UPS 120, UPS 150, UPS 250 and UPS 300 Uninterruptible Power Supplies Caterpillar


Generator Set Start Module

Usage:

UPS 250 APZ



Illustration 1g00741402

Generator Set Start Module

System Description

The Generator Set Start Module provides redundant starting capability for the Caterpillar generator set. This option increases the generator's starting reliability. The Generator Set Start Module should be used as a redundant starting option to batteries.

Note: Caterpillar recommends the Generator Set Start Module in parallel to the Starting Power Paralleling Option. The Starting Power Paralleling Option provides isolation between the batteries and the Generator Set Start Module. The Generator Set Start Module can also be used with a separate dedicated starter.

The Generator Set Start Module provides auxiliary power to a starter. The auxiliary power comes from the Uninterruptible Power Supply (UPS).

Note: The auxiliary power can be up to 1000 amperes at 24 VDC.

When starting power is provided from the UPS flywheel, the standby generator will ensure a constant voltage source with the following characteristics:

  • independent of starting batteries

  • tolerant of wide temperature variances

  • monitored by the UPS

The Generator Set Start Module can be mounted on the floor or on a wall. When the specified cable and the provided connector are used, the length of the cable should not exceed 152.40 m (500.00 ft). The length of the cable between the Generator Set Start Module and the engine starter should not exceed 7.62 m (25.00 ft).

Specifications

Table 1
Electrical Specifications    
Nominal Voltage (Voltage Regulation)     24 VDC (+10% to -40%) at 0 − 1000 amperes DC    
Current Rating     1000 amperes    
Input Voltage     Up to 720 VAC (line to line)    
Output Fusing     1000 amperes    
Rated number of start cycles     5 cycles at 10 seconds per cycle    

Table 2
Physical Dimensions    
Height    
914.40 mm (36.0 inch)    
Depth    
310 mm (12.2 inch)    
Width    
610 mm (24 inch) (1)    
Weight    
181.44 kg (400 lb)    
Distance from UPS     less than
152.4 m (500 ft)    
Distance from engine starter     less than
7.62 m (25 ft)    
Three-phase AC line from UPS (2)     #6 AWG with 4 wires    
DC cables     3/0 cable is the minimum size for a 1% maximum loss at 1000 amperes.    
Indoor installation     NEMA 1 construction    
Operating temperature    
−20 °C (−4.0 °F) to
50 °C (122.0 °F)    
Storage temperature    
−25 °C (−13.0 °F) to
70 °C (158.0 °F)    
Humidity     5% to 95% (3)    
( 1 ) This dimension includes the width of the heat sink.
( 2 ) This item is not provided.
( 3 ) non-condensable

Table 3
Fuses    
Location     Quantity    
Bus Inductor Fuse for the Generator Set Start Module "F9"     1    
The Generator Set Start Filter for the Generator Set Start Module (1)     2    
( 1 ) UPS 250 model only

Information Plate




Illustration 2g00825894

Information Plate for the Generator Set Start Module

Receiving and Handling

Open the attached document that is located on the outside of the crate. This document will contain the instructions for removing the system and handling the system.

Site Preparation

  • Ensure that the floor can support the weight of the unit.

  • In order to service the unit, ensure that there is 1067.00 mm (42.00 inch) of clearance in front of the unit. Ensure that there are 160.27 mm (6.31 inch) of clearance on the unit's right side. This clearance is needed for the entry of the cable and for air circulation. Ensure that there are 236.47 mm (9.31 inch) of clearance on the unit's left side for air circulation.

Mounting

Clearance for the Door




Illustration 3g00821917

Requirements for the Clearance of the Door for the Generator Set Start Module

The Generator Set Start Module can be anchored to the floor or the Generator Set Start Module can be mounted on a wall. While the Generator Set Start Module is being installed, ensure that a radius of 518.16 mm (20.40 inch) is maintained for door swing. Refer to illustration 3.

