UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Caterpillar


Specifications

Usage:

UPS 250 APZ

Table 1
  50 Hz Units  60 Hz Units 
  UPS 250i  UPS 500  UPS 750  UPS 300  UPS 600  UPS 900 
Rating  250 kVA
200 kW 
500 kVA
400 kW 
750 kVA
600 kW 
300 kVA
240 kW 
600 kVA
480 kW 
900 kVA
720 kW 
Input Voltage  380 VAC
400 VAC
415 VAC 
380 VAC
400 VAC
415 VAC 
380 VAC
400 VAC
415 VAC 
480 VAC  480 VAC  480 VAC 
AC Input 
Nominal Amperage  315 A
299 A
288 A 
631 A
599 A
578 A 
946 A
899 A
867 A 
297 A  595 A  892 A 
Maximum Amperage Non-continuous(1)  440 A  880 A  1320 A  440 A  880 A  1320 A 
Maximum Amperage Continuous  400 A  800 A  1200 A  400 A  800 A  1200 A 
AC Output 
Nominal Amperage  380 A
361 A
348 A 
761 A
723 A
696 A 
1140 A
1084 A
1044 A 
361 A  722 A  1084 A 
Typical System Efficiency 
100 Percent load  96 Percent  96 Percent  96 Percent  97 Percent  97 Percent  97 Percent 
Specifications for Input 
Voltage  380 VAC, 400 VAC, 415 VAC, 3 phase plus neutral and ground(2)  380 VAC, 400 VAC, 415 VAC, 3 phase plus neutral and ground(2)(3)  380 VAC, 400 VAC, 415 VAC, 3 phase plus neutral and ground(2)(3)  480 VAC, 3 phase plus ground(2)(4)  480 VAC, 3 phase plus ground(2)(4)  480 VAC, 3 phase plus ground(2)(4) 
Voltage Range  +10 Percent / −15 Percent (2)(5)  +10 Percent / −15 Percent (2)(5)  +10 Percent / −15 Percent (2)(5)  +10 Percent / −15 Percent (5)  +10 Percent / −15 Percent (5)  +10 Percent / −15 Percent (5) 
Power Factor  0.99 at rated load and nominal voltage  0.99 at rated load and nominal voltage  0.99 at rated load and nominal voltage  0.99 at rated load and nominal voltage  0.99 at rated load and nominal voltage  0.99 at rated load and nominal voltage 
Harmonic Current Distortion  
Linear Load  <3 Percent max at 100 Percent resistive load  <3 Percent max at 100 Percent resistive load  <3 Percent max at 100 Percent resistive load  <3 Percent max at 100 Percent resistive load  <3 Percent max at 100 Percent resistive load  <3 Percent max at 100 Percent resistive load 
Nonlinear Load  <8 Percent with a 100 Percent nonlinear load  <8 Percent with a 100 Percent nonlinear load  <8 Percent with a 100 Percent nonlinear load  <8 Percent with a 100 Percent nonlinear load  <8 Percent with a 100 Percent nonlinear load  <8 Percent with a 100 Percent nonlinear load 
Input Frequency  50 Hz ± 10 Percent max (5)(6)  50 Hz ± 10 Percent max (5)(6)  50 Hz ± 10 Percent max (5)(6)  60 Hz ± 10 Percent max (5)  60 Hz ± 10 Percent max (5)  60 Hz ± 10 Percent max (5) 
Specifications for Surge  IEEE 587/ANSI C62.41  IEEE 587/ANSI C62.41  IEEE 587/ANSI C62.41  IEEE 587/ANSI C62.41  IEEE 587/ANSI C62.41  IEEE 587/ANSI C62.41 
Specifications for Output 
Voltage  380 VAC, 400 VAC, 415 VAC, 3 phase plus neutral and ground  380 VAC, 400 VAC, 415 VAC, 3 phase plus neutral and ground  380 VAC, 400 VAC, 415 VAC, 3 phase plus neutral and ground  480 VAC, 3 phase plus ground(7)  480 VAC, 3 phase plus ground(7)  480 VAC, 3 phase plus ground(7) 
Voltage Regulation 
Steady state  ± 2% of nominal for ± 10% input and balanced or unbalanced load  ± 2% of nominal for ± 10% input and balanced or unbalanced load  ± 2% of nominal for ± 10% input and balanced or unbalanced load  ± 2% of nominal for ± 10% input and balanced or unbalanced load  ± 2% of nominal for ± 10% input and balanced or unbalanced load  ± 2% of nominal for ± 10% input and balanced or unbalanced load 
Flywheel Mode  ± 2% of nominal for steady state balanced or unbalanced load  ± 2% of nominal for steady state balanced or unbalanced load  ± 2% of nominal for steady state balanced or unbalanced load  ± 2% of nominal for steady state balanced or unbalanced load  ± 2% of nominal for steady state balanced or unbalanced load  ± 2% of nominal for steady state balanced or unbalanced load 
Transient  ± 5% of nominal for 100% load(8)  ± 5% of nominal for 100% load(8)  ± 5% of nominal for 100% load(8)  ± 5% of nominal for 100% load(8)  ± 5% of nominal for 100% load(8)  ± 5% of nominal for 100% load(8) 
Voltage Distortion  <3% at Full Linear Load  <3% at Full Linear Load  <3% at Full Linear Load  <3% at Full Linear Load  <3% at Full Linear Load  <3% at Full Linear Load 
<5% at Full Nonlinear Load <5% at Full Nonlinear Load  <5% at Full Nonlinear Load  <5% at Full Nonlinear Load  <5% at Full Nonlinear Load  <5% at Full Nonlinear Load 
Output Frequency  50 Hz ±3%(9)(10)  50 Hz ±3%(9) (10)  50 Hz ±3% (9)(10)  60 Hz ±10% (9)(10)  60 Hz ±10% (9)(10)  60 Hz ±10% (9)(10) 
(1) Including flywheel recharge current
(2) from a grounded wye source
(3) Except ± 10 Percent max at 380 VAC
(4) 4-wire optional
(5) programmable
(6) Also Available with 60 Hz nominal voltage
(7) 4-wire with optional 4-wire input
(8) 4 milliseconds recovery time
(9) utility synchronized, normal operation
(10) nominal ± 0.2 Percent free running

