Cat® Digital Voltage Regulator Caterpillar


Reactive Voltage Droop

Usage:

SR4B 1BN
The parameters that are related to voltage regulation with reactive droop are listed below.

  • Rated generator voltage

  • Generator PT primary voltage rating

  • Generator PT secondary voltage rating

  • Voltage set point

  • Generator frequency

  • Knee frequency

  • Integral gain

  • Derivative gain

  • Proportional gain

  • Loop gain

  • Generator CT current primary rating

  • Generator CT current secondary rating

  • Load compensation mode

  • Droop percentage

  • Rated generator current

  • Programmable input (current firmware only)

Two primary objectives of parallel generator operation are to share the following system electrical load components:

  • Real power requirements

  • Reactive power requirements

The engine governors will control sharing of the real power requirements (kW). The voltage regulator will control sharing of the reactive power requirements (KVAR) of the total system load. There exists the possibility that the output voltage of one paralleled generator is slightly higher than the other generators that are linked together. The generator with the slightly higher output voltage will supply a lagging reactive current to the other generators connected in the group. The current will circulate between generators, possibly causing ampere overloading. One method of minimizing the effect is to cause an individual generator output voltage to sag, or "droop". The droop is in proportion to the lagging reactive current flow from the generator as measured with a current transformer (CT).

For proper reactive load sharing, the regulator must know the following:

  • The rated generator output current

  • The CT current at rated generator current

  • The desired percentage of output voltage droop when the generator is at rated reactive output current

As reactive lagging generator output current increases, the regulator will cause the output voltage to droop (lower the voltage) proportionally. If the measured reactive output current is leading, the output voltage will rise. In either case, this action will tend to reduce the reactive current for better KVAR sharing with other units. The droop percentage controls how much the generator output voltage will vary for a given amount of reactive current.

The polarity of the CT that is used must be correct for the voltage to droop with lagging current flow. The CT must be installed on phase B. Reactive droop compensation and line droop compensation work opposite of one another. Reactive droop compensation and line droop compensation and cannot be used at the same time.

Caterpillar Information System:

Cat® Digital Voltage Regulator Line Loss Compensation
Cat® Digital Voltage Regulator Voltage Regulation
Cat® Digital Voltage Regulator Loading and Stopping Profile
2003/06/23 Troubleshooting Low Pressure Fuel System Problems for Machine Engines {1250, 7569}
C7 On-highway Engine Fan Drive Mounting Group
Cat® Digital Voltage Regulator Startup Profile Function
2003/06/23 New Connecting Rod {1218, 1225}
2003/06/01 New Top Piston Ring {1215}
C7 Engines for Combat and Tactical Vehicles Refill Capacities and Recommendations
UPS 250, UPS 300, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supply Component Location - MMU Cabinet
C7 Engines for Combat and Tactical Vehicles 0164-04 Injection Actuation Pressure voltage low (15)
C7 Engines for Combat and Tactical Vehicles 0164-03 Injection Actuation Pressure voltage high (15)
New Fractured Connecting Rod is Now Available for Certain Engines {1218} New Fractured Connecting Rod is Now Available for Certain Engines {1218}
Cat® Digital Voltage Regulator Cross Current Compensation
Cat® Digital Voltage Regulator KVAR Regulation
C7 Engines for Combat and Tactical Vehicles Warning Lamp Circuit - Test
Cat® Digital Voltage Regulator Power Factor Regulation
2003/08/11 New Recommended Maintenance Intervals for Coolant and Temperature Regulators {1350, 1355, 1395}
3508B, 3512B, 3516B, 3512C and and 3516C Auxiliary Engines, Generator Set Engines, and Generator Sets Instrument Panel
2003/06/01 Improved Rectifiers Increases Service Life {4473}
G3300 Engines Cooling System Coolant Analysis (Level I) - Obtain
C15 and C18 Generator Set Engines Crankshaft Front Seal - Remove
G3300 Engines Cooling System Coolant Analysis (Level II) - Obtain
G3500 Generator Sets Reference Information