Mounting on a Floor




Illustration 4g00821922

Clearance Requirements for the Generator Set Start Module for Mounting on the Floor

(A) 50.80 mm (2.00 inch)

(B) 236.47 mm (9.31 inch)

(C) Holes for 5/16 inch hardware

(D) 228.60 mm (9.00 inch)

(E) 160.27 mm (6.31 inch)

(F) 25.40 mm (1.00 inch)

(G) 25.40 mm (1.00 inch)

(H) 457.20 mm (18.00 inch)

(I) 508.00 mm (20.00 inch)

(J) 1067 mm (42.00 inch)

(K) 904.75 mm (35.62 inch)

Inspect the location for the installation. Ensure that the floor meets the load requirements of the Generator Set Start Module. Ensure that there is sufficient space between the Generator Set Start Module and any obstructions. Refer to illustration 4.

Mounting on a Wall




Illustration 5g00822188

Dimensions for Mounting the Generator Set Start Module on a Wall

(A) 63.50 mm (2.50 inch)

(B) 381.00 mm (15.00 inch)

(C) 555.75 mm (21.88 inch)

(D) Mounting holes provisions for 5/16 inch mounting hardware

(E) 331.72 mm (13.06 inch)

Inspect the location for the installation. Ensure that the wall meets the load requirements of the Generator Set Start Module. Ensure that sufficient clearance for the door is maintained.

The Generator Set Start Module has four mounting holes (D). These mounting holes are located on the back panel. These holes will accommodate 5/16 inch mounting hardware. Refer to illustration 5.

Electrical Connections

The Generator Set Start Module should be installed per the National Electrical Code (NEC) and other applicable codes. The size of the cable and the size of the conduit should be based on Start Module specifications. Class 1 wiring methods should be used.




Illustration 6g00822212

Generator Set Start Module Right Side View

(1) Holes for Conduit for 24 VDC

(1) Holes for Conduit for Control Power

(1) Holes for Conduit for Ground

(2) Entrance for the AC Voltage Bottom Entry Option or Side Entry Option

(A) 309.88 mm (12.20 inch)

The holes must be drilled in the bottom of the lower access panel or the holes must be drilled in the side of the lower access panel (1, 2) in order to allow the cables to enter the Generator Set Start Module. Refer to illustration 6. The location of the holes will depend on the use of the following options: floor mounting option and wall mounting option. The input cables and the output cables must be routed in separate conduits.

Control Power (UPS 250)

Note: This section pertains to the UPS 250 only.




Illustration 7g00872251

Terminal Block for the Generator Set Start Module

(3) Output To the Generator Set +24 VDC

(4) Output To the Generator Set −24 VDC

(5) Input From Generator Set +24 VDC

(6) Input From Generator Set −24 VDC

------ WARNING! ------

The inside compartments of the Generator Set Starting Module can contain the risk of electric shock or hazardous energy levels. Personal inuury can result from Electric Shock. Do not touch live electric parts.

----------------------

The Control Power Signals for the Generator Set Start Module come from the connected generator and from the UPS. During starting attempts, either the battery for the generator set or the Caterpillar UPS will provide power for the Generator Set Control Circuits.

Use the following information to assemble the wires:

  • Wire size must be between #10 AWG and #14 AWG.

  • In order to connect the wire to the terminals, attach ring lugs (# 8 AWG) to the wire.

  • Maximum length of the wire is 15.24 m (50.00 ft).

24 VDC Output Cable




Illustration 8g00913187

Location for the connection of the 24 VDC Output Power Cable

(7) AC Connector

(B) 609.60 mm (24.00 inch)

(C) 914.40 mm (36.00 inch)

(D) Terminal Locations for the 24 VDC ( 3/8 inch hardware)

------ WARNING! ------

The inside compartments of the Generator Set Starting Module can contain the risk of electric shock or hazardous energy levels. Personal inuury can result from Electric Shock. Do not touch live electric parts.

----------------------

Use the "+" terminal and the "−" terminal (D) in order to connect the cable for output power (24 VDC) to the generator. The "+" terminal and the "−" terminal (D) are located in the lower access compartment of the Generator Set Start Module. Refer to illustration 8.

Configure the cable in the following manner:

  • no smaller than 3/0

  • 3/8 inch lugs and hardware

  • the maximum cable length from the generator 7.62 m (25.00 ft)

  • terminal torque 63.72 N·m (47 lb ft)

  • use nonferrous conduit

24 VDC Output Cable Connections (for Systems without a Starting Power Paralleling Module)

Note: This configuration requires a dedicated starting motor for the generator.

------ WARNING! ------

To avoid personal injury from electrical shock, disconnect the AC Cable Connector that is located in the lower access compartment of the Generator Set Start Module before working on this equipment.

