2001/11/01 Caterpillar


Setting the Desired Rated Speed or Emissions Strategy for Generator Sets {1901}

Usage:

3456 CAH
Generator Set:
3456 (S/N: CAH1-UP; CBX1-UP; CCB1-UP)

Table 1
EPA-Certified Engine Generator Sets Currently Available    
Power Rating     Frequency    
300 ekW (kVA)     60 HZ (50 HZ) as Tier II    
350 ekW (kVA)     60 HZ (50 HZ) as Tier II    
400 ekW (kVA)     60 HZ (50 HZ) as Tier II    
450 ekW (kVA)     60 HZ (50 HZ) as Tier II    
500 kVA     50 HZ as Tier II    
500 ekW     60 HZ as Tier I    

Table 2
Non EPA-Certified Engine Generator Sets Currently Available    
Power Rating     Frequency     Performance Options    
300 ekW (kVA)     60 HZ (50 HZ)     Low emission or low BSFC    
350 ekW (kVA)     60 HZ (50 HZ)     Low emission or low BSFC    
400 ekW (kVA)     60 HZ (50 HZ)     Low emission or low BSFC    
450 ekW (kVA)     60 HZ (50 HZ)     Low emission or low BSFC    
500 ekW (kVA)     60 HZ (50 HZ)     Low emission or low BSFC    

Within each product model ekW (kVA) rating, the dealership can use Caterpillar Electronic Technician (ET) to configure the parameter screen. On EPA-certified engine generator sets and on non EPA-certified engine generator sets, the dealership can choose the desired engine rated speed (and subsequent frequency). In the case of non EPA-certified engine generator sets, the dealership can also choose to operate in ONE of the following performance modes:

  • low emission

  • low BSFC performance

Note: When an engine generator set leaves the factory as EPA certified, the engine generator set must remain EPA certified. Once an engine generator set leaves the factory, a non EPA-certified engine generator set cannot be turned into a EPA-certified engine generator set.

A factory password is required to change 3456 model ekW ratings. Power rating changes are password protected because any changes that are made to the power ratings directly affect the package design configuration. Power rating changes and package design configuration changes must be made at the same time. If power rating changes and package design configuration changes are not made at the same time, performance will be affected. For assistance with power rating changes, consult the Electric Power Application Support Center (ASC). The Electric Power Application Support Center can be reached in the following ways:

  • Phone: (765) 448-2400

  • FAX: (765) 448-2300

  • Email: applicationsupport@cat.com

Caterpillar Information System:

Power Module Switchgear (Low Voltage and Medium Voltage) Manual Parallel Operation
3406E, C-10, C-12, C-15, C-16 and C-18 On-highway Engines Air Inlet Shutoff Circuit - Test
120H, 12H, 135H, 140H, 143H, 160H and 163H Motor Graders Electrical Connector - Inspect
Power Module Switchgear (Low Voltage and Medium Voltage) Base Load Operation
Power Module Switchgear (Low Voltage and Medium Voltage) Standby Operation
Power Module Switchgear (Low Voltage and Medium Voltage) General Operation
G3516B Engines MID 036 - CID 1447 - FMI 12 Fuel Metering Sensor Module malfunction
G3516B Engines MID 036 - CID 1446 - FMI 13 Fuel Metering Module calibration required
Power Module Switchgear (Low Voltage and Medium Voltage) Metering Screen
Power Module Switchgear (Low Voltage and Medium Voltage) Alarm Screen
G3516B Engines MID 036 - CID 1446 - FMI 12 Fuel Metering Module malfunction
C15 and C18 Engines for Caterpillar Built Machines CID 0100 FMI 03 Engine Oil Pressure open/short to +batt
3126 Truck Engine (Military) Diagnostic Flash Code Retrieval
3054 and 3056 Engines 520 Generator Set Control Panel Symbols
3054 and 3056 Marine Generator Set Engines Valve Depth - Inspect
3054 and 3056 Engines 520 Generator Set Control Panel Specification
Power Module Switchgear (Low Voltage and Medium Voltage) Generator Circuit Breaker
3054 and 3056 Engines 520 Generator Set Control Panel Initial Startup Procedure
3126 Truck Engine (Military) Engine Operation
3126 Truck Engine (Military) Maintenance Interval Schedule
3126 Truck Engine (Military) Engine Oil and Filter - Change
3054 and 3056 Marine Generator Set Engines Air Inlet Heater - Test
UPS 250, UPS 300, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supply Dry Contact - Configure
SCT673 Truck Mounted PumperPOD Control Panel - Raise/Lower Blender
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.