Winding Data for 9Y-0157 Generator through 9Y-0389 Generator
9Y-0157 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 330.2 mm (13.0 inch)     |
342.9 mm (13.5 inch)     |
|||||
Slots     | 60     | -     | |||||
Coil Throw     | 1 - 12     | -     | |||||
Turns/Coil     | 1.6     | -     | |||||
Turns/Pole     | -     | 216     | |||||
No. & Wire Size     | 29 - #14     | #6 SQ     | |||||
Mean Length Turn     | 1630.7 mm (64.2 inch)     |
-     | |||||
Copper Weight     | 85.7 kg (189.0 lb)     |
157.8 kg (348.0 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 24 - #1/0     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00857 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.166 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 127.0 mm (5.0 inch)     |
127.0 mm (5.0 inch)     |
-     | ||||
Coils/Group     | 1     | 1     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 140     | 8     | -     | ||||
No. & Size Wire     | 1 - #15.5     | 2 - #16     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 464.8 mm (18.3 inch)     |
464.8 mm (18.3 inch)     |
-     | ||||
Copper Weight     | 5.2 kg (11.5 lb)     |
2.7 kg (6.0 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 42 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram B |
9Y-0159 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 355.6 mm (14.0 inch)     |
368.3 mm (14.5 inch)     |
|||||
Slots     | 60     | -     | |||||
Coil Throw     | 1 - 13     | -     | |||||
Turns/Coil     | 3     | -     | |||||
Turns/Pole     | -     | 216     | |||||
No. & Wire Size     | 15 - #13     | #6 SQ     | |||||
Mean Length Turn     | 1752.6 mm (69.0 inch)     |
-     | |||||
Copper Weight     | 112.9 kg (249.0 lb)     |
164.2 kg (362.0 lb)     |
|||||
Inside Connection (1)     | 4 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 24 - #1/0     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00647 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.214 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 127.0 mm (5.0 inch)     |
127.0 mm (5.0 inch)     |
-     | ||||
Coils/Group     | 1     | 1     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 140     | 8     | -     | ||||
No. & Size Wire     | 1 - #15.5     | 2 - #16     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 464.8 mm (18.3 inch)     |
464.8 mm (18.3 inch)     |
-     | ||||
Copper Weight     | 5.2 kg (11.5 lb)     |
2.7 kg (6.0 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 19 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram B |
9Y-0161 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 381.0 mm (15.0 inch)     |
393.7 mm (15.5 inch)     |
|||||
Slots     | 84     | -     | |||||
Coil Throw     | 1 - 16     | -     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 216     | |||||
No. & Wire Size     | 31 - #13     | #6 SQ     | |||||
Mean Length Turn     | 1828.8 mm (72.0 inch)     |
-     | |||||
Copper Weight     | 113.4 kg (250.0 lb)     |
170.8 kg (376.5 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 24 - #2/0     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00627 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.27 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 127.0 mm (5.0 inch)     |
127.0 mm (5.0 inch)     |
-     | ||||
Coils/Group     | 1     | 1     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 140     | 8     | -     | ||||
No. & Size Wire     | 1 - #15.5     | 2 - #16     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 464.8 mm (18.3 inch)     |
464.8 mm (18.3 inch)     |
-     | ||||
Copper Weight     | 5.2 kg (11.5 lb)     |
2.7 kg (6.0 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 42 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram B |
9Y-0163 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 431.8 mm (17.0 inch)     |
444.5 mm (17.5 inch)     |
|||||
Slots     | 72     | -     | |||||
Coil Throw     | 1 - 15     | -     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 216     | |||||
No. & Wire Size     | 39 - #13     | #6 SQ     | |||||
Mean Length Turn     | 1963.4 mm (77.3 inch)     |
-     | |||||
Copper Weight     | 144.2 kg (318.0 lb)     |
183.7 kg (405.0 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 24 - #3/0     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00461 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.380 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 127.0 mm (5.0 inch)     |
127.0 mm (5.0 inch)     |
-     | ||||
Coils/Group     | 1     | 1     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 140     | 8     | -     | ||||
No. & Size Wire     | 1 - #15.5     | 2 - #16     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 464.8 mm (18.3 inch)     |
464.8 mm (18.3 inch)     |
-     | ||||
Copper Weight     | 5.2 kg (11.5 lb)     |
2.7 kg (6.0 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 42 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram B |
9Y-0165 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 508.0 mm (20.0 inch)     |
520.7 mm (20.5 inch)     |
|||||
Slots     | 60     | -     | |||||
Coil Throw     | 1 - 13     | -     | |||||