----------------------

------ WARNING! ------

Personal injury or death can result from high voltage.

When power generation equipment must be in operation to make tests and/or adjustments, high voltage and current are present.

Improper test equipment can fail and present a high voltage shock hazard to its user.

Make sure the testing equipment is designed for and correctly operated for high voltage and current tests being made.

When servicing or repairing electric power generation equipment:

  • Make sure the unit is off-line (disconnected from utility and/or other generators power service), and either locked out or tagged DO NOT OPERATE.

  • Remove all fuses.

  • Make sure the generator engine is stopped.

  • Make sure all batteries are disconnected.

  • Make sure all capacitors are discharged.

Failure to do so could result in personal injury or death. Make sure residual voltage in the rotor, stator and the generator is discharged.

----------------------

------ WARNING! ------

To avoid personal injury from electrical shock, ensure that the negative battery cable is disconnected first.

----------------------

  1. Disconnect the negative battery cable from the "-" terminal of the battery.

  1. Disconnect the positive battery cable from the "+" terminal of the battery.

  1. Route the DC cable from the Generator Set Start Module's "+" terminal to the "+" terminal of the dedicated starting motor. Tighten to 63.72 N·m (47.00 lb ft).

  1. Route the DC cable from the Generator Set Start Module's "-" terminal to the "-" terminal of the dedicated starting motor. Tighten to 63.72 N·m (47.00 lb ft).

  1. Reconnect the battery cables for the Generator Set.

    Note: Connect the positive cable to the "+" terminal of the battery. Connect the negative cable to the "-" terminal of the battery.

    Note: Battery voltage is now applied to the Generator Set Start Module.

  1. Connect the AC Cable to the Generator Set Start Module. Refer to illustration 8.

  1. The Connection of the Generator Set Start Module is complete.

The Cable for the UPS to Generator Set Start Module




Illustration 9g00869337

The AC Input Connector for the Generator Set Start Module

(8) Cable Shield

(9) Terminal lugs (#6 AWG wire) for 1/4 inch studs

(10) AC input connector

(11) "A" phase

(12) No Connection

(13) "B" phase

(14) "C" phase

The cable that is used to connect to the UPS must comply with the following parameters. This cable is not included.

  • Maximum length of the cable is 152.4 m (500 ft).

  • Cable must be run in a conduit.

  • Cable must comply with all local ordinances.

Connect one end of the AC cable to the AC Input Connector (7) for the Generator Set Start Module. Refer to illustration 8.

Note: The penetration of the wall of the cabinet requires a female threaded fitting on the end of the conduit in order to accommodate strain relief.

The remaining end of the AC cable is connected to the AC output terminal blocks which are located inside the UPS. The UPS AC Output Terminals can be found in one of two locations. Refer to illustration 11 and illustration 10.

In order to connect the AC cable to the AC output terminal blocks, perform the following steps:

  1. Strip a sufficient amount of cable shielding from the cable so that terminal lugs can be attached.

  1. Attach terminal lugs to the cable. Terminal lugs should be sized for 1/4 inch studs.

  1. Attach the cable to the Caterpillar UPS AC Output Terminals.

AC Output Terminal Location for the UPS 250




Illustration 10g00822965

AC Out terminal location for the UPS 250

On the UPS 250 (the 50 Hz and 60 Hz units), the AC output terminals are located on the AC capacitor bank panel. The ground connection is located on the Generator Set Start Module Inductor Panel.

AC Output Terminal Location for the UPS 300




Illustration 11g00822978

AC Output terminal location for the UPS 300

On the following models, the AC Output terminals and the ground terminal are located on the Generator Set Start Module Inductor Panel:

  • UPS 250 (50 Hz unit)

  • UPS 300 (60 Hz unit)

  • UPS 500 (50 Hz unit)

  • UPS 600 (60 Hz unit)

  • UPS 750 (50 Hz unit)

  • UPS 900 (60 Hz unit)

Grounding

The grounding wire should meet the following parameters:

  • # 6 AWG wire

  • a lug which will accommodate a 1/4 inch stud

  • maximum length of 7.62 m (25.00 ft)

Run a ground wire from the ground stud for the generator set to the Generator Set Start Module. The ground stud is located in the lower access compartment. Disconnect the AC ground from the upper cabinet. Insulate the AC ground from the upper cabinet.

