UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Caterpillar


Transfer to Online Mode

Usage:

ES12F CZE

UPS/SMS

  1. Check to ensure that the Parallel Bus Output (PBO) circuit breaker is open in the Parallel Control Cabinet (PCC).

  1. Press the "Log On" button.

  1. Enter a valid service level user name and password.

  1. Press the "Enable Online Comand" button.

  1. Press the "Online" button.

The UPS/SMS or Multi-Module Unit (MMU) performs system checks and goes online in a UPS/SMS system.

An MMU system will go online but the system will not affect the load until the system is brought online via the PCC. Refer to the PCC service literature for more information on putting the Paralleled UPS online.

Note: Confirm that the UPS/SMS is online by observing the "Status" box on the Graphical User Interface (GUI).

Adding a Paralleled MMU to System that is NOT Online

  1. Check to ensure that the Parallel Bus Input Breaker (PIB) is closed in the Parallel Control Cabinet (PCC).

  1. Confirm that the system is in bypass and the load is energized via the bypass source. If not, place the system in bypass via the procedure in the PCC service literature.

  1. Press the "Log On" button.

  1. Enter a valid service level user name and password.

  1. Press the "Enable Online Command" button.

  1. Press the "Online" button.

The Multi-Module Unit (MMU) performs system checks and goes online.

An MMU will go online but will not affect the load until the system is brought online via the PCC. Refer to the PCC service literature for information on putting the Paralleled UPS online.

Note: confirm that the MMU is online by observing the status box on the Graphical User Interface (GUI).

Adding a Paralleled Multi-Module Unit (MMU) to an Online System

  1. Check to ensure that the Parallel Bus Input Breaker (PIB) is closed in the Parallel Control Cabinet (PCC).

  1. Confirm that the system is online and load is energized.

  1. Press the "Log On" button.

  1. Enter a valid service level user name and password.

  1. Press the "Enable Online Command" button.

  1. Press the "Online" button.

The Multi-Module Unit (MMU) performs system checks, goes online, and joins the array.

Note: Confirm that the MMU is online by observing the "Status" box on the Graphical User Interface (GUI).

Black Box Start Procedure (MMU only)

This start procedure is used in a parallel system when the Multi-Module Units (MMUs) have input but the bypass source does not. The Parallel Control Cabinet (PCC) is powered down and the load is not powered.

  1. Check to ensure that the Parallel Bus Output Breaker (PBO) is open in the Parallel Control Cabinet (PCC).

  1. Check to ensure that the Parallel Bus Input Breaker (PIB) is closed in the PCC.

  1. Transfer MMU #1 to online mode. Refer to "UPS/SMS" Step 1 through Step 5.

Caterpillar Information System:

Troubleshooting the Fuel Injection System For 3054 and 3056 Engines {1251, 1252} Troubleshooting the Fuel Injection System For 3054 and 3056 Engines {1251, 1252}
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Transfer to Bypass Mode
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Gen Set Module Circuit Breaker (Input/Output Cabinet)
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies External Source Sync Relay and Terminal Block
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Fan (Input/Output Cabinet)
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Isolation Switches
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Fan Transformer
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies System Fuse (Input/Output Cabinet)
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Internal Component Preremoval Steps (Input/Output Cabinet)
2006/07/10 New Parts are Available for Engines that use Heavy Duty Air Cleaners {1051, 1316, 1317}
TH48-E70 Petroleum Transmission Plate Locations and Film Locations
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Bringing UPS Online
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Flywheel Preheat Modes
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Service Tools
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys General Information (4 Wire Output Cabinet)
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Maintenance
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Internal Component Preremoval Steps (4 Wire Output Cabinet)
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Circuit Breaker (K8)
VR6 Or K65-12B Voltage Regulators Require An External Jumper Wire When Used With A Permanent Magnet Generator{4467} VR6 Or K65-12B Voltage Regulators Require An External Jumper Wire When Used With A Permanent Magnet Generator{4467}
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Internal Component Preremoval Steps (MMS System Cabinet)
3044C Industrial Engine After Starting Engine
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Capacitor (4 Wire Output Cabinet)
3044C Industrial Engine Fuel Shutoff
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Cable Landing (4 Wire Output Cabinet)
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.