Turns/Coil     | 2     | -     | |||||
Turns/Pole     | -     | 216     | |||||
No. & Wire Size     | 22 - #13     | #6 SQ     | |||||
Mean Length Turn     | 2082.8 mm (82.0 inch)     |
-     | |||||
Copper Weight     | 130.6 kg (288.0 lb)     |
203.7 kg (449.0 lb)     |
|||||
Inside Connection (1)     | 4 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 24 - #4/0     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00360 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.503 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 127.0 mm (5.0 inch)     |
127.0 mm (5.0 inch)     |
-     | ||||
Coils/Group     | 1     | 1     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 140     | 8     | -     | ||||
No. & Size Wire     | 1 - #15.5     | 2 - #16     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 464.8 mm (18.3 inch)     |
464.8 mm (18.3 inch)     |
-     | ||||
Copper Weight     | 5.2 kg (11.5 lb)     |
2.7 kg (6.0 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 19 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram B |
9Y-0167 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 711.2 mm (28.0 inch)     |
723.9 mm (28.5 inch)     |
|||||
Slots     | 60     | -     | |||||
Coil Throw     | 1 - 11     | -     | |||||
Turns/Coil     | 3     | -     | |||||
Turns/Pole     | -     | 225.5     | |||||
No. & Wire Size     | 2 - 5.0 mm (0.197 inch)× 6.0 mm (0.236 inch)     |
3.7 mm (0.145 inch)× 7.7 mm (0.302 inch) HF     |
|||||
Mean Length Turn     | 2489.2 mm (98.0 inch)     |
-     | |||||
Copper Weight     | 244.0 kg (537.9 lb)     |
207.2 kg (456.8 lb)     |
|||||
Inside Connection (1)     | 1 Series Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 6 - #4/0     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0912 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.184 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 120 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 8     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 63.5 mm (2.5 inch)     |
63.5 mm (2.5 inch)     |
-     | ||||
Coils/Group     | 1     | 2     | -     | ||||
Slots (Coils)     | 8     | 48     | -     | ||||
Turns (Coils)     | 160     | 7     | -     | ||||
No. & Size Wire     | 1 - #14     | 2 - #16     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 330.2 mm (13.0 inch)     |
386.1 mm (15.2 inch)     |
-     | ||||
Copper Weight     | 11.1 kg (24.5 lb)     |
6.2 kg (13.7 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 12 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram I |
9Y-0169 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 558.8 mm (22.0 inch)     |
571.5 mm (22.5 inch)     |
|||||
Slots     | 60     | -     | |||||
Coil Throw     | 1 - 11     | -     | |||||
Turns/Coil     | 2     | -     | |||||
Turns/Pole     | -     | 216     | |||||
No. & Wire Size     | 26 - #13     | #6 SQ     | |||||
Mean Length Turn     | 2049.8 mm (80.7 inch)     |
-     | |||||
Copper Weight     | 152.0 kg (335.0 lb)     |
216.4 kg (477.0 lb)     |
|||||
Inside Connection (1)     | 4 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 24 - #4/0     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00306 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.600 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 152.4 mm (6.0 inch)     |
152.4 mm (6.0 inch)     |
-     | ||||
Coils/Group     | 1     | 2     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 140     | 9     | -     | ||||
No. & Size Wire     | 1 - #15.5     | 1 - #16     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 515.6 mm (20.3 inch)     |
431.8 mm (17.0 inch)     |
-     | ||||
Copper Weight     | 6.0 kg (13.3 lb)     |
3.2 kg (7.0 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 19 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
9Y-0353 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 182.9 mm (7.2 inch)     |
182.9 mm (7.2 inch)     |
|||||
Slots     | 48     | -     | |||||
Coil Throw     | 1 - 11.3748     | -     | |||||
Turns/Coil     | 12 - 9 - 4     | -     | |||||
Turns/Pole     | -     | 96     | |||||
No. & Wire Size     | 1 - #15 and 3 - #16 SQ     | 1 - #8 3/4 RD     | |||||
Mean Length Turn     | 901.7 mm (35.5 inch)     |
-     | |||||
Copper Weight     | 13.6 kg (30.0 lb)     |
16.1 kg (35.4 lb)     |
|||||
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 12 - #6     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0367 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.7237 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 50.8 mm (2.0 inch)     |
50.8 mm (2.0 inch)     |
-     | ||||
Coils/Group     | 1     | 2     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 180     | 10     | -     | ||||
No. & Size Wire     | 1 - #17.0 SQ     | 1 - #14.5 SQ     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 315.0 mm (12.4 inch)     |
254.0 mm (10.0 inch)     |
-     | ||||
Copper Weight     | 2.7 kg (6.0 lb)     |
1.4 kg (3.1 lb)     |
-     | ||||
Insulation     | Heavy Nytherm     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 3 - #12     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 24 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
