Winding Data for 9Y-0390 Generator through 9Y-0533 Generator
9Y-0390 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 414.0 mm (16.3 inch)     |
414.0 mm (16.3 inch)     |
|||||
Slots     | 60     | -     | |||||
Coil Throw     | 1 - 12     | -     | |||||
Turns/Coil     | 1.4 (1-2-1-2-1)     | -     | |||||
Turns/Pole     | -     | 180     | |||||
No. & Wire Size     | 27 - #14     | #6.5 RD     | |||||
Mean Length Turn     | 1678.9 mm (66.1 inch)     |
-     | |||||
Copper Weight     | 71.8 kg (158.3 lb)     |
99.8 kg (220.0 lb)     |
|||||
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 24 - #000     | -     | |||||
Terminal bolt size     | 3/8 in     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00218 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.44 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | 240 Hz     | ||||
Exciter Poles     | 6     | 16     | |||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 127.0 mm (5.0 inch)     |
127.0 mm (5.0 inch)     |
25.4 mm (1.0 inch)     |
||||
Coils/Group     | 1     | 1     | 1     | ||||
Slots (Coils)     | 6     | 36     | 48     | ||||
Turns (Coils)     | 140     | 8     | 12     | ||||
No. & Size Wire     | 1 - #15.5     | 2 - #16     | 4 - #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1 - 4     | ||||
Mean Length Turn (Calc.)     | 464.8 mm (18.3 inch)     |
464.8 mm (18.3 inch)     |
208.3 mm (8.2 inch)     |
||||
Copper Weight     | 5.2 kg (11.5 lb)     |
2.9 kg (6.4 lb)     |
1.8 kg (4.0 lb)     |
||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | 1 Series     | ||||
Line Leads     | 1 - #14     | 3 - #10     | 3 - #14     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 47 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
9Y-0391 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 431.8 mm (17.0 inch)     |
431.8 mm (17.0 inch)     |
|||||
Slots     | 60     | -     | |||||
Coil Throw     | 1 - 12     | -     | |||||
Turns/Coil     | 1.4 (1-2-1-2-1)     | -     | |||||
Turns/Pole     | -     | 180     | |||||
No. & Wire Size     | 29 - #14     | #6.5 RD     | |||||
Mean Length Turn     | 1714.5 mm (67.5 inch)     |
-     | |||||
Copper Weight     | 78.9 kg (174.0 lb)     |
102.5 kg (225.9 lb)     |
|||||
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 48 - #2     | -     | |||||
Terminal bolt size     | 3/8 in     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00215 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.545 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | 240 Hz     | ||||
Exciter Poles     | 6     | 16     | |||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 127.0 mm (5.0 inch)     |
127.0 mm (5.0 inch)     |
25.4 mm (1.0 inch)     |
||||
Coils/Group     | 1     | 1     | 1     | ||||
Slots (Coils)     | 6     | 36     | 48     | ||||
Turns (Coils)     | 140     | 8     | 12     | ||||
No. & Size Wire     | 1 - #15.5     | 2 - #16     | 4 - #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1 - 4     | ||||
Mean Length Turn (Calc.)     | 464.8 mm (18.3 inch)     |
464.8 mm (18.3 inch)     |
208.3 mm (8.2 inch)     |
||||
Copper Weight     | 5.2 kg (11.5 lb)     |
2.9 kg (6.4 lb)     |
1.8 kg (4.0 lb)     |
||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | 1 Series     | ||||
Line Leads     | 1 - #14     | 3 - #10     | 3 - #14     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 47 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
9Y-0392 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 457.2 mm (18.0 inch)     |
457.2 mm (18.0 inch)     |
|||||
Slots     | 60     | -     | |||||
Coil Throw     | 1 - 12     | -     | |||||
Turns/Coil     | 1.4 (1-2-1-2-1)     | -     | |||||
Turns/Pole     | -     | 180     | |||||
No. & Wire Size     | 34 - #14     | #6.5 RD     | |||||
Mean Length Turn     | 1765.3 mm (69.5 inch)     |
-     | |||||
Copper Weight     | 95.3 kg (210.0 lb)     |
106.6 kg (235.0 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 12 - #0000     | -     | |||||
Terminal bolt size     | 3/8 in     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00628 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.53 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | 240 Hz     | ||||
Exciter Poles     | 6     | 16     | |||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 127.0 mm (5.0 inch)     |
127.0 mm (5.0 inch)     |
25.4 mm (1.0 inch)     |
||||
Coils/Group     | 1     | 1     | 1     | ||||
Slots (Coils)     | 6     | 36     | 48     | ||||
Turns (Coils)     | 140     | 8     | 12     | ||||
