UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Caterpillar


Flywheel Load Cell - Calibrate

Usage:

UPS 250 APZ

Calibration Procedure

Perform the procedure whenever the flywheel interface board or the load cell is replaced.

Note: Bring the RPM of the system to zero. The flywheel should be in shutdown mode. The bus may purge while calibration is being performed.




    Illustration 1g00839253

    (1) Key switch

  1. Place the key switch (1) in the Bypass position for the MMU that is being calibrated.

    Note: In a single module system, place the key switch (1) in the Bypass position on the system cabinet.

    Note: Continuing with step 2 may disable power to the load.

  1. Disable the input voltage to the system by opening the input circuit breaker.

  1. Connect a PC to the parallel cabinet interface board that is located in the system cabinet.



    Illustration 2g01051091

  1. Rotate the switch on the parallel cabinet interface board to the corresponding multiple module unit.

    Proceed to Step 8.

  1. Disable the input voltage to the system by opening the input circuit breaker.

    Note: Step 5 may disable power to the load.




    Illustration 3g00839256

    (2) System I/O and isolation board




    Illustration 4g00840027

    (3) Jumper (Jmp 1)

  1. Remove all sheet metal panels. Remove the sheet metal panel for the system I/O and isolation board (2) .

  1. Connect a PC to the system RS232/RS485 port that is located on the system I/O and isolation board. Ensure that jumper Jmp1 (3) on the system I/O and isolation board is in the correct position.

    Note: The lower side is RS232 and the higher side is RS485.

  1. Close the input circuit breaker in order to restore the power to the system.

    The system will start but the key will remain in the Bypass position.

  1. Start the PC.



    Illustration 5g00840053

    (4) UPSView icon

  1. Run the UPSView software by double clicking the icon (4) on the PC.



    Illustration 6g01003395

  1. Move the computer mouse over "PC Settings" in the menu bar.

    Refer to Illustration 6.




    Illustration 7g01003391

    (6) Direct connect radio button

    (7) PC COM port

    (8) Baud rate setting

    (9) Detailed MMU telemetry setting

    (10) OK button

  1. Click "Connection Settings" in the menu bar.

    Refer to Illustration 6.

    The dialog that is shown in Illustration 7 will open.

  1. Click the "Direct Connect (serial)" radio button (6) .

  1. Select the "PC COM Port" (7) for the SERIAL Connection. Set the baud rate (8) .

    Note: The radio button for "Detailed MMU telemetry" (9) must be checked.

  1. Click on the "OK" Button (10) in order to accept these settings.



    Illustration 8g01003435

  1. Click "Connection" on the menu bar.

  1. Select "Connect" from the drop-down menu.

    The PC will be connected to the system. The PC will receive the system telemetry.




    Illustration 9g01003470

    (13) "Enter Password"

  1. Once the PC is connected, click "Enter Password" (13) on the menu bar.

    The "Enter User Name/Password" dialog will open. Refer to Illustration 9.

  1. Enter the user name.

  1. Enter the password.

  1. Click the "OK" button.

    After the password has been entered, the menu bar will change.

    The menu bar will contain a "Calibrate" option.

    Note: Perform Steps 22 through 25 if the load cell has been replaced.

  1. On the "Op. Params." menu, select "OP Group 11 MMU Serial Number". The selection will allow access to a submenu. Select "Load Cell Serial Number" from the submenu.

  1. Select "Load Cell Serial Number". A "Request Operating Parameter Change" will open.



    Illustration 10g01049801

  1. Enter the serial number of the load cell that is located on the manufacturer data sheet.

    Note: The data sheet is enclosed with the assembly (lower bearing cartridge).

    Note: Enter a numeric value. Do not use the number that is shown in Illustration 10. The number in Illustration 10 is an example.




    Illustration 11g01049799

  1. Select "Op. Group 5: Model Index" from the "Op. Params." menu. Then, select "Load Cell Calibration Constant" from the "Model Index" submenu.

