DC Bus Voltage - Calibrate

Usage:

UPS 250 APZ

Calibration Procedure for the DC Bus Voltage

Note: Perform this procedure whenever the following boards are replaced: DC Interface Board and System Controller Board.

Table 1
Required Tools 
Tool  Part Number  Part Description  Qty 
146-4080  Digital Multimeter 


    Illustration 1g00839253
    (1) Keyswitch

  1. Place the keyswitch in BYPASS position (1).

    Note: If the UPS is not equipped with a Bypass Switch, power to the load will be lost by continuing with Step 2.

  2. De-energize the system. Refer to the Testing and Adjusting, "SMS System Shutdown" and Testing and Adjusting, "MMS System Shutdown" sections of this manual for information on shutting down the system.


    Illustration 2g00839256
    (2) Sheet Metal Panel

  3. Remove the Sheet metal panel (2) for the System Input/Output and Isolation Board.


    Illustration 3g00840027
    (3) Jumper "Jmp 1"

  4. Connect a PC to the System RS232/RS485 port that is located on the System Input/Output and Isolation Board. Make sure that jumper "Jmp 1" (3) on System Input/Output and Isolation Board is in the correct position.

    Note: The lower side is RS232 and the higher side is RS485.

  5. Close the input circuit breaker in order to restore the power to the System.

    The System will start but the key will remain in the BYPASS position.

  6. Start your PC.


    Illustration 4g00840053
    (4) UPS View Icon

  7. Run the UPS View software by double clicking over the icon (4) on your PC.


    Illustration 5g01003395


    Illustration 6g01003391
    (6) "Direct Connect" Radio Button
    (7) PC COM Port
    (8) "Baud Rate" Setting
    (9) "Detailed MMU telemetry" Setting
    (10) "OK" Button

  8. Click over the "PC Settings" in the Menu Bar.

    Refer to Illustration 5.

    The window that is shown in Illustration 6 will open.

  9. Click over the "Connection Settings" in the Menu Bar.

    Refer to Illustration 5.

    The window that is shown in Illustration 6 will open.

  10. Check the "Direct Connect (serial)" radio button (6).

  11. Select your PC COM Port (7) for this Serial Connection and set the Baud rate (8).

    Note: The radio button for "Detailed MMU telemetry" (9) must be checked.

  12. Click on the "OK" Button (10) in order to accept these settings.


    Illustration 7g01003435

  13. Click on "Connection" on the Menu Bar.

  14. Select "Connect" from the drop-down menu.

    Your PC will be connected to the System. Your PC will receive the System Telemetry.



    Illustration 8g01003470
    (13) "Enter Password"

  15. Once you are Connected, Click over the "Enter Password" (13) in the Menu Bar.

    The "Enter User Name/Password" window will open. Refer to Illustration 8.

  16. Enter your username.

  17. Enter your password.

  18. Click on "OK" Button.

    After the password has been entered, the menu bar will change.

    The Menu bar will contain a "Calibrate" Option.



    Illustration 9g01003485

  19. Click on the "Calibrate" menu.

  20. Select "DC Bus Voltages". Refer to Illustration 9.

    A "Calibration of a Channel" window will open. Refer to Illustration 10.



    Illustration 10g00840516

  21. Click on "View Status" button.

    Another "Calibration Group Status" window will open. Refer to Illustration 5.

  22. Drag this window aside if the view of "Calibration of a Channel" window is blocked.

  23. Click on "Use Defaults" on "Calibration of a Channel" window.

    You will be prompted to "Enter Calibration Point for Positive DC Bus".

    Note: The "Minimum Button" on "Calibration of a Channel" window is selected. Refer to Illustration 10. The "Minimum Button" on "Calibration of a Channel" window is the default selection.

  24. Measure the DC Bus Voltage from the DC Common terminal to the Positive DC Bus terminal.

    This value should be close to zero.



    Illustration 11g00840531

  25. Enter this value in "Enter Calibration Point" field and click "OK". Refer to Illustration 11.

    The System will process the Calibration and the System will automatically change the prompt to "Enter Calibration Point" for "Negative DC Bus". The "Calibration of a Channel" window will change in order to show "Positive DC Bus Minimum value entered". Refer to Illustration 12.



    Illustration 12g00840534

  26. Measure the DC Bus Voltage from the DC Common terminal to the Negative DC Bus terminal. Refer to Illustration 13.

    This value should be close to zero.



