Electronic Modular Control Panel II (EMCP II) Caterpillar


Engine Does Not Shutdown (for EUI Engines)

Usage:

3406B 4JK
System Operation Description:

The engine does not shut down when a shutdown fault occurs.

Note: It is critical that GSC setpoint 023 is correct for the engine application. Ensure that setpoint 023 is programmed correctly for the engine application before continuing with this procedure.

There are several possible causes when a shutdown fault occurs and an engine does not shut down:

  • Operator Error: The operating conditions of the generator may not be understood by the operator. Ensure that the condition is one that should cause an engine shutdown.

  • The Fault Is Overridden Or The Fault Is Disabled.: It is possible to program the GSC in order to override certain shutdown faults. An overridden shutdown fault will be treated as an alarm fault. The YELLOW fault alarm indicator will be FLASHING instead of the RED fault shutdown indicator. If the GSC is programmed in order to disable a particular fault, there will not be any fault indicators. Check the setpoints. It is also possible to program the engine ECM to override certain shutdown faults. See Troubleshooting, RENR2227, "3406E and 3456 EPG Engines" for more information on programming the engine ECM.

  • The Setpoints Are Incorrect For The Application. : It is possible to program the GSC setpoints to a value that does not allow the situation to be recognized by the GSC as a shutdown condition. In this case, check the appropriate setpoints for correct values.

  • Faulty Component The following problems prevent the engine stopping procedure.engine ECM, GSC and a broken harness wire or a shorted harness wire. The controller will be shutting down the engine.

Test Step 1. CHECK FOR DIAGNOSTIC CODES

  1. Check the GSC for a diagnostic code on the upper display.

Expected Result:

The GSC should show a diagnostic code on the upper display.

Results:

  • YES - The GSC shows a diagnostic code on the upper display.

    Repair: See theTesting and Adjusting section of this book for the diagnostic code that is displayed on the GSC.

    Stop.

  • NO - The GSC does NOT show a diagnostic code on the upper display. Proceed to Test Step 2.

Test Step 2. CHECK THE YELLOW FAULT ALARM INDICATOR

  1. Check the display of the GSC for the yellow fault alarm indicator.

Expected Result:

The yellow fault alarm indicator is ON CONTINUOUSLY.

Results:

  • YES - The yellow fault alarm indicator is ON CONTINUOUSLY. The GSC has been programmed to override the normal shutdown response. The setpoints have been modified and the GSC treats the condition as an alarm fault. The engine will continue to run.

    Repair: In order to view the setpoints, seeSystems Operation, "Engine/Generator Setpoint Viewing OP2". In order to reprogram the setpoints, see Systems Operation, "Engine/Generator Programming OP5".

    Stop.

  • NO - The yellow fault alarm indicator is not illuminated at all. Proceed to Test Step 3.

Test Step 3. CHECK FOR THE RED FAULT SHUTDOWN INDICATOR

  1. Check the display area of the GSC for the red fault shutdown indicator.

Expected Result:

The red fault shutdown should be FLASHING.

Results:

  • YES - The red fault shutdown indicator is FLASHING and the engine remains running. Proceed to Test Step 4.

  • NO - All fault indicators are OFF. A problem that is occurring should cause the GSC to shut down the engine. It is possible to program the GSC setpoints to a value that does not allow the situation to be recognized by the GSC as a shutdown condition.

    Repair: Check the appropriate setpoints for correct values. In order to view the setpoints, see System Operation, "Engine/Generator Setpoint Viewing OP2". In order to reprogram the setpoints, see System Operation, "Engine/Generator Programming OP5".

    Stop.

Test Step 4. CHECK K1 INDICATOR ON GSC DISPLAY

  1. The red fault shutdown indicator is FLASHING and the engine remains running.

  1. Check the upper display of the GSC.

Expected Result:

TheK1 symbol is showing on the GSC upper display.

Results:

  • YES - The K1symbol is showing on the GSC upper display. The red fault shutdown indicator is FLASHING and the engine remains running. The GSC may have failed.

    Repair: The GSC may have failed. It is unlikely that the GSC has failed. Exit this procedure and perform this entire procedure again. If the problem remains, replace the GSC.

    Stop.

  • NO - The K1symbol is not showing at all on the GSC upper display. Proceed to Test Step 5.

