Cat® Digital Voltage Regulator Caterpillar


Wiring Diagrams

Usage:

SR4B 1BN


Illustration 1g01425818
Math Model - per unit block diagram for rotating rectifier excitation system.

Vs - Sensing voltage

Vc - Compensated terminal voltage

Vref - Reference voltage

Kg - Programmed gain

Kp - Proportional gain

Ki - Integral gain

Kd - Derivative gain

Td - Derivative time

Vp - Input from the power source for the excitation system

Vrlmt - Forcing limit

Ta - Alternator time limit

Vr - Regulated voltage

Te - Exciter time constant

Ke - Exciter gain

Efd - Exciter field



Illustration 2g01015474
Typical connections for PMG power input, ABC rotation, and three phase voltage sensing
Notes:
(A) Contact 52a required only for Var/PF control. Var/PF enabled only when 52a is closed, inactive when open.
(B) When excitation disable switch is open, excitation is enabled.
(C) When fault reset switch is momentarily closed, any shutdown fault is reset.
(D) S1 (SPST, spring return to center-off position) adjusts CDVR set point.
(E) Alarm driver and shutdown fault driver are normally off.
(F) The ±10 VDC input provides adjustment of output.
(G) A three-phase PMG is shown in Illustration 2. For single-phase, remove P6-3 connection. For HV machines using two single phase PMGs in series, connect PMG leads 2 and 3 together, and connect leads 1 and 4 to CDVR pins P6-1 and P6-2, respectively.
(H) Sensing potential transformer is required if line voltage exceeds 600 VAC.
(I) When generator rotation is ACB, the connections for the CTB should be reversed.


Illustration 3g01015488
Typical connections for shunt power input, ABC rotation, and single phase voltage sensing.
Notes:
(A) 52a contact required only for Var/PF control. Var/PF enabled only when 52a is closed, inactive when open.
(B) When excitation disable switch is open, excitation is enabled.
(C) When fault reset switch is momentarily closed, any shutdown fault is reset.
(D) S1 (SPST, spring return to center-off position) adjusts CDVR set point.
(E) Alarm driver and shutdown fault driver are normally off.
(F) The ±10 VDC input provides adjustment of output.
(G) Sensing potential transformer is required if line voltage exceeds 600 VAC.
(H) When generator rotation is ACB, the connections for the CTB should be reversed.


Illustration 4g01408526
Typical connections for a SE, L-N directly connected power input, ABC rotation, and single phase voltage sensing (generator less than 480 V).
Notes:
(A) 52a contact required only for Var/PF control. Var/PF enabled only when 52a is closed, inactive when open.
(B) When excitation disable switch is open, excitation is enabled.
(C) When fault reset switch is momentarily closed, any shutdown fault is reset.
(D) S1 (SPST, spring return to center-off position) adjusts CDVR set point.
(E) Alarm driver and shutdown fault driver are normally off.
(F) The ±10 VDC input provides adjustment of output.
(G) Sensing potential transformer is required if line voltage exceeds 600 VAC.
(H) When generator rotation is ACB, the connections for the CTB should be reversed.


Illustration 5g01015546
Typical connections for shunt power input, ABC rotation, and three phase voltage sensing.
Notes:
(A) 52a contact required only for Var/PF control. Var/PF enabled only when 52a is closed, inactive when open.
(B) When excitation disable switch is open, excitation is enabled.
(C) When fault reset switch is momentarily closed, any shutdown fault is reset.
(D) S1 (SPST, spring return to center-off position) adjusts CDVR set point.
(E) Alarm driver and shutdown fault driver are normally off.
(F) The ±10 VDC input provides adjustment of output.
(G) Sensing potential transformer is required if line voltage exceeds 600 VAC.
(H) When generator rotation is ACB, the connections for the CTB should be reversed.


Illustration 6g01015576
Typical connections for PMG power input, ABC rotation, and single phase voltage sensing.
Notes:
(A) 52a contact required only for Var/PF control. Var/PF enabled only when 52a is closed, inactive when open.
(B) When excitation disable switch is open, excitation is enabled.
(C) When fault reset switch is momentarily closed, any shutdown fault is reset.
(D) S1 (SPST, spring return to center-off position) adjusts CAT Digital Voltage Regulator setpoint.
(E) Alarm driver and shutdown fault driver are normally off.
(F) The ±10 VDC input provides adjustment of output.
(G) Three-phase PMG is shown. For single-phase, remove P6-3 connection. For HV machines using two single phase PMGs in series, connect PMG leads 2 and 3 together, and connect leads 1 and 4 to CDVR pins P6-1 and P6-2, respectively.
(H) Sensing potential transformer is required if line voltage exceeds 600 VAC.
(I) When generator rotation is ACB, the connections for the CTB should be reversed.


Illustration 7g01425819
Typical connections for PMG power input, ABC rotation, and single phase voltage sensing.
Notes:
(A) 52a contact required only for Var/PF control. Var/PF enabled only when 52a is closed, inactive when open.
(B) When excitation disable switch is open, excitation is enabled.
(C) When fault reset switch is momentarily closed, any shutdown fault is reset.
(D) S1 (SPST, spring return to center-off position) adjusts CAT Digital Voltage Regulator set point.
(E) Alarm driver and shutdown fault driver are normally off.
(F) The ±10 VDC input provides adjustment of output.
(G) Three-phase PMG is shown. For single-phase, remove P6-3 connection. For HV machines using two single phase PMGs in series, connect PMG leads 2 and 3 together, and connect leads 1 and 4 to CDVR pins P6-1 and P6-2, respectively.
(H) Sensing potential transformer is required if line voltage exceeds 600 VAC.
(I) When generator rotation is ACB, the connections for the CTB should be reversed.