No. & Size Wire     | 1 - #15.5     | 2 - #16     | 4 - #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1 - 4     | ||||
Mean Length Turn (Calc.)     | 464.8 mm (18.3 inch)     |
464.8 mm (18.3 inch)     |
208.3 mm (8.2 inch)     |
||||
Copper Weight     | 5.2 kg (11.5 lb)     |
2.9 kg (6.4 lb)     |
1.8 kg (4.0 lb)     |
||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | 1 Series     | ||||
Line Leads     | 1 - #14     | 3 - #10     | 3 - #14     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 55 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
9Y-0393 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 558.8 mm (22.0 inch)     |
566.4 mm (22.3 inch)     |
|||||
Slots     | 60     | -     | |||||
Coil Throw     | 1 - 14     | -     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 180     | |||||
No. & Wire Size     | 35 - #14     | #6.5 RD     | |||||
Mean Length Turn     | 2095.5 mm (82.5 inch)     |
-     | |||||
Copper Weight     | 80.3 kg (177.0 lb)     |
123.4 kg (272.0 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 24 - #1     | -     | |||||
Terminal bolt size     | 3/8 in     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00574 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.732 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | 240 Hz     | ||||
Exciter Poles     | 6     | 16     | |||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 127.0 mm (5.0 inch)     |
127.0 mm (5.0 inch)     |
25.4 mm (1.0 inch)     |
||||
Coils/Group     | 1     | 1     | 1     | ||||
Slots (Coils)     | 6     | 36     | 48     | ||||
Turns (Coils)     | 140     | 8     | 12     | ||||
No. & Size Wire     | 1 - #15.5     | 2 - #16     | 4 - #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1 - 4     | ||||
Mean Length Turn (Calc.)     | 464.8 mm (18.3 inch)     |
464.8 mm (18.3 inch)     |
208.3 mm (8.2 inch)     |
||||
Copper Weight     | 5.2 kg (11.5 lb)     |
2.9 kg (6.4 lb)     |
1.8 kg (4.0 lb)     |
||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | 1 Series     | ||||
Line Leads     | 1 - #14     | 3 - #10     | 3 - #14     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 41 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram B |
9Y-0394 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 355.6 mm (14.0 inch)     |
368.3 mm (14.5 inch)     |
|||||
Slots     | 66     | -     | |||||
Coil Throw     | 1 - 12     | -     | |||||
Turns/Coil     | 2.4     | -     | |||||
Turns/Pole     | -     | 216     | |||||
No. & Wire Size     | 18 - #13     | #6 SQ     | |||||
Mean Length Turn     | 1676.4 mm (66.0 inch)     |
-     | |||||
Copper Weight     | 103.9 kg (229.0 lb)     |
164.2 kg (362.0 lb)     |
|||||
Inside Connection (1)     | 4 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 24 - #3/0     | -     | |||||
Terminal bolt size     | 3/8 in     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00385 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.214 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 127.0 mm (5.0 inch)     |
127.0 mm (5.0 inch)     |
-     | ||||
Coils/Group     | 1     | 1     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 140     | 8     | -     | ||||
No. & Size Wire     | 1 - #15.5     | 2 - #16     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 464.8 mm (18.3 inch)     |
464.8 mm (18.3 inch)     |
-     | ||||
Copper Weight     | 5.2 kg (11.5 lb)     |
2.9 kg (6.4 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 19 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram B |
9Y-0396 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 406.4 mm (16.0 inch)     |
419.1 mm (16.5 inch)     |
|||||
Slots     | 60     | -     | |||||
Coil Throw     | 1 - 13     | -     | |||||
Turns/Coil     | 2     | -     | |||||
Turns/Pole     | -     | 216     | |||||
No. & Wire Size     | 19 - #13     | #6 SQ     | |||||
Mean Length Turn     | 1821.2 mm (71.7 inch)     |
-     | |||||
Copper Weight     | 98.7 kg (217.6 lb)     |
177.3 kg (390.9 lb)     |
|||||
Inside Connection (1)     | 4 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 24 - #4/0     | -     | |||||
Terminal bolt size     | 3/8 in     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00329 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.375 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 127.0 mm (5.0 inch)     |
127.0 mm (5.0 inch)     |
-     | ||||
Coils/Group     | 1     | 1     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 140     | 8     | -     | ||||
No. & Size Wire     | 1 - #15.5     | 2 - #16     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 464.8 mm (18.3 inch)     |