Note: If there is a connection between the AC Input Connector and the ground, remove the connection before grounding the Generator Set Start Module to the Generator Set. Refer to illustration 8.

Disconnecting the Generator Set Start Module

------ WARNING! ------

The inside compartments of the Generator Set Starting Module can contain the risk of electric shock or hazardous energy levels. Personal inuury can result from Electric Shock. Do not touch live electric parts.

----------------------

To disconnect the Generator Set Start Module from the power source for the UPS, unplug the AC cable connector. The Generator Set Start Module's AC cable connector (7) is located inside the Lower Access Compartment. Refer to illustration 8. Make sure that the generator set start module does not attempt to start the engine.

Starting Power Paralleling Option




Illustration 12g00932621

(1) Output (+)

(2) Input 2 (+)

(3) Input 1 (+)

(4) Input/Output (-)

(A) 609.60 mm (24.00 inch)

(B) 531.88 mm (20.94 inch)

(C) 762.00 mm (30.00 inch)

(D) 684.28 mm (26.94 inch)

Installation Notes

The Starting Power Paralleling Option should be installed per the National Electrical Code (NEC) and all other applicable codes. The size of the cable and the size of the conduit should be determined by the specifications for the Starting Power Paralleling Option. Class 1 methods for wiring need to be used.

Install the Starting Power Paralleling Option in a clean environment that is free of dust.

When the Starting Power Paralleling Option is mounted on a wall, ensure that the wall can support the weight of the module (79.4 kg (175 lb)).




Illustration 13g00932672

(E) 457.20 mm (18.00 inch)

(F) 76.20 mm (3.00 inch)

(G) 793.75 mm (31.25 inch)

(H) 11.18 mm (0.44 inch)

The Starting Power Paralleling Option has four mounting brackets that are located on the back of the module. These four mounting brackets have provisions for 5/16 inch mounting hardware.




Illustration 14g00932673

(I) 598.93 mm (23.58 inch)

Ensure that a radius of 598.93 mm (23.58 inch) is maintained for the swing of the door. Ensure that there is 431.8 mm (17 inch) of front clearance.

Holes must be punched in the module in order to accommodate the entry of the cable and the points of exit. The location of these holes will depend on the location of the Starting Power Paralleling Option with respect to the Generator Set and the Generator Set Start Module.

Input 1 and Input 2 are interchangeable. Input 1 and Input 2 can be used for the Generator Set Start Module. Input 1 and Input 2 can be used for the Batteries for Generator Set.

DC Cable Connections (Generator Set Start Module to Starting Power Paralleling Option)

------ WARNING! ------

To avoid personal injury from electrical shock, disconnect the AC Cable Connector that is located in the lower access compartment of the Generator Set Start Module before working on this equipment.

----------------------

------ WARNING! ------

Personal injury or death can result from high voltage.

When power generation equipment must be in operation to make tests and/or adjustments, high voltage and current are present.

Improper test equipment can fail and present a high voltage shock hazard to its user.

Make sure the testing equipment is designed for and correctly operated for high voltage and current tests being made.

When servicing or repairing electric power generation equipment:

  • Make sure the unit is off-line (disconnected from utility and/or other generators power service), and either locked out or tagged DO NOT OPERATE.

  • Make sure the generator engine is stopped.

  • Make sure all batteries are disconnected.

  • Make sure all capacitors are discharged.

----------------------

  1. Route the DC cable from the terminal at the Generator Set Start Module "+" to Input 1 of the Positive Bus of the Starting Power Paralleling Option. Tighten to 63.72 N·m (47 lb ft).

  1. Route the DC cable from the "-" terminal of the Generator Set Start Module to the Input/Output of the Negative Bus of the Starting Power Paralleling Option. Tighten to 63.72 N·m (47 lb ft).

DC Cable Connections (Starting Motor for the Generator Set to Starting Power Paralleling Option)

------ WARNING! ------

To avoid personal injury from electrical shock, ensure that the negative battery cable is disconnected first.

----------------------

  1. Disconnect the negative battery cable from the "-" terminal of the battery.

  1. Disconnect the positive battery cable from the "+" terminal of the battery and the "+" terminal of the starting motor.

    Note: This cable will not be reused.