Illustration 8g01112935
Typical connections for internal excitation power input, ABC rotation, and three phase voltage sensing.
Notes:
(A) 52a contact required only for Var/PF control. Var/PF enabled only when 52a is closed, inactive when open.
(B) When excitation disable switch is open, excitation is enabled.
(C) When fault reset switch is momentarily closed, any shutdown fault is reset.
(D) S1 (SPST, spring return to center-off position) adjusts CDVR set point.
(E) Alarm driver and shutdown fault driver are normally off.
(F) The ±10 VDC input provides adjustment of output.
(G) Sensing potential transformer is required if line voltage exceeds 600 VAC.
(H) When generator rotation is ACB, the connections for the CTB should be reversed.


Illustration 9g01112701
Typical connections for PMG power input, ABC rotation, and single phase voltage sensing (generator less than 600 V).
Notes:
(A) 52a contact required only for Var/PF control. Var/PF enabled only when 52a is closed, inactive when open.
(B) When excitation disable switch is open, excitation is enabled.
(C) When fault reset switch is momentarily closed, any shutdown fault is reset.
(D) S1 (SPST, spring return to center-off position) adjusts CDVR set point.
(E) Alarm driver and shutdown fault driver are normally off.
(F) The ±10 VDC input provides adjustment of output.
(G) Three-phase PMG is shown. For single-phase, remove P6-3 connection. For HV machines using two single phase PMGs in series, connect PMG leads 2 and 3 together, and connect leads 1 and 4 to CDVR pins P6-1 and P6-2, respectively.
(H) Sensing potential transformer is required if line voltage exceeds 600 VAC.
(I) When generator rotation is ACB, the connections for the CTB should be reversed.


Illustration 10g01112717
Typical connections for PMG power input and three phase direct voltage sensing (generator less than 600 V)
Notes:
(A) 52a contact required only for Var/PF control. Var/PF enabled only when 52a is closed, inactive when open.
(B) When excitation disable switch is open, excitation is enabled.
(C) When fault reset switch is momentarily closed, any shutdown fault is reset.
(D) S1 (SPST, spring return to center-off position) adjusts CDVR set point.
(E) Alarm driver and shutdown fault driver are normally off.
(F) The ±10 VDC input provides adjustment of output.
(G) Three-phase PMG is shown. For single-phase, remove P6-3 connection.
(H) Sensing potential transformer is required if line voltage exceeds 600 VAC. For HV machines using two single phase PMGs in series, connect PMG leads 2 and 3 together, and connect leads 1 and 4 to CDVR pins P6-1 and P6-2, respectively.
(I) When generator rotation is ACB, the connections for the CTB should be reversed.


Illustration 11g01429193
Typical connections for cross current compensation


Illustration 12g01429203
Typical connections for cross current compensation (two CDVR's).


Illustration 13g01429204
Typical connections for cross current compensation (one CDVR and one DVR).


Illustration 14g01112822
Typical connections for a manual voltage control

Caterpillar Information System:

2004/04/01 New Rocker Arm Improves Lubrication {1123}
G3406 Engines Engine Oil Pan
C11 and C13 Engines for Caterpillar Built Machines Inlet and Exhaust Valve Seat Inserts - Remove and Install
Customer Interface for the 3512B Well Fracturing Engine (ADEM II){1408} Customer Interface for the 3512B Well Fracturing Engine (ADEM II){1408}
2003/09/01 Improved Pump Drive Gear for an Auxiliary Sea Water Pump {1242}
C11 and C13 Engines for Caterpillar Built Machines Front Cover - Install
C15 and C18 Engines for Caterpillar Built Machines Injector Solenoid Circuit - Test
2003/08/01 An Improved Stub Shaft is Used for Engines with Dual Vibration Dampers {1237, 5569}
C11 and C13 Engines for Caterpillar Built Machines Front Cover - Remove
G3520C and G3520E Generator Set Engines Component Location
C11 and C13 Engines for Caterpillar Built Machines Gear Group (Front) - Install
3512C and 3516C Marine Auxiliary and Generator Set Engines Gas Pressure Regulator Condensation - Drain
G3406 Engines Engine Oil Pan
C11 and C13 Engines for Caterpillar Built Machines Inlet and Exhaust Valve Guides - Remove and Install
G3406 Engines Engine Oil Pan
2003/08/04 There Is a New Maximum Temperature for 2W-8147 Gear {1204}
2003/10/01 Fuel Transfer System for Power Modules {1256}
2003/09/01 There Is a New Maximum Temperature for 2W-8147 Gear {1204}
G3520C and G3520E Generator Set Engines Air/Fuel Ratio Control
2003/09/01 There Is a New Maximum Temperature for 2W-8147 Gear {1204}
Installation Instructions for the 240-0716 Tube Kit for the High Pressure Oil Line for the Hydraulic Electronic Unit Injector (HEUI) Pump{1307, 1714} Installation Instructions for the 240-0716 Tube Kit for the High Pressure Oil Line for the Hydraulic Electronic Unit Injector (HEUI) Pump{1307, 1714}
G3500 Generator Sets Ignition System Timing - Check/Adjust
3456 Generator Sets Insulation - Test
C11 and C13 Engines for Caterpillar Built Machines Rocker Shaft - Disassemble
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.