464.8 mm (18.3 inch)     |
-     | ||||
Copper Weight     | 5.2 kg (11.5 lb)     |
2.7 kg (6.0 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 19 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram B |
9Y-0398 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 508.0 mm (20.0 inch)     |
520.7 mm (20.5 inch)     |
|||||
Slots     | 72     | -     | |||||
Coil Throw     | 1 - 14     | -     | |||||
Turns/Coil     | 1.5     | -     | |||||
Turns/Pole     | -     | 216     | |||||
No. & Wire Size     | 33 - #13     | #6 SQ     | |||||
Mean Length Turn     | 2176.8 mm (85.7 inch)     |
-     | |||||
Copper Weight     | 184.4 kg (406.5 lb)     |
203.7 kg (449.0 lb)     |
|||||
Inside Connection (1)     | 4 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 48 - #1/0     | -     | |||||
Terminal bolt size     | 3/8 in     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00203 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.503 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 127.0 mm (5.0 inch)     |
127.0 mm (5.0 inch)     |
-     | ||||
Coils/Group     | 1     | 1     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 140     | 8     | -     | ||||
No. & Size Wire     | 1 - #15.5     | 2 - #16     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 464.8 mm (18.3 inch)     |
464.8 mm (18.3 inch)     |
-     | ||||
Copper Weight     | 5.2 kg (11.5 lb)     |
2.7 kg (6.0 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 29 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram B |
9Y-0400 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 566.4 mm (22.3 inch)     |
566.4 mm (22.3 inch)     |
|||||
Slots     | 60     | -     | |||||
Coil Throw     | 1 - 13     | -     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 180     | |||||
No. & Wire Size     | 40 - #14     | #6.5 RD     | |||||
Mean Length Turn     | 1983.7 mm (78.1 inch)     |
-     | |||||
Copper Weight     | 93.9 kg (207.0 lb)     |
123.4 kg (272.0 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 24 - #0     | -     | |||||
Terminal bolt size     | 3/8 in     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00485 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.732 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 127.0 mm (5.0 inch)     |
127.0 mm (5.0 inch)     |
-     | ||||
Coils/Group     | 1     | 1     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 140     | 8     | -     | ||||
No. & Size Wire     | 1 - #15.5     | 2 - #16     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 464.8 mm (18.3 inch)     |
464.8 mm (18.3 inch)     |
-     | ||||
Copper Weight     | 5.2 kg (11.5 lb)     |
2.9 kg (6.4 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 1 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 41 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram B |
9Y-0452 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 406.4 mm (16.0 inch)     |
419.1 mm (16.5 inch)     |
|||||
Slots     | 72     | -     | |||||
Coil Throw     | 1 - 13     | -     | |||||
Turns/Coil     | 5     | -     | |||||
Turns/Pole     | -     | 216     | |||||
No. & Wire Size     | 2 - 3.3 mm (0.129 inch)× 3.4 mm (0.133 inch)     |
#6 SQ     | |||||
Mean Length Turn     | 1879.6 mm (74.0 inch)     |
-     | |||||
Copper Weight     | 128.4 kg (283.0 lb)     |
177.3 kg (390.9 lb)     |
|||||
Inside Connection (1)     | 1 Series Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 6 - #4     | -     | |||||
Terminal bolt size     | 3/8 in     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.3840 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.375 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 127.0 mm (5.0 inch)     |
127.0 mm (5.0 inch)     |
-     | ||||
Coils/Group     | 1     | 1     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 140     | 8     | -     | ||||
No. & Size Wire     | 1 - #15.5     | 2 - #16     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 464.8 mm (18.3 inch)     |
464.8 mm (18.3 inch)     |
-     | ||||
Copper Weight     | 5.2 kg (11.5 lb)     |
2.7 kg (6.0 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 12 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram B |
9Y-0454 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 508.0 mm (20.0 inch)     |
520.7 mm (20.5 inch)     |
|||||
Slots     | 60     | -     | |||||
Coil Throw     | 1 - 11     | -     | |||||
Turns/Coil     | 5     | -     | |||||
Turns/Pole     | -     | 216     | |||||
No. & Wire Size     | 2 - 3.7 mm (0.145 inch)× 4.5 mm (0.177 inch)     |