9Y-0356 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 215.9 mm (8.5 inch)     |
215.9 mm (8.5 inch)     |
|||||
Slots     | 48     | -     | |||||
Coil Throw     | 1 - 10     | -     | |||||
Turns/Coil     | 5.50 (5-6-5-6)     | -     | |||||
Turns/Pole     | -     | 96     | |||||
No. & Wire Size     | 4 - #15 SQ     | 1 - #8 3/4 RD     | |||||
Mean Length Turn     | 909.3 mm (35.8 inch)     |
-     | |||||
Copper Weight     | 14.4 kg (31.7 lb)     |
17.6 kg (38.8 lb)     |
|||||
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 12 - #4     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0317 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.7924 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 50.8 mm (2.0 inch)     |
50.8 mm (2.0 inch)     |
-     | ||||
Coils/Group     | 1     | 2     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 180     | 10     | -     | ||||
No. & Size Wire     | 1 - #17.0 SQ     | 1 - #14.5 SQ     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 315.0 mm (12.4 inch)     |
254.0 mm (10.0 inch)     |
-     | ||||
Copper Weight     | 2.7 kg (6.0 lb)     |
1.4 kg (3.1 lb)     |
-     | ||||
Insulation     | Heavy Nytherm     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 3 - #12     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 04 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
9Y-0363 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 254.0 mm (10.0 inch)     |
254.0 mm (10.0 inch)     |
|||||
Slots     | 48     | -     | |||||
Coil Throw     | 1 - 8.2512     | -     | |||||
Turns/Coil     | 4-4-4-3     | -     | |||||
Turns/Pole     | -     | 130     | |||||
No. & Wire Size     | 8 - #14.0 SQ     | 1 - #8 SQ     | |||||
Mean Length Turn     | 1104.9 mm (43.5 inch)     |
-     | |||||
Copper Weight     | 30.0 kg (66.2 lb)     |
43.5 kg (95.9 lb)     |
|||||
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 24 - #4     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0119 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.8472 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 76.2 mm (3.0 inch)     |
76.2 mm (3.0 inch)     |
-     | ||||
Coils/Group     | 1     | 2     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 150     | 7     | -     | ||||
No. & Size Wire     | 1 - #16.0 SQ     | 2 - #15.5 SQ     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 363.2 mm (14.3 inch)     |
325.1 mm (12.8 inch)     |
-     | ||||
Copper Weight     | 3.9 kg (8.5 lb)     |
2.2 kg (4.8 lb)     |
-     | ||||
Insulation     | Heavy Nytherm     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 27 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
9Y-0364 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 276.9 mm (10.9 inch)     |
276.9 mm (10.9 inch)     |
|||||
Slots     | 48     | -     | |||||
Coil Throw     | 1 - 9.2464     | -     | |||||
Turns/Coil     | 5-4-3-1     | -     | |||||
Turns/Pole     | -     | 130     | |||||
No. & Wire Size     | 9 - #14.0 SQ     | 1 - #8 SQ     | |||||
Mean Length Turn     | 1209.0 mm (47.6 inch)     |
-     | |||||
Copper Weight     | 32.1 kg (70.7 lb)     |
45.7 kg (100.7 lb)     |
|||||
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 24 - #4     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00892 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.9610 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
-     | ||||
Coils/Group     | 1     | 2     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 150     | 8     | -     | ||||
No. & Size Wire     | 1 - #16 SQ     | 2 - #16 SQ     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 388.6 mm (15.3 inch)     |
350.5 mm (13.8 inch)     |
-     | ||||
Copper Weight     | 4.1 kg (9.1 lb)     |
2.2 kg (4.8 lb)     |
-     | ||||
Insulation     | Heavy Nytherm     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 33 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 27 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
9Y-0365 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 304.8 mm (12.0 inch)     |
304.8 mm (12.0 inch)     |
|||||
Slots     | 48     | -     | |||||
Coil Throw     | 1 - 9.0708     | -     | |||||
Turns/Coil     | 4-4-3-1     | -     | |||||
Turns/Pole     | -     | 130     | |||||
No. & Wire Size     | 10 - #14.0 SQ     | 1 - #8 SQ     | |||||
Mean Length Turn     | 1252.2 mm (49.3 inch)     |
-     | |||||
Copper Weight     | 34.0 kg (75.0 lb)     |
48.4 kg (106.6 lb)     |
|||||
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 10 - #000     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0071 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.9414 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
-     | ||||
Coils/Group     | 1     | 2     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 150     | 8     | -     | ||||
No. & Size Wire     | 1 - #16 SQ     | 2 - #16 SQ     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 388.6 mm (15.3 inch)     |
350.5 mm (13.8 inch)     |
-     | ||||
Copper Weight     | 4.1 kg (9.1 lb)     |
2.2 kg (4.8 lb)     |
-     | ||||