  1. Fabricate 2 cables. Use 3/0 cable as a minimum with 3/8 inch hardware (Grade 8) for the lugs. Maximum cable length is 7.62 m (25 ft) from the generator set. Tighten to 63.72 N·m (47 lb ft). If a conduit is used, use a conduit that is nonferrous in order to avoid heating. Ensure that the cable is long enough to reach from the starting motor to the Starting Power Paralleling Option.

  1. Route the DC cable from the "+" terminal of the starting motor to the Positive bus of the Starting Power Paralleling Option. Tighten to 63.72 N·m (47 lb ft).

  1. Install the DC cable and route the DC cable from the "-" terminal of the starting motor to the negative bus of the Starting Power Paralleling Module. Tighten to 63.72 N·m (47 lb ft).

DC Cable Connections (Batteries for the Generator Set to Starting Power Paralleling Option)

  1. Fabricate cable. Use 3/0 cable as a minimum with 3/8 inch hardware (Grade 8) for the lugs. Maximum cable length is 7.62 m (25 ft) from the generator set. Tighten to 63.72 N·m (47 lb ft). If a conduit is used, use a conduit that is a nonferrous type in order to avoid heating. Ensure that the cable is long enough to reach from the starting motor to the Starting Power Paralleling Option.

  1. Route the DC cable from the "+" terminal of the battery of the Generator Set to Input 2 of the Positive bus of the Starting Power Paralleling Module. Tighten to 63.72 N·m (47 lb ft).

Grounding

  • Fabricate the Cable.

  • Use #6 AWG wire

  • Attach a lug that will accommodate a 1/4 inch stud.

  • The maximum length of the wire should not exceed 3.05 m (10 ft).

  1. Route the ground cable from the ground stud of the Starting Power Paralleling Module to the Ground stud of the Generator Set.

  1. Tighten the ground stud to 63.72 N·m (47.00 lb ft).

  1. Reconnect the battery cables for the Generator Set.

    Connect the positive cable to the positive terminal of the battery. Connect the negative cable to the negative terminal of the battery.

  1. Connect the AC cable for the Generator Set Start Module to the Generator Set Start Module. Refer to illustration 8.

    The connection of the Starting Power Paralleling Module is complete.

Reference Materials

Symbols

There may be several specific symbols on the Generator Set Start Module. Refer to Operation and Maintenance Manual, "Symbols" for the related information.

System Schematic

Refer to illustration 15 for the Gen Set Start Option Schematic.




Illustration 15g00867048

Connection Diagram




Illustration 16g00869435

Caterpillar Information System:

Alternator - Delco 27SI Insulated Screw - Check
797F Off-Highway Truck Steering System Piston Pump (Steering) Pressure - Test and Adjust
3500 Engines Power Take-Off Clutch
2002/03/01 A New Spark Plug Extender Is Used In The Ignition Systems For The Engine Supervisory System (ESS) {1550}
3500B Engines Auxiliary Water Pump
3500 Industrial Engine Attachments Cooling System
Alternator - Delco 27SI Rectifier - Test
3524B and C175 Engines for Off-Highway Truck/Tractors Auxiliary Water Pump
Alternator - Delco 27SI Diode Assembly - Test
2002/03/01 Software Available For Programming Allen-Bradley Programmable Logic Controller (PLC) {1000, 7620}
3500 Generator Set Engines Auxiliary Water Pump
3500 Industrial Engine Attachments Duplex Oil Filter
3406E, C12, C15 and C18 Marine Engines Engine Speed/Timing Sensor Circuit - Test
UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies UPS View Software
UPS 120, UPS 150, UPS 250 and UPS 300 Uninterruptible Power Supplies Remote Status Panel
UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Related Options
UPS 250 and UPS 300 Uninterruptible Power Supplies Battery - Replace
3406E, C12, C15 and C18 Marine Engines Injector Solenoid Circuit - Test
C-9 Engine for TK711, TK721, TK722, TK732, TK741, TK751, and TK752 Track Feller Bunchers Injector Solenoid Circuit - Test
3500 Industrial Engine Attachments Electrical System
793F and 797F Off-Highway Trucks Power Train Electronic Control System MID 081 - CID 0127 - FMI 03
Alternator - Delco 27SI Residual Magnetism - Restore
C9 Marine Engines Event Codes
2002/04/01 A Different Mounting Nut Is Required For The Hydrax Actuator {1716}
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.