Test Step 5. CHECK THE GSC RELAY MODULE.

The engine remains running and the red fault shutdown indicator is FLASHING.

  1. In the control panel, remove BOTH of the wires from RM-13 on the GSC.

Expected Result:

The engine should shut down.

Results:

  • OK - The engine shuts down.

    Repair: The GSC Relay Module may have failed. It is unlikely that the GSC Relay Module has failed. Exit this procedure and perform this entire procedure again. If the problem remains, replace the GSC Relay Module. See Testing And Adjusting, "EMCP Electronic Control (Relay Module) - Replace".

    Stop.

  • NOT OK - The engine runs and the engine will start. Proceed to Test Step 6.

Test Step 6. CHECK THE SYSTEM BY USING THE ESPB.

The engine remains running and the red fault shutdown indicator is FLASHING.

  1. Push the emergency stop push button (ESPB).

Expected Result:

The engine should shut down.

Results:

  • OK - The engine does shutdown. Proceed to Test Step 7.

  • NOT OK - The engine does NOT shut down.

    Repair: The engine ECM may have failed. Refer to Troubleshooting, RENR2227, "3406E and 3456 EPG Engines".

    Stop.

Test Step 7. CHECK THE WIRING BETWEEN THE ENGINE ECM AND THE GSC.

The engine remains running and the red fault shutdown indicator is FLASHING.

  1. Check the wiring between RM-13 of the GSC and J1-8 and J1-14 of the engine ECM. Check for shorts, open connections, or damaged wires.

Expected Result:

The wiring has a problem.

Results:

  • OK - The wiring is damaged.

    Repair: Troubleshoot and repair the wiring. See Generator Set Wiring Diagram in Testing And Adjusting, "Schematics And Wiring Diagrams". Verify that the repair corrects the problem.

    Stop.

  • NOT OK - The wiring is not damaged at all. The engine ECM may have failed.

    Repair: The engine ECM may have failed. Refer to Troubleshooting, RENR2227, "3406E and 3456 EPG Engines".

    Stop.

Caterpillar Information System:

3512B Petroleum Engines with the ADEM 2 Electronic Control Module Permanent Timing Calibration Sensor
3512B Petroleum Engines with the ADEM 2 Electronic Control Module Injector Solenoids
Power Module Switchgear (Low Voltage and Medium Voltage) Glossary
UPS 250, UPS 300, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supply Contactor - Remove and Install
Electronic Modular Control Panel II (EMCP II) Starting Motor Remains Engaged (for MUI Engines)
2001/11/19 A New Edition of the Special Publication, SEBD0640, "Oil and Your Engine" is Available {1348}
2001/11/01 A New Edition of the Special Publication, SEBD0640, "Oil and Your Engine" is Available {1348}
3512B Petroleum Engines with the ADEM 2 Electronic Control Module Ether Injection System
2002/02/01 Turbocharger Compressor Bypass Valve is used on 3616 Engines {1081}
3512B Petroleum Engines with the ADEM 2 Electronic Control Module Engine Speed/Timing Sensor
3126 Truck Engine (Military) Air Inlet and Exhaust System - Inspect
3126 Truck Engine (Military) Gear Group (Front) - Time
G3500 Engines Specifications
Electronic Modular Control Panel II (EMCP II) Engine Does Not Shutdown (for MUI Engines)
CIPI UNDERCARRIAGE Arrangements: 9Q-5262, 191-4041, and 204-9207 Track Adjuster - Disassemble
CIPI UNDERCARRIAGE Arrangements: 9Q-5262, 191-4041, and 204-9207 Track Adjuster - Assemble
Electronic Modular Control Panel II (EMCP II) GSC Operation Is Erratic
G3500 Engines Plate Locations and Film Locations
Electronic Modular Control Panel II (EMCP II) Display of Voltage or Current Is Zero
Electronic Modular Control Panel II (EMCP II) Display of Voltage or Current is Inaccurate
UPS 250, UPS 300, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supply Fuse - Remove and Install
CIPI UNDERCARRIAGE Arrangements: 9Q-5262, 191-4041, and 204-9207 Final Drive Sprocket - Remove and Install
CIPI UNDERCARRIAGE Arrangements: 9Q-5262, 191-4041, and 204-9207 Travel Brake Valve - Remove
SPT343 Truck Mounted Pumper Model View Illustrations
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.