Power Module Switchgear (Low Voltage and Medium Voltage) Caterpillar


Standby Operation

Usage:

PM3508 BLM
Standby Operation is automatically initiated when the utility circuit breaker is open and the contacts for the "UTILITY AUX CONTACT" are open. (No electrical continuity exists.) The generator operates as an isochronous machine that is isolated from the utility supply for standby operation. The controls enable automatic standby operation. Automatic operation is initiated locally or automatic operation is initiated remotely by the customer's SCADA system or the building control system. Dead bus closing is allowed for standby operation.

The standby start signal is provided locally or the standby start signal is provided remotely by the customer. This is done by establishing continuity between the "STANDBY START" contacts. When a standby start signal is received, the genset will automatically perform the following functions:

  • Start

  • Attain the rated speed and voltage.

  • Close the generator circuit breaker onto the dead bus.

The customer must ensure that the load bus is disconnected from the utility supply. The customer must ensure that the load is less than the block loading capability of the genset. The generator circuit breaker will trip open when the generator circuit breaker receives a standby shutdown signal. This is done by establishing continuity between the "STANDBY STOP" contacts. The engine will run without a load for the cooldown period. Then, the engine will automatically shut down. The utility may then be reconnected to the load bus.

Ensure that all targets for the generator protective relays have been reset. Ensure that the emergency stop push buttons are reset.

Note: Examine the "UTILITY AUX CONTACT". If the indicator for "UTILITY BREAKER CLOSED" is illuminated, a jumper is installed at the "UTILITY AUX CONTACT" for peak shaving. This jumper is required for base load operation because the "UTILITY AUX CONTACT" contact is not available.




Illustration 1g00853858

"MAIN" Screen

(1) Icon for the genset

(2) Indicator for the state of the system

(3) generator bus

(4) Generator circuit breaker

(5) Button for "START LOAD"

(6) Button for "STOP UNLOAD"

(7) Indicator for the mode of the system

(8) Indicator for remote start enable

(9) Setpoint for base load operation

(10) Indicator for the position of the engine control switch (ECS)

(11) Indicator for local mode or remote mode

(12) Indicator for the status of the utility circuit breaker

(13) Indicator for the status of the generator multifunction relay (GMR)

(14) Indicator for the "UTTR TRIP"

(15) Utility bus

(16) Indicator for the status of the utility multifunction relay (UMR)

(17) Button for the "MAIN" screen

Local Start For Standby Operation

Place the controls in the following positions:

Table 1
CONTROL     POSITION/SELECTION     ACTION    
"DROOP-ISOCHRONOUS" switch     "ISOCHRONOUS"     Engine speed does not drop when a load is applied.    
"IDLE"/"RATED" switch     "RATED"     Moves engine from "IDLE" speed to "RATED" speed.    
Circuit breaker switch     "NAC" (1)     Enables closure of the generator circuit breaker.    
Lockout relay     "RESET"     Removes the disabling (lockout) voltage from the switchgear.    
"LOCAL"/"REMOTE" setpoint     "LOCAL"     Enables local start/stop from the "MAIN" screen of the touchscreen display.    
"START/LOAD" on the "MAIN" screen     "START/LOAD"     Starts the engine. Closes the generator circuit breaker. (2)    
"STOP/UNLOAD" on the "MAIN" screen     Not used     None    
"SYNCHRONIZING" switch     Not used     None    
Engine control switch     "AUTO"     Puts the switchgear in automatic mode.    
Alarm switch     Not used     None    
Manual load potentiometer     Not used     None    
VAR/Power factor adjust potentiometer     Not used     None    
"BASE LOAD START" (Remote)     No     None    
"BASE LOAD STOP" (Remote)     No     None    
"STANDBY START" (Remote)     No     None    
"STANDBY STOP" (Remote)     No     None    
( 1 ) Turn the handle of the circuit breaker switch to the fully clockwise position. Release the handle. The handle will return to the center position. The red target will be visible.
( 2 ) The generator circuit breaker will close automatically when all of the permissives have been met.

Momentarily touch the button for "START LOAD" (5). The genset will automatically start. The genset will obtain rated speed and voltage. After the voltage has built up, the generator circuit breaker will automatically close. The generator will send power to all of the loads that are connected to the bus.

Local Stop For Standby Operation

Place the controls in the following positions:

Table 2
CONTROL     POSITION/SELECTION     ACTION    
"DROOP-ISOCHRONOUS" switch     "ISOCHRONOUS"     Engine speed does not drop when a load is applied.    
"IDLE"/"RATED" switch     "RATED"     Moves engine from "IDLE" speed to "RATED" speed.    
Circuit breaker switch     "TRIP"     Opens the generator circuit breaker.    
Lockout relay     "RESET"     Removes the disabling (lockout) voltage from the switchgear.    
"LOCAL"/"REMOTE" setpoint     "LOCAL"     Enables local start/stop from the "MAIN" screen of the touchscreen display.    
"START/LOAD" on the "MAIN" screen     Not used     None    
"STOP/UNLOAD" on the "MAIN" screen     "STOP/UNLOAD"     Opens the generator circuit breaker. Places the engine in cooldown mode.    
"SYNCHRONIZING" switch     Not used     None    
Engine control switch     "AUTO"     Puts the switchgear in automatic mode.    
Alarm switch     Not used     None    
Manual load potentiometer     Not used     None    
VAR/Power factor adjust potentiometer     Not used     None    
"BASE LOAD START" (Remote)     No     None    
"BASE LOAD STOP" (Remote)     No     None    
"STANDBY START" (Remote)     No     None    
"STANDBY STOP" (Remote)     No     None    

Momentarily press the button for "STOP UNLOAD". The generator circuit breaker will open. The engine will run without a load for the cooldown period. The engine will shut down.