Insulation     | Heavy Nytherm     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 33 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 25 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
9Y-0367 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 419.1 mm (16.5 inch)     |
419.1 mm (16.5 inch)     |
|||||
Slots     | 48     | -     | |||||
Coil Throw     | 1 - 10     | -     | |||||
Turns/Coil     | 2.25 (2-2-2-3)     | -     | |||||
Turns/Pole     | -     | 130     | |||||
No. & Wire Size     | 10 - #14 and 5 - #15     | #8 SQ     | |||||
Mean Length Turn     | 1470.7 mm (57.9 inch)     |
-     | |||||
Copper Weight     | 41.7 kg (91.9 lb)     |
59.1 kg (130.4 lb)     |
|||||
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 20 - #1     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00459 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.225 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
-     | ||||
Coils/Group     | 6     | 2     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 150     | 8     | -     | ||||
No. & Size Wire     | 1 - #16     | 2 - #16     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 388.6 mm (15.3 inch)     |
350.5 mm (13.8 inch)     |
-     | ||||
Copper Weight     | 4.1 kg (9.1 lb)     |
2.2 kg (4.8 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 01 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram A |
9Y-0368 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 223.5 mm (8.8 inch)     |
223.5 mm (8.8 inch)     |
|||||
Slots     | 48     | -     | |||||
Coil Throw     | 1 - 10     | -     | |||||
Turns/Coil     | 4     | -     | |||||
Turns/Pole     | -     | 130     | |||||
No. & Wire Size     | 8 - #14 and 1 - #15     | #8 SQ     | |||||
Mean Length Turn     | 1079.5 mm (42.5 inch)     |
-     | |||||
Copper Weight     | 34.4 kg (75.9 lb)     |
40.6 kg (89.4 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 24 - #4     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00982 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.828 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 76.2 mm (3.0 inch)     |
76.2 mm (3.0 inch)     |
-     | ||||
Coils/Group     | 1     | 2     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 150     | 7     | -     | ||||
No. & Size Wire     | 1 - #16     | 2 - #15.5     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 363.2 mm (14.3 inch)     |
325.1 mm (12.8 inch)     |
-     | ||||
Copper Weight     | 3.9 kg (8.5 lb)     |
2.2 kg (4.8 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 03 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram A |
9Y-0373 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 360.7 mm (14.2 inch)     |
360.7 mm (14.2 inch)     |
|||||
Slots     | 48     | -     | |||||
Coil Throw     | 1 - 9.34276     | -     | |||||
Turns/Coil     | 3-3-3-2     | -     | |||||
Turns/Pole     | -     | 130     | |||||
No. & Wire Size     | 3 - #15 and 9 - #14 SQ     | 1 - #8 SQ     | |||||
Mean Length Turn     | 1364.0 mm (53.7 inch)     |
-     | |||||
Copper Weight     | 37.0 kg (81.6 lb)     |
53.7 kg (118.3 lb)     |
|||||
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 10 - #000     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0074 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.1140 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
-     | ||||
Coils/Group     | 1     | 2     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 150     | 8     | -     | ||||
No. & Size Wire     | 1 - #16 SQ     | 2 - #16 SQ     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 388.6 mm (15.3 inch)     |
350.5 mm (13.8 inch)     |
-     | ||||
Copper Weight     | 4.1 kg (9.1 lb)     |
2.2 kg (4.8 lb)     |
-     | ||||
Insulation     | Heavy Nytherm     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 33 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 25 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
9Y-0374 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 419.1 mm (16.5 inch)     |
419.1 mm (16.5 inch)     |
|||||
Slots     | 48     | -     | |||||
Coil Throw     | 1 - 9.1220     | -     | |||||
Turns/Coil     | 4-2-2-1     | -     | |||||
Turns/Pole     | -     | 130     | |||||
No. & Wire Size     | 5 - #15 and 10 - #14 SQ     | 1 - #8 SQ     | |||||
Mean Length Turn     | 1480.8 mm (58.3 inch)     |
-     | |||||
Copper Weight     | 42.1 kg (92.8 lb)     |
59.2 kg (130.6 lb)     |
|||||
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 20 - #1     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0051 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.2250 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
-     | ||||
Coils/Group     | 1     | 2     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 150     | 8     | -     | ||||
No. & Size Wire     | 1 - #16 SQ     | 2 - #16 SQ     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 388.6 mm (15.3 inch)     |
350.5 mm (13.8 inch)     |
-     | ||||
Copper Weight     | 4.1 kg (9.1 lb)     |
2.2 kg (4.8 lb)     |
-     | ||||
Insulation     | Heavy Nytherm     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 33 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