UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Caterpillar


Telemetry Parameters

Usage:

UPS 250 APZ

Telemetry Parameters

From the top level of the display, you can scroll through the logs and the telemetry data. Navigation is accomplished with the soft keys. The keys are located at the bottom of the display and the keys are located on the right side of the display.

Table 1
Three Phase Telemetry Points 
"Input Line Voltage A, B, and C"  Measurement of the input voltages from phases A, B, and C to neutral. 
"Phase - Phase Input Volts A, B, and C"  Measurement of the phase voltage to the phase voltage. The measurement is made on the input side across phases A, B, and C. 
"Current In Phases A, B, and C"  Input current to the system, measured for each phase A, B, and C. 
"Input Power Phases A, B, and C"  Calculated value based on the input phase to neutral voltages and the input currents. 
"Input kVA Phases A, B, and C"  Calculated value based on the input phase to neutral voltages and the input currents. 
"Output Line Voltage Phases A, B, and C"  Measurement of output voltages from phases A, B, and C to neutral. 
"Phase - Phase Output Volts A, B, and C"  Measurement of the phase to phase voltages from output phases A, B, and C. 
"Current Out Phases A, B, and C"  Output current from the system, measured for each phase A, B, and C. 
"Output Power Phases A, B, and C"  Calculated value based on the output phase to neutral voltages and the output currents. 
"Output kVA Phases A, B, and C"  Calculated value based on the output phase to neutral voltages and the output currents. 

Table 2
Single Phase Telemetry Points 
"Frequency"  Measurement of the frequency as seen on phase C. 
"Output Power"  Sum of the output power on phases A, B, and C. 
"Total Output kVA"  Sum of the output kVA on phases A, B, and C. 
"Output Power Factor"  Calculated value based on the output phase to neutral voltages and the output currents. 
"Input Frequency"  Measurement of the input frequency as seen on phase C. 
"Total Input Power"  Sum of the input power on phases A, B, and C. 
"Total Input kVA"  Sum of the input kVA on phases A, B, and C. 
"Input Power Factor"  Calculated value based on the input phase to neutral voltages and the input currents. 
"Cabinet Temp"  Air temperature measurement taken in the cabinet. 
"Air Inlet Temp"  Air temperature taken at the air inlet to the cabinet 
"Static Switch Temp"  Temperature of the static switch heat sink. 
"Positive DC Bus Voltage"  Positive DC bus voltage produced by the input rectifier. 
"Negative DC Bus Voltage"  Negative DC bus voltage produced by the input rectifier. 
"Tachometer"  Flywheel tachometer. 
"Percent Energy"  Calculated value that represents the usable energy stored in the flywheel. 
"Vacuum Gauge"  Measurement indicates the vacuum level in the flywheel housing. 
"Top Field Coil Current"  Measurement indicates the current through the top field coil of the flywheel. 
"Bottom Field Coil Current"  Measurement indicates the current through the bottom field coil of the flywheel. 
"Bottom Bearing Force"  Amount of force exerted on the bottom bearing. 
"Lateral Vibration"  Measurement is the lateral vibration measured by the flywheel accelerometers. 
"Axial Vibration"  Measurement is the axial vibration measured by the flywheel accelerometers. 
"Top Field Coil Temp"  Measured temperature of the top field coil in the flywheel housing. 
"Bottom Field Coil Temp"  Measured temperature of the bottom field coil in the flywheel housing. 
"Armature Temp"  Measured temperature of the main armature in the flywheel housing. 
"Top Field Coil IGBT Temp"  Measured temperature of the top IGBT field coil. 
"Bottom Field Coil IGBT Temp"  Measured temperature of the bottom IGBT field coil . 
"Top Bearing Temp"  Measured temperature of the top flywheel bearing. 
"Bottom Bearing Temp"  Measured temperature of the bottom flywheel bearing. 
"Comm. Sensor Advance"  Value that describes the calibration setting of the commutation sensor. The commutation sensor is used to measure the rotor position. 

Table 3
Control Set Points 
"Field Current Setpoint"  Current set point for the bottom field. 
"Rotor Speed Setpoint"  Desired flywheel speed. 
"Motor Current Limit"  Upper limit for the amount of current used in the motor armature. 
"Discharge FC @7000 Setpoint"  Sets the amplitude of the field current profile during discharge. 
"Voltage Ref. Set point"  Target for the output voltage of the machine. 

Caterpillar Information System:

UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies System Messages
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies MMU Master Messages
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies MMU Messages
C13 and C15 On-Highway Engines Monitoring System - Dash Lamps and Controls for the Aftertreatment Regeneration Device (ARD)
C4.4 Industrial Engine Power Sources
C13 Engine Engine Oil Pressure Sensor - Remove and Install - Intake Valve Actuator
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Service Connections
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Additional UPS Concepts
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Front Panel Overview
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Flywheel Preheat Modes
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies System Operational Modes
C13 Engine Engine Oil Pressure Sensor - Remove and Install
C4.4 Industrial Engine Glossary of Electronic Control Terms
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Troubleshooting
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies UPS View Commands and Hot Keys
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Operating Parameters Menu
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Changing Parameters
C9 On-highway Engine Cylinder Head
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies UPS Operating Parameters
2007/04/09 Improved Battery Chargers For Gensets are Available {1406}
C13 On-highway Engine Engine Oil Pan
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Specifications
Procedure for Operating Caterpillar Filter Carts {0680, 0768, 5050} Procedure for Operating Caterpillar Filter Carts {0680, 0768, 5050}
2006/05/15 A New Air Lines Group is Used {1071}
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.