Illustration 1 | g00845493 |
Block Diagram of the Control System |
Illustration 1 is an overview of the design of the control system. The PLC has expansion modules for input and the PLC has expansion modules for output. The PLC has two serial ports. Channel 0 is used for communication with the protective relays through a converter. A modbus master driver is used in the PLC application program. Channel 1 is used for communication with the door mounted touchscreen display.
The PLC has a battery that will need to be replaced occasionally. See "Allen-Bradley A3811L5 MicroLogix 1500 Programmable Controllers (Bulletin 1764 Controllers) User Manual, Publication Number 1764-UM001A-US-P".
The PLC may experience a loss of memory. The PLC may experience a fatal data memory error. A copy of the program for the PLC is stored in an EEPROM. The program for the PLC may be replaced by the program that is stored in the EEPROM. See "Allen-Bradley A3811L5 MicroLogix 1500 Programmable Controllers (Bulletin 1764 Controllers) User Manual, Publication Number 1764-UM001A-US-P".