Remote Start For Standby Operation

Place the controls in the following positions:

Table 3
CONTROL     POSITION/SELECTION     ACTION    
"DROOP-ISOCHRONOUS" switch     "ISOCHRONOUS"     Engine speed does not drop when a load is applied.    
"IDLE"/"RATED" switch     "RATED"     Moves engine from "IDLE" speed to "RATED" speed.    
Circuit breaker switch     NAC (1)     Enables closure of the generator circuit breaker.    
Lockout relay     "RESET"     Removes the disabling (lockout) voltage from the switchgear.    
"LOCAL"/"REMOTE" setpoint     "REMOTE"     Disables local start/stop from the "MAIN" screen of the touchscreen display.    
"START/LOAD" on the "MAIN" screen     Not used     None    
"STOP/UNLOAD" on the "MAIN" screen     Not used     None    
"SYNCHRONIZING" switch     Not used     None    
Engine control switch     "AUTO"     Puts the switchgear in automatic mode.    
Alarm switch     Not used     None    
Manual load potentiometer     Not used     None    
VAR/Power factor adjust potentiometer     Not used     None    
"BASE LOAD START" (Remote)     No     None    
"BASE LOAD STOP" (Remote)     No     None    
"STANDBY START" (Remote)     A contact is applied.     Starts the engine. Closes the generator circuit breaker. (2)    
"STANDBY STOP" (Remote)     No     None    
( 1 ) Turn the handle of the circuit breaker switch to the fully clockwise position. Release the handle. The handle will return to the center position. The red target will be visible.
( 2 ) The breaker will close automatically when all permissives have been met.

Wire the remote start contacts to the "STANDBY START" terminal connections. When the contacts for remote starting close for at least one second, the genset will start. The genset reaches the rated speed and voltage. The generator circuit breaker will close. Power is supplied to all connected loads.

Remote Stop For Standby Operation

Place the controls in the following positions:

Table 4
CONTROL     POSITION/SELECTION     ACTION    
"DROOP-ISOCHRONOUS" switch     "ISOCHRONOUS"     Engine speed does not drop when a load is applied.    
"IDLE"/"RATED" switch     "RATED"     Moves engine from "IDLE" speed to "RATED" speed.    
Circuit breaker switch     "TRIP"     Opens the generator circuit breaker.    
Lockout relay     "RESET"     Removes the disabling (lockout) voltage from the switchgear.    
"LOCAL"/"REMOTE" setpoint     "REMOTE"     Disables local start/stop from the "MAIN" screen of the touchscreen display.    
"START/LOAD" on the "MAIN" screen     Not used     None    
"STOP/UNLOAD" on the "MAIN" screen     Not used     Opens the generator circuit breaker and places the engine in cool down.    
"SYNCHRONIZING" switch     Not used     None    
Engine control switch     "AUTO"     Puts the switchgear in automatic mode.    
Alarm switch     Not used     None    
Manual load potentiometer     Not used     None    
VAR/Power factor adjust potentiometer     Not used     None    
"BASE LOAD START" (Remote)     No     None    
"BASE LOAD STOP" (Remote)     No     None    
"STANDBY START" (Remote)     No     None    
"STANDBY STOP" (Remote)     A contact is applied.     The generator circuit breaker is opened. The engine is placed in cooldown mode.    

Wire the remote stop contacts to the "STANDBY STOP" terminal connections. When the remote contacts close for at least one second, the generator circuit breaker will open. The engine will run without a load for the cooldown period. The engine will shut down.

Caterpillar Information System:

Power Module Switchgear (Low Voltage and Medium Voltage) General Operation
G3516B Engines MID 036 - CID 1447 - FMI 12 Fuel Metering Sensor Module malfunction
G3516B Engines MID 036 - CID 1446 - FMI 13 Fuel Metering Module calibration required
Power Module Switchgear (Low Voltage and Medium Voltage) Metering Screen
Power Module Switchgear (Low Voltage and Medium Voltage) Alarm Screen
G3516B Engines MID 036 - CID 1446 - FMI 12 Fuel Metering Module malfunction
C15 and C18 Engines for Caterpillar Built Machines CID 0100 FMI 03 Engine Oil Pressure open/short to +batt
3126 Truck Engine Belt Tensioner - If Equipped
3126 Truck Engine (Military) Sensors and Electrical Components
Power Module Switchgear (Low Voltage and Medium Voltage) Help Screen
Power Module Switchgear (Low Voltage and Medium Voltage) Annunciate Screen
Power Module Switchgear (Low Voltage and Medium Voltage) Programmable Logic Controller
Power Module Switchgear (Low Voltage and Medium Voltage) Base Load Operation
120H, 12H, 135H, 140H, 143H, 160H and 163H Motor Graders Electrical Connector - Inspect
3406E, C-10, C-12, C-15, C-16 and C-18 On-highway Engines Air Inlet Shutoff Circuit - Test
Power Module Switchgear (Low Voltage and Medium Voltage) Manual Parallel Operation
2001/11/01 Setting the Desired Rated Speed or Emissions Strategy for Generator Sets {1901}
3126 Truck Engine (Military) Diagnostic Flash Code Retrieval
3054 and 3056 Engines 520 Generator Set Control Panel Symbols
3054 and 3056 Marine Generator Set Engines Valve Depth - Inspect
3054 and 3056 Engines 520 Generator Set Control Panel Specification
Power Module Switchgear (Low Voltage and Medium Voltage) Generator Circuit Breaker
3054 and 3056 Engines 520 Generator Set Control Panel Initial Startup Procedure