#6 SQ     | |||||
Mean Length Turn     | 2014.2 mm (79.3 inch)     |
-     | |||||
Copper Weight     | 177.4 kg (391.0 lb)     |
203.7 kg (449.0 lb)     |
|||||
Inside Connection (1)     | 1 Series Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 6 - #2     | -     | |||||
Terminal bolt size     | 3/8 in     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.2270 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.503 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 127.0 mm (5.0 inch)     |
127.0 mm (5.0 inch)     |
-     | ||||
Coils/Group     | 1     | 1     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 140     | 8     | -     | ||||
No. & Size Wire     | 1 - #15.5     | 2 - #16     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 464.8 mm (18.3 inch)     |
464.8 mm (18.3 inch)     |
-     | ||||
Copper Weight     | 5.2 kg (11.5 lb)     |
2.7 kg (6.0 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 12 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram B |
9Y-0456 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 431.8 mm (17.0 inch)     |
439.4 mm (17.3 inch)     |
|||||
Slots     | 60     | -     | |||||
Coil Throw     | 1 - 11     | -     | |||||
Turns/Coil     | 5     | -     | |||||
Turns/Pole     | -     | 225.5     | |||||
No. & Wire Size     | 2 - 3.9 mm (0.155 inch)× 5.5 mm (0.218 inch)     |
3.7 mm (0.145 inch)× 7.7 mm (0.302 inch) HF     |
|||||
Mean Length Turn     | 1996.4 mm (78.6 inch)     |
-     | |||||
Copper Weight     | 231.0 kg (509.3 lb)     |
327.6 kg (722.3 lb)     |
|||||
Inside Connection (1)     | 1 Series Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 6 - #1     | -     | |||||
Terminal bolt size     | 3/8 in     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.1739 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.849 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 120 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 8     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 63.5 mm (2.5 inch)     |
63.5 mm (2.5 inch)     |
-     | ||||
Coils/Group     | 1     | 2     | -     | ||||
Slots (Coils)     | 8     | 48     | -     | ||||
Turns (Coils)     | 160     | 7     | -     | ||||
No. & Size Wire     | 1 - #14     | 3 - #15     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 330.2 mm (13.0 inch)     |
386.1 mm (15.2 inch)     |
-     | ||||
Copper Weight     | 11.1 kg (24.5 lb)     |
6.2 kg (13.7 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 12 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram I |
9Y-0459 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 520.7 mm (20.5 inch)     |
533.4 mm (21.0 inch)     |
|||||
Slots     | 60     | -     | |||||
Coil Throw     | 1 - 11     | -     | |||||
Turns/Coil     | 4     | -     | |||||
Turns/Pole     | -     | 225.5     | |||||
No. & Wire Size     | 2 - 5.1 mm (0.201 inch)× 5.6 mm (0.220 inch)     |
3.7 mm (0.145 inch)× 7.7 mm (0.302 inch) HF     |
|||||
Mean Length Turn     | 2176.8 mm (85.7 inch)     |
-     | |||||
Copper Weight     | 263.4 kg (580.6 lb)     |
374.7 kg (826.0 lb)     |
|||||
Inside Connection (1)     | 1 Series Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 6 - #1/0     | -     | |||||
Terminal bolt size     | 3/8 in     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.119 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.970 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 120 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 8     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 63.5 mm (2.5 inch)     |
63.5 mm (2.5 inch)     |
-     | ||||
Coils/Group     | 1     | 2     | -     | ||||
Slots (Coils)     | 8     | 48     | -     | ||||
Turns (Coils)     | 160     | 7     | -     | ||||
No. & Size Wire     | 1 - #14     | 3 - #15     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 330.2 mm (13.0 inch)     |
386.1 mm (15.2 inch)     |
-     | ||||
Copper Weight     | 11.1 kg (24.5 lb)     |
6.2 kg (13.7 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 12 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram I |
9Y-0461 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 546.1 mm (21.5 inch)     |
558.8 mm (22.0 inch)     |
|||||
Slots     | 60     | -     | |||||
Coil Throw     | 1 - 11     | -     | |||||
Turns/Coil     | 4     | -     | |||||
Turns/Pole     | -     | 225.5     | |||||
No. & Wire Size     | 4 - 2.7 mm (0.105 inch)× 4.9 mm (0.194 inch)     |
3.7 mm (0.145 inch)× 7.7 mm (0.302 inch) HF     |
|||||
Mean Length Turn     | 2237.7 mm (88.1 inch)     |
-     | |||||
Copper Weight     | 248.3 kg (547.4 lb)     |
