UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Caterpillar


Maintenance

Usage:

ES12F CZE

Air Filter - Cleaning

Clean the filters after 90 days of operation.

Filters should be cleaned more frequently if you notice any of the following conditions:

  • Excessive buildup of dust

  • The filter deflects excessively due to blocked air flow

  • The system temperatures are steadily increasing or the UPS presents temperature warnings

Filter cleaning is not covered by warranty or standard service contracts.

Filters are installed in the front doors of the cabinet. The filters are the washable electrostatic type and can be removed for cleaning without opening the cabinet doors.

Flywheels and Cabinets - Clean

------ WARNING! ------

Risk of electric shock or energy hazard. Parts inside this UPS are energized by the flywheel even when the AC power is disconnected.

----------------------

The accumulation of dust on the surface of the flywheel and inside the cabinets can reduce heat transfer and reduce cooling. The routine replacement of air filters should minimize dust buildup on these surfaces.

  • Monitor general cleanliness.

  • If you notice excessive dust or contaminant buildup on system components, carefully vacuum the dust from the components.

Vacuum Pump Oil - Change

The vacuum pump oil should be changed once per year. If storage is anticipated, or if vacuum pump shutdown is anticipated for more than 30 days, the vacuum pump oil reservoir should be drained and filled with new oil.

Vacuum Pump Oil

All of the cabinets with a flywheel contain a vacuum pump. The vacuum pump requires a yearly oil change. Refer to the "Vacuum Pump Oil - Change" section of this document for information in order to replace the vacuum pump oil. The "Vacuum Pump Oil - Change" section is in "Chapter 13 - Procedures" of this document.

Flywheel Bearing - Replace

UPS flywheel bearings must be changed due to wear and vibration.

Scheduled bearing change interval is every 2.5 years. A bearing may need changed earlier in system service life if there is excessive vibration or elevated temperature.

When the time limits for the bearing life of each flywheel bearing have been reached, a notice message will appear and the alarm will sound. When the bearings are replaced, the installation date can be set to the current date via CSVIEW.

The bearings are contained in removable cartridges. The cartridges are replaced at the same time as the bearings. The cartridges must be positioned accurately for proper operation.

For the replacement procedure, refer to the "Flywheel Bearing - Replace" section of this document section that is in "Chapter 13 - Procedures".

Controller Board Battery Replacement

There are two printed circuit (pc) boards that control the Series 1200 UPS System. Each pc board contains a lithium ion battery.

The UPS Controller Board (APC2) contains a lithium ion battery. The UPS Controller Board (APC2) is located in the "Controls" cabinet.

The "CSHV Controller Board" (APC) contains a lithium ion battery. "CSHV Controller Board" (APC) is located in the "CSHV" cabinet.

The UPS Controller Board and the"CSHV Controller Board" has a lithium ion battery in order to maintain power for the on board clocks, discharge the counter, and for the uptime counter.

The lithium ion batteries for both the UPS and the controller boards for the Flywheel Cabinets have a life of five (5) years.

If either of the following symptoms appear, the batteries may need replaced.

  • Telemetry appears to be inaccurate.

  • The system will not restart properly after utility power is lost and system has discharged completely.

Refer to the "Controller Board Battery - Replace" section that is located in the "Procedures" portion of this document. The "Controller Board Battery - Replace" section will provide instructions in order to replace the batteries.

Capacitors - Replace

Capacitors that are in the inverter cabinet and the Flywheel Cabinet should be replaced about every seven (7) years. Capacitor replacement frequency is greatly affected by per cent load, types of loads, and operating environment temperatures. Refer to Table 1.

Table 1
Ambient Temperature (Degrees C)     Per Cent Load     Lagging Power Factor     Number Years Between Replacement    
40     100     0.8     5    
30     100     0.8     8    
40     75     0.8     10    
30     75     0.8     18    

Cable and Bus Connections - Check

The recommended interval in order to check the tightness and torque of the major power conductors is once every three (3) to five (5) years.

The interval period may vary due to local environmental conditions.

An alternate solution in order to avoid manually checking the tightness and torque of each physical connection, would be to scan the system with a thermal camera while the system is under normal load. Normal load assumes 50% to 100% nominal system capacity.

Caterpillar Information System:

UPS 1000S/ UPS 1200S Uninterruptible Power Supplys General Information (4 Wire Output Cabinet)
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Service Tools
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Flywheel Preheat Modes
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Transfer to Online Mode
Troubleshooting the Fuel Injection System For 3054 and 3056 Engines {1251, 1252} Troubleshooting the Fuel Injection System For 3054 and 3056 Engines {1251, 1252}
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Transfer to Bypass Mode
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Gen Set Module Circuit Breaker (Input/Output Cabinet)
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies External Source Sync Relay and Terminal Block
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Fan (Input/Output Cabinet)
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Isolation Switches
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Fan Transformer
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies System Fuse (Input/Output Cabinet)
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Internal Component Preremoval Steps (4 Wire Output Cabinet)
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Circuit Breaker (K8)
VR6 Or K65-12B Voltage Regulators Require An External Jumper Wire When Used With A Permanent Magnet Generator{4467} VR6 Or K65-12B Voltage Regulators Require An External Jumper Wire When Used With A Permanent Magnet Generator{4467}
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Internal Component Preremoval Steps (MMS System Cabinet)
3044C Industrial Engine After Starting Engine
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Capacitor (4 Wire Output Cabinet)
3044C Industrial Engine Fuel Shutoff
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Cable Landing (4 Wire Output Cabinet)
C13 On-highway Engine Connecting Rod Bearing Journal
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies System Fuses (MMS System Cabinet)
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Terminal Block (ESS)
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys UPS Shutdown
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.