    Illustration 13g00840632


    Illustration 14g00840655

  27. Enter the value that was measured in Step 26 into the "Enter Calibration Point" field and click "OK". Refer to Illustration 13.

    The System will process the calibration. The system will prompt you to "Enter Calibration Point for Positive DC Bus". Refer to Illustration 14.

    The "Calibration Group Status" window will display "Negative DC Bus Voltage Minimum value entered". Refer to Illustration 14.



    Illustration 15g00840658

  28. Click on the "Maximum" button.

    You will hear the input contactor "K1" close. The Static Switch will turn on and the DC Bus will rise.

    You will be prompted to "Enter Calibration Point for Positive DC Bus". Refer to Illustration 16.



    Illustration 16g00840676


    Illustration 17g00860251

  29. Measure the DC Bus Voltage from the DC Common terminal to the Positive DC Bus terminal on the Field Coil Driver Module. Enter this value in "Enter Calibration Point" field. Click "OK". Refer to Illustration 13.

    The System will process the calibration. The system will automatically prompt you to "Enter Calibration Point for Negative DC Bus". Refer to Illustration 17.

    The "Calibration Group Status" window will Display "Positive DC Voltage Calibration Complete but not saved".

  30. Measure the DC Bus Voltage from the DC Common terminal to the Negative DC Bus terminal.

  31. Enter this value in "Enter Calibration Point" field and click "OK". Refer to illustration 13.

    The System will process Calibration. The System will prompt you to "Enter Calibration Point for positive DC Bus".

    The "Calibration Group Status" window will display "Negative DC Voltage Calibration Complete but not saved".



    Illustration 18g01003502

  32. Click on "Save" on "Calibration of a channel" window.

    You will hear the input contactor "K1" open.

    The Calibration ends. You will see the following message on the text window of UPS View: "Flash reprogrammed OK". This indicates that the Calibration has been done successfully.



    Illustration 19g00840138


    Illustration 20g01003513

  33. To end the calibration in UPS View, click on the "Connection" on the Menu Bar.

  34. Select "Disconnect".

    Your PC will stop receiving the System Telemetry.

  35. Unplug the RS232 cable from the System Input/Output and Isolation Board and put back the sheet metal panels.

  36. Close the doors for proper air flow into the System.

Caterpillar Information System:

C7 On-Highway Engine Fuel Injection Pump - Install
325D and 329D Excavators and 325D Material Handler Machine System Specifications Control Valve (Auxiliary) - Medium Pressure
C13 Engine Pistons and Connecting Rods - Install
C13 Engine Pistons and Connecting Rods - Remove
325D and 329D Excavators and 325D Material Handler Machine System Specifications Solenoid Valve (Work Tool, 4-Function)
3500B Industrial Engines with the ADEM 3 Electronic Control Module Diagnostic Code List
C9 On-highway Engine Turbocharger Oil Lines
C13 Engine Inlet and Exhaust Valve Springs - Remove and Install
C7 On-Highway Engine Lifter Group - Remove and Install
C9 On-highway Engine Engine Oil Pan
C11 and C13 Petroleum Engines Rocker Arm - Assemble
C11 and C13 Petroleum Engines Rocker Arm - Disassemble
TH31-C9I, TH31-C9P, TH31-C9T, TH35-C11I, TH35-C13I, TH35-C13T, TH35-C15I and TH35-C15T Petroleum Power Train Packages and TH31-E61 and TH35-E81 Petroleum Transmissions Power Train Electronic Control System Programmable Parameters
C7 PETROLEUM Petroleum Engine Unit Injector Hydraulic Pump - Remove
C175-16 Locomotive Engine Engine Design
C7 PETROLEUM Petroleum Engine Unit Injector Hydraulic Pump - Install
C7 On-Highway Engine Water Pump - Remove
C7 On-Highway Engine Water Pump - Install
C7 On-Highway Engine Vibration Damper and Pulley - Remove and Install
C7 Industrial Engines Camshaft Bearings - Remove
C7 Industrial Engines Pistons and Connecting Rods - Install
C7 Industrial Engines Housing (Front) - Install
C175-16 and C175-20 Generator Set Engines Fuel Filter (Primary)
C7 PETROLEUM Petroleum Engine Crankshaft Rear Seal - Remove
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.