386.0 kg (851.0 lb)     |
|||||
Inside Connection (1)     | 1 Series Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 6 - #2/0     | -     | |||||
Terminal bolt size     | 3/8 in     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.132 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.0 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 120 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 8     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 63.5 mm (2.5 inch)     |
63.5 mm (2.5 inch)     |
-     | ||||
Coils/Group     | 1     | 2     | -     | ||||
Slots (Coils)     | 8     | 48     | -     | ||||
Turns (Coils)     | 160     | 7     | -     | ||||
No. & Size Wire     | 1 - #14     | 3 - #15     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 330.2 mm (13.0 inch)     |
386.1 mm (15.2 inch)     |
-     | ||||
Copper Weight     | 11.1 kg (24.5 lb)     |
6.2 kg (13.7 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 12 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram I |
9Y-0463 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 622.3 mm (24.5 inch)     |
635.0 mm (25.0 inch)     |
|||||
Slots     | 60     | -     | |||||
Coil Throw     | 1 - 11     | -     | |||||
Turns/Coil     | 7     | -     | |||||
Turns/Pole     | -     | 225.5     | |||||
No. & Wire Size     | 2 - 3.0 mm (0.117 inch)× 5.5 mm (0.218 inch)     |
3.7 mm (0.145 inch)× 7.7 mm (0.302 inch) HF     |
|||||
Mean Length Turn     | 2407.9 mm (94.8 inch)     |
-     | |||||
Copper Weight     | 291.7 kg (643.0 lb)     |
416.8 kg (919.0 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 6 - #2/0     | -     | |||||
Terminal bolt size     | 3/8 in     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.09538 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.08 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 120 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 8     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 63.5 mm (2.5 inch)     |
63.5 mm (2.5 inch)     |
-     | ||||
Coils/Group     | 1     | 2     | -     | ||||
Slots (Coils)     | 8     | 48     | -     | ||||
Turns (Coils)     | 160     | 7     | -     | ||||
No. & Size Wire     | 1 - #14     | 3 - #15     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 330.2 mm (13.0 inch)     |
386.1 mm (15.2 inch)     |
-     | ||||
Copper Weight     | 11.1 kg (24.5 lb)     |
6.2 kg (13.7 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 44 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram I |
9Y-0513 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 330.2 mm (13.0 inch)     |
342.9 mm (13.5 inch)     |
|||||
Slots     | 60     | -     | |||||
Coil Throw     | 1 - 12     | -     | |||||
Turns/Coil     | 1.6     | -     | |||||
Turns/Pole     | -     | 216     | |||||
No. & Wire Size     | 29 - #14     | #6 SQ     | |||||
Mean Length Turn     | 1630.7 mm (64.2 inch)     |
-     | |||||
Copper Weight     | 85.7 kg (189.0 lb)     |
157.8 kg (348.0 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 24 - #1/0     | -     | |||||
Terminal bolt size     | 3/8 in     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00857 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.166 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 127.0 mm (5.0 inch)     |
127.0 mm (5.0 inch)     |
-     | ||||
Coils/Group     | 1     | 1     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 140     | 8     | -     | ||||
No. & Size Wire     | 1 - #15.5     | 2 - #16     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 464.8 mm (18.3 inch)     |
464.8 mm (18.3 inch)     |
-     | ||||
Copper Weight     | 5.2 kg (11.5 lb)     |
2.7 kg (6.0 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 2 - #16     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 41 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram B |
9Y-0516 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 355.6 mm (14.0 inch)     |
368.3 mm (14.5 inch)     |
|||||
Slots     | 60     | -     | |||||
Coil Throw     | 1 - 13     | -     | |||||
Turns/Coil     | 3     | -     | |||||
Turns/Pole     | -     | 216     | |||||
No. & Wire Size     | 15 - #13     | #6 SQ     | |||||
Mean Length Turn     | 1752.6 mm (69.0 inch)     |
-     | |||||
Copper Weight     | 112.9 kg (249.0 lb)     |
164.2 kg (362.0 lb)     |
|||||
Inside Connection (1)     | 4 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 24 - #1/0     | -     | |||||
Terminal bolt size     | 3/8 in     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00647 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.214 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 127.0 mm (5.0 inch)     |
