)
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies External Source Sync Relay and Terminal Block
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Fan (Input/Output Cabinet)
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Isolation Switches
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Fan Transformer
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Circuit Breaker (K8)
VR6 Or K65-12B Voltage Regulators Require An External Jumper Wire When Used With A Permanent Magnet Generator{4467} VR6 Or K65-12B Voltage Regulators Require An External Jumper Wire When Used With A Permanent Magnet Generator{4467}
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Internal Component Preremoval Steps (MMS System Cabinet)
3044C Industrial Engine After Starting Engine
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Capacitor (4 Wire Output Cabinet)
3044C Industrial Engine Fuel Shutoff
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Cable Landing (4 Wire Output Cabinet)
C13 On-highway Engine Connecting Rod Bearing Journal
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies System Fuses (MMS System Cabinet)
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Terminal Block (ESS)
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys UPS Shutdown
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Thermal Switch Terminal Block
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.