  1. Select "Load Cell" on the "Calibrate" menu. The "Load Cell Calibration" dialog will open.

  1. Select "View Status". A dialog box will open that provides a text message. The message indicates the status of the process (calibration). Initially, the dialog will show that the minimum has not been calibrated.

  1. Select "Use Defaults".



    Illustration 12g01049803

  1. Verify that the "Minimum" button in the dialog (calibration) is highlighted. If the "Minimum" button is not highlighted, click the "Minimum" button.



    Illustration 13g01032443

  1. Disconnect the 16-pin connector for the lower wiring harness (flywheel) from the interface board (flywheel).



    Illustration 14g01263288

    View of "Min/Max Jumpers" for new FWI PWAS

    (14) 268-0058 Cable Assembly (MAX)

    (15) 268-0057 Cable Assembly (MIN)




    Illustration 15g01292481

    View of minimum jumper (cable assembly) for older FWI PWAS

    (16) 253-8087 Cable Assembly (MIN)

  1. Connect the jumper (15) that is labeled "MIN".



    Illustration 16g01049808

  1. Click the "OK" button on the calibration dialog.

  1. Verify that the "Maximum" button on the calibration dialog is highlighted. If the "Maximum" button is not highlighted, click the "Maximum" button. The dialog (status) will indicate that the Maximum has not been calibrated.



    Illustration 17g01292501

    View of maximum jumper (cable assembly) for older FWI PWAS

    (17) 253-8089 Cable Assembly (MAX)

  1. Disconnect the jumper (15) that is labeled "MIN".

  1. Connect the jumper (14) that is labeled "MAX".



    Illustration 18g01049807

  1. Click the "OK" button on the calibration dialog. The dialog (status) will indicate that the calibration values have not been saved.

  1. Click the "Save" button on the calibration dialog.

    Note: At the end of Step 37, two errors (temperature) will be announced on the dialog. The errors will be cleared when the wiring harness is reconnected in Step 38.

  1. Connect the wiring harness to the flywheel interface board.

    Calibration is complete.

Calibration Check

A proper calibration can be verified by using voltage measurements and a calculator.

  1. Measure the voltage between pins "16" and "4" on the flywheel interface board and record the voltage. The value will be "Ve".

  1. Measure the voltage between pins "11" and "12" on the flywheel interface board and record the voltage. The value will be "VL". The voltage measurements are completed only with control power on.



    Illustration 19g01049809

  1. Calculate the force (bottom bearing) that is expected by using the equation in Illustration 19.

  1. Compare the value that is calculated with the reading that is indicated by UPSView. The values should agree within ±1 percent.

Caterpillar Information System:

336E Excavator Machine System Specifications Sprocket
2006/05/15 A New Air Lines Group is Used {1071}
Procedure for Operating Caterpillar Filter Carts {0680, 0768, 5050} Procedure for Operating Caterpillar Filter Carts {0680, 0768, 5050}
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Specifications
C13 On-highway Engine Engine Oil Pan
2007/04/09 Improved Battery Chargers For Gensets are Available {1406}
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies UPS Operating Parameters
C9 On-highway Engine Cylinder Head
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Changing Parameters
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Operating Parameters Menu
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies UPS View Commands and Hot Keys
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Troubleshooting
C13 On-highway Engine Cylinder Block
3044C Industrial Engine Product Lifting
C15 On-Highway Engine Fuel Temperature Sensor - Remove and Install
C15 On-Highway Engine Camshaft Position Sensor - Remove and Install
C15 On-Highway Engine Crankshaft Position Sensor - Remove and Install
TA19-M2WD and TA19-M4WD Agricultural Transmissions Clutch (Front Wheel Assist) - Remove
3500B Industrial Engines with the ADEM 3 Electronic Control Module Prelubrication System
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Hardware Revision - Version 3.0 Design
C15 On-Highway Engine Engine Oil Pressure Sensor - Remove and Install - Variable Intake Valve Actuator
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies General Information (SMS Bypass Cabinet)
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies General Information (Input/Output Cabinet)
TA19-M2WD and TA19-M4WD Agricultural Transmissions Clutch (Front Wheel Assist) - Install
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.