127.0 mm (5.0 inch)     |
-     | ||||
Coils/Group     | 1     | 1     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 140     | 8     | -     | ||||
No. & Size Wire     | 1 - #15.5     | 2 - #16     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 464.8 mm (18.3 inch)     |
464.8 mm (18.3 inch)     |
-     | ||||
Copper Weight     | 5.2 kg (11.5 lb)     |
2.7 kg (6.0 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 2 - #16     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 60 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram B |
9Y-0519 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 381.0 mm (15.0 inch)     |
393.7 mm (15.5 inch)     |
|||||
Slots     | 84     | -     | |||||
Coil Throw     | 1 - 16     | -     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 216     | |||||
No. & Wire Size     | 31 - #13     | #6 SQ     | |||||
Mean Length Turn     | 1828.8 mm (72.0 inch)     |
-     | |||||
Copper Weight     | 113.4 kg (250.0 lb)     |
170.8 kg (376.5 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 24 - #2/0     | -     | |||||
Terminal bolt size     | 3/8 in     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00627 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.27 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 127.0 mm (5.0 inch)     |
127.0 mm (5.0 inch)     |
-     | ||||
Coils/Group     | 1     | 1     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 140     | 8     | -     | ||||
No. & Size Wire     | 1 - #15.5     | 2 - #16     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 464.8 mm (18.3 inch)     |
464.8 mm (18.3 inch)     |
-     | ||||
Copper Weight     | 5.2 kg (11.5 lb)     |
2.7 kg (6.0 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 2 - #16     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 41 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram B |
9Y-0521 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 431.8 mm (17.0 inch)     |
444.5 mm (17.5 inch)     |
|||||
Slots     | 72     | -     | |||||
Coil Throw     | 1 - 15     | -     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 216     | |||||
No. & Wire Size     | 39 - #13     | #6 SQ     | |||||
Mean Length Turn     | 1963.4 mm (77.3 inch)     |
-     | |||||
Copper Weight     | 144.2 kg (318.0 lb)     |
183.7 kg (405.0 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 24 - #3/0     | -     | |||||
Terminal bolt size     | 3/8 in     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00461 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.380 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 127.0 mm (5.0 inch)     |
127.0 mm (5.0 inch)     |
-     | ||||
Coils/Group     | 1     | 1     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 140     | 8     | -     | ||||
No. & Size Wire     | 1 - #15.5     | 2 - #16     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 464.8 mm (18.3 inch)     |
464.8 mm (18.3 inch)     |
-     | ||||
Copper Weight     | 5.2 kg (11.5 lb)     |
2.7 kg (6.0 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 2 - #16     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 41 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram B |
9Y-0523 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 508.0 mm (20.0 inch)     |
520.7 mm (20.5 inch)     |
|||||
Slots     | 60     | -     | |||||
Coil Throw     | 1 - 13     | -     | |||||
Turns/Coil     | 2     | -     | |||||
Turns/Pole     | -     | 216     | |||||
No. & Wire Size     | 22 - #13     | #6 SQ     | |||||
Mean Length Turn     | 2082.8 mm (82.0 inch)     |
-     | |||||
Copper Weight     | 130.6 kg (288.0 lb)     |
203.7 kg (449.0 lb)     |
|||||
Inside Connection (1)     | 4 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 24 - #4/0     | -     | |||||
Terminal bolt size     | 3/8 in     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00360 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.503 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 127.0 mm (5.0 inch)     |
127.0 mm (5.0 inch)     |
-     | ||||
Coils/Group     | 1     | 1     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 140     | 8     | -     | ||||
No. & Size Wire     | 1 - #15.5     | 2 - #16     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 464.8 mm (18.3 inch)     |
464.8 mm (18.3 inch)     |
-     | ||||
Copper Weight     | 5.2 kg (11.5 lb)     |