Table 2
480 V Systems 
Percent Load  Ride-Through Time 
100 Percent  13 seconds 
75 Percent  17 seconds 
50 Percent  25 seconds 
25 Percent  50 seconds 
380/400/415 V Systems 
Percent Load  Ride-Through Time 
100 Percent  15 seconds 
75 Percent  20 seconds 
50 Percent  30 seconds 
25 Percent  60 seconds 

Caterpillar Information System:

C13 On-highway Engine Engine Oil Pan
2007/04/09 Improved Battery Chargers For Gensets are Available {1406}
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies UPS Operating Parameters
C9 On-highway Engine Cylinder Head
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Changing Parameters
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Operating Parameters Menu
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies UPS View Commands and Hot Keys
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Troubleshooting
C4.4 Industrial Engine Glossary of Electronic Control Terms
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Telemetry Parameters
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies System Messages
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies MMU Master Messages
Procedure for Operating Caterpillar Filter Carts {0680, 0768, 5050} Procedure for Operating Caterpillar Filter Carts {0680, 0768, 5050}
2006/05/15 A New Air Lines Group is Used {1071}
336E Excavator Machine System Specifications Sprocket
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Flywheel Load Cell - Calibrate
C13 On-highway Engine Cylinder Block
3044C Industrial Engine Product Lifting
C15 On-Highway Engine Fuel Temperature Sensor - Remove and Install
C15 On-Highway Engine Camshaft Position Sensor - Remove and Install
C15 On-Highway Engine Crankshaft Position Sensor - Remove and Install
TA19-M2WD and TA19-M4WD Agricultural Transmissions Clutch (Front Wheel Assist) - Remove
3500B Industrial Engines with the ADEM 3 Electronic Control Module Prelubrication System
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Hardware Revision - Version 3.0 Design
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.