UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Caterpillar


AC Voltage - Calibrate

Usage:

UPS 250 APZ

Calibration Procedure for the AC Voltage

------ WARNING! ------

During the calibration procedures, voltages up to 600 V are present in the control panel.

Do not short the terminals to ground with any part of the body or any conductive material. Loss of life or injury could result from electrical shock or injury from molten metal.


Note: Perform this procedure whenever the following components are replaced: AC Interface Board and System Controller Board. AC Current Calibration is also required.

Table 1
Required Tools 
Part Number  Description 
146-4080  Digital Multimeter 

  1. Bring the RPM of the system to zero.

  2. Place the keyswitch in the BYPASS position for the MMU that is being calibrated.

    Note: In a Single-Module System, place the keyswitch in the BYPASS position on the System Cabinet.

    Note: Proceed to step 6 for Single-Module Systems.

  3. Connect a PC to the Parallel Cabinet Interface Board that is located in the System Cabinet.


    Illustration 1g01051091
    (1) Switch

  4. Rotate the switch (1) on the Parallel Cabinet Interface Board to the corresponding Multiple Module Unit.

    Proceed to Step 7.



    Illustration 2g00839256
    (2) System I/O and Isolation Board


    Illustration 3g00840027
    (3) Jumper "Jmp1"

  5. Remove all sheet metal panels. Remove the sheet metal panel for the System I/O and Isolation Board (2).

  6. Connect a PC to the System RS232/RS485 port that is located on the System I/O and Isolation Board. Make sure that jumper Jmp1 (3) on the System I/O and Isolation Board is in the correct position.

    Note: The lower side is RS232 and the higher side is RS485.

  7. Close the input circuit Breaker in order to restore power to the System.

    The System will initialize, but the key will remain at the BYPASS position.

  8. Initialize your Personal Computer.


    Illustration 4g00840053
    (4) Icon for UPS View

  9. Run UPS View by double clicking over the icon (4) on your PC.


    Illustration 5g01003395


    Illustration 6g01003391
    (6) "Direct Connect" Radio Button
    (7) PC COM Port
    (8) "Baud Rate" Setting
    (9) "Detailed MMU telemetry" Setting
    (10) "OK" Button
    (6) "Direct Connect" Radio Button
    (7) PC COM Port
    (8) Setting for the Baud Rate
    (9) "Detailed MMU telemetry" Setting
    (10) "OK" Button

  10. Click over the "PC Settings" in the Menu Bar. Refer to Illustration 5.

    Click on "Connection Settings". The "Connection" window will open.

  11. Refer to Illustration 6. Click on the radio button that is for the "Direct Connect (serial)" (6).

  12. Select your PC COM Port for (7) this Serial Connection and set the Baud rate (8).

    The radio button for "Detailed MMU Telemetry" (9) must be checked.

  13. Click on "OK" Button (10) in order to accept these settings.


    Illustration 7g01003435

  14. Click on "Connection" on the Menu Bar.

  15. Select "Connect" from the drop-down menu.

    The PC will be connected to the System and the PC will receive the System Telemetry.



    Illustration 8g01003470
    (13) "Enter Password"

  16. When the PC connects, click on "Enter Password" (13) in the Menu Bar.

    The window that is illustrated above will open.

  17. Enter the username and enter the password.

  18. Click on "OK" Button.

    After the Password has been entered, the Menu Option will Change.

    The Menu bar will contain a "Calibrate" option.

    Note: The vacuum for the Flywheel needs to be less than 58 mTorr before the system can start this calibration.



    Illustration 9g00840232

  19. Click "Calibrate" on the drop-down menu.

  20. Select "AC Voltages".

    The following events will occur.

    • The input contactor "K1" closes.

    • The output contactor "K2" closes.

    • The Static Switch turns on.

    • The DC Bus Voltage rises.

    • The "Calibration of a Channel" window opens. Refer to Illustration 9.

  21. Click on "View Status" button.

    Another "Calibration Group Status" window will open.

    Note: Drag the "Calibration Group Status" window aside if the view of the "Calibration of a Channel" window is blocked.

  22. Click on "Use Defaults" on "Calibration of a Channel" window.

    You will be prompted to "Enter Calibration Point" for "Voltage in Ph. AB".



    Illustration 10g01087513
    (14) Phase A terminal
    (15) Phase B Terminal


    Illustration 11g00840319


    Illustration 12g00840348

  23. Measure the input voltage from the terminal of phase A (14) to the terminal of phase B (15).

    Reference: Refer to Illustration 10.

  24. Enter the value from step 23 in the "Enter Calibration Point" field.

  25. Click "OK".

    The System will process the calibration. The system will automatically display "Enter Calibration Point" for the "Voltage in Ph. BC". The "Calibration Group Status" window will display "Calibration complete but not saved for Phase AB".



    Illustration 13g01087520
    (16) Phase C Terminal


    Illustration 14g00840385

  26. Measure the input voltage from the terminal of phase B (15) to the terminal of phase C (16).

    Reference: Refer to Illustration 13.

  27. Enter the value from step 26 in the "Enter Calibration Point" field.

  28. Click on "OK".

    The System will process the calibration again. The system will automatically prompt "Enter Calibration Point" for the "Voltage in Ph. BN". The "Calibration Group Status" window will display "Calibration complete but not saved for Phase BC".



    Illustration 15g00840393


    Illustration 16g01087545
    (17) Neutral Terminal

    Note: Step 29 is for a three-phase 4-wire system.

  29. Measure the input voltage from the terminal of phase B (15) to neutral terminal (17).

    Reference: Refer to Illustration 16.

    Note: If the system is a 3-wire system, then Measure the AC voltage from the terminal of phase B (15) to the ground terminal.

  30. Enter the value from step 29 in the "Enter Calibration Point" field.

  31. Click "OK".

    The System will process the calibration again. The system will automatically prompt "Enter Calibration Point" for the "Voltage in Ph. AB". The "Calibration Group Status" window will display "Calibration complete but not saved for Phase BN".



    Illustration 17g00840407

  32. Click on the "Save" button that is on the "Calibration of a channel" window.

    The noise from the input contactors and the output contactors that are opening can be heard. The Calibration ends. A "Flash reprogrammed OK" message appears. This indicates that the calibration has been successfully completed.



    Illustration 18g01003513

  33. To end the calibration in UPS View, click on the "Connection" that is located on the Menu Bar.

  34. Select "Disconnect".

    You will stop receiving the telemetry signal.

  35. Unplug the RS232 cable from the System I/O Isolation Board. Reinstall the back Sheet Metal.

  36. Close the doors for proper air flow into the System.
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.