2.7 kg (6.0 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 2 - #16     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 60 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram B |
9Y-0525 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 558.8 mm (22.0 inch)     |
571.5 mm (22.5 inch)     |
|||||
Slots     | 60     | -     | |||||
Coil Throw     | 1 - 11     | -     | |||||
Turns/Coil     | 2     | -     | |||||
Turns/Pole     | -     | 216     | |||||
No. & Wire Size     | 26 - #13     | #6 SQ     | |||||
Mean Length Turn     | 2049.8 mm (80.7 inch)     |
-     | |||||
Copper Weight     | 152.0 kg (335.0 lb)     |
202.8 kg (447.0 lb)     |
|||||
Inside Connection (1)     | 4 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 24 - #4/0     | -     | |||||
Terminal bolt size     | 3/8 in     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00306 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.600 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 152.4 mm (6.0 inch)     |
152.4 mm (6.0 inch)     |
-     | ||||
Coils/Group     | 1     | 2     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 140     | 9     | -     | ||||
No. & Size Wire     | 1 - #15.5     | 1 - #16     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 515.6 mm (20.3 inch)     |
431.8 mm (17.0 inch)     |
-     | ||||
Copper Weight     | 6.0 kg (13.3 lb)     |
3.2 kg (7.0 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 60 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
9Y-0527 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 419.1 mm (16.5 inch)     |
439.4 mm (17.3 inch)     |
|||||
Slots     | 72     | -     | |||||
Coil Throw     | 1 - 13     | -     | |||||
Turns/Coil     | 2     | -     | |||||
Turns/Pole     | -     | 225.5     | |||||
No. & Wire Size     | 28 - #13     | 3.7 mm (0.145 inch)× 7.7 mm (0.302 inch) HF     |
|||||
Mean Length Turn     | 1943.1 mm (76.5 inch)     |
-     | |||||
Copper Weight     | 186.4 kg (411.0 lb)     |
327.6 kg (722.3 lb)     |
|||||
Inside Connection (1)     | 4 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 48 - #1     | -     | |||||
Terminal bolt size     | 3/8 in     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00316 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.849 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 120 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 8     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 63.5 mm (2.5 inch)     |
63.5 mm (2.5 inch)     |
-     | ||||
Coils/Group     | 1     | 2     | -     | ||||
Slots (Coils)     | 8     | 48     | -     | ||||
Turns (Coils)     | 160     | 7     | -     | ||||
No. & Size Wire     | 1 - #14     | 3 - #15     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 330.2 mm (13.0 inch)     |
386.1 mm (15.2 inch)     |
-     | ||||
Copper Weight     | 11.1 kg (24.5 lb)     |
6.2 kg (13.7 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 43 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram I |
9Y-0529 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 520.7 mm (20.5 inch)     |
533.4 mm (21.0 inch)     |
|||||
Slots     | 60     | -     | |||||
Coil Throw     | 1 - 11     | -     | |||||
Turns/Coil     | 2     | -     | |||||
Turns/Pole     | -     | 225.5     | |||||
No. & Wire Size     | 44 - #13     | 3.7 mm (0.145 inch)× 7.7 mm (0.302 inch) HF     |
|||||
Mean Length Turn     | 2176.8 mm (85.7 inch)     |
-     | |||||
Copper Weight     | 273.1 kg (602.0 lb)     |
374.7 kg (826.0 lb)     |
|||||
Inside Connection (1)     | 4 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 48 - #1/0     | -     | |||||
Terminal bolt size     | 3/8 in     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00192 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.970 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 120 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 8     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 63.5 mm (2.5 inch)     |
63.5 mm (2.5 inch)     |
-     | ||||
Coils/Group     | 1     | 2     | -     | ||||
Slots (Coils)     | 8     | 48     | -     | ||||
Turns (Coils)     | 160     | 7     | -     | ||||
No. & Size Wire     | 1 - #14     | 3 - #15     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 330.2 mm (13.0 inch)     |
386.1 mm (15.2 inch)     |
-     | ||||
Copper Weight     | 11.1 kg (24.5 lb)     |
6.2 kg (13.7 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 43 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram I |
9Y-0531 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 571.5 mm (22.5 inch)     |
584.2 mm (23.0 inch)     |
|||||
Slots     | 60     | -     | |||||
