Screen For Annunciation For Low Voltage Switchgear
Illustration 1 | g00846187 |
Screen for annunciation for the power module (480 Volt gas) |
Illustration 2 | g00856593 |
Annunciate Screen for the Power Module (480 Volt Diesel) |
The screen for annunciation displays an illuminated box for each alarm or shutdown. The icons will illuminate and the icons will flash when an event occurs.
Note: The icons that are configured at the factory for a cool down event will appear yellow. The icons that are configured at the factory for a shut down event will appear red.
The operator can rotate the alarm control switch (ACS) to the "ACK" position in order to acknowledge any icon that is flashing. After the alarm is acknowledged, the flashing will stop. The icon will remain illuminated until the alarm is no longer active. If an alarm that is not acknowledged is no longer active, the icon will remain illuminated until the alarm is acknowledged.
The first two columns group the events of the genset. The two columns in the center group the trip events for the generator multifunction relay (GMR). The last two columns group the trip events for the utility multifunction relay (UMR).
Screen For Annunciation For Medium Voltage Switchgear
Illustration 3 | g00854908 |
Screen for annunciation for the power module (gas powered medium voltage generator) |
Illustration 4 | g00856604 |
Screen for the power module annunciation (diesel powered medium voltage generator) |