Coil Throw     | 1 - 13     | -     | |||||
Turns/Coil     | 1.6     | -     | |||||
Turns/Pole     | -     | 225.5     | |||||
No. & Wire Size     | 42 - #13     | 3.7 mm (0.145 inch)× 7.7 mm (0.302 inch) HF     |
|||||
Mean Length Turn     | 2440.9 mm (96.1 inch)     |
-     | |||||
Copper Weight     | 234.1 kg (516.0 lb)     |
393.7 kg (868.0 lb)     |
|||||
Inside Connection (1)     | 4 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 48 - #2/0     | -     | |||||
Terminal bolt size     | 3/8 in     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00188 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.02 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 120 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 8     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 63.5 mm (2.5 inch)     |
63.5 mm (2.5 inch)     |
-     | ||||
Coils/Group     | 1     | 2     | -     | ||||
Slots (Coils)     | 8     | 48     | -     | ||||
Turns (Coils)     | 160     | 7     | -     | ||||
No. & Size Wire     | 1 - #14     | 3 - #15     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 330.2 mm (13.0 inch)     |
386.1 mm (15.2 inch)     |
-     | ||||
Copper Weight     | 11.1 kg (24.5 lb)     |
6.2 kg (13.7 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 43 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram I |
9Y-0533 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 635.0 mm (25.0 inch)     |
647.7 mm (25.5 inch)     |
|||||
Slots     | 84     | -     | |||||
Coil Throw     | 1 - 17     | -     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 225.5     | |||||
No. & Wire Size     | 60 - #14     | 3.7 mm (0.145 inch)× 7.7 mm (0.302 inch) HF     |
|||||
Mean Length Turn     | 2669.5 mm (105.1 inch)     |
-     | |||||
Copper Weight     | 253.6 kg (559.0 lb)     |
422.3 kg (931.0 lb)     |
|||||
Inside Connection (1)     | 4 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 48 - #3/0     | -     | |||||
Terminal bolt size     | 3/8 in     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00135 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.095 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 120 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 8     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 63.5 mm (2.5 inch)     |
63.5 mm (2.5 inch)     |
-     | ||||
Coils/Group     | 1     | 2     | -     | ||||
Slots (Coils)     | 8     | 48     | -     | ||||
Turns (Coils)     | 160     | 7     | -     | ||||
No. & Size Wire     | 1 - #14     | 3 - #15     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 330.2 mm (13.0 inch)     |
386.1 mm (15.2 inch)     |
-     | ||||
Copper Weight     | 11.1 kg (24.5 lb)     |
6.2 kg (13.7 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 43 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram I |
Caterpillar Information System:
3500 Generator Set Engines Coolant Temperature Switch
JF Series Starting Motor Service Tools
3500 Engines For Caterpillar Built Power Modules Engine Speed Sensor
PM3516 Power Modules Maintenance Recommendations
3500 Engines For Caterpillar Built Power Modules Starting Motor
3126B and 3126E On-highway Engines Engine Temperature Sensor Open or Short Circuit - Test
3500 Generator Set Engines Magnetic Switch
JF Series Starting Motor Armature End Play - Adjust
3500 Engines For Caterpillar Built Power Modules Alternator
3500 Generator Set Engines Electrical System Operation
3126B and 3126E On-highway Engines Engine Pressure Sensor Open or Short Circuit - Test
Installation Instructions For Product Link 101 Inline Timer{7602} Installation Instructions For Product Link 101 Inline Timer{7602}
2000/07/01 New Timing Control Module Used {1900, 1901}
3126B and 3126E On-highway Engines Injection Actuation Pressure Control Valve Circuit - Test
Electronic Modular Control Panel II+ (EMCP II+) GSC CID 0110 - FMI 02 (for EUI Engines)
Generator Set Control Panel for Switchgear Conversion Control Board
Programmable Relay Control Module (PRCM) Customer Device Problem
C-9 Engine for TK711, TK721, TK722, TK732, TK741, TK751, and TK752 Track Feller Bunchers Replacing the ECM
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for <B>9Y-1408</B> Generator through <B>9Y-9422</B> Generator
3126B Engine for Caterpillar Built Machines Turbocharger
3126B and 3126E On-highway Engines Injection Actuation Pressure Sensor - Test
2000/07/01 New Water Pumps With Improved Resistance To Shock Loads Used {1361}
3500 Generator Set Engines Fuel Injector Timing
3176C and 3196 Engines for Caterpillar Built Machines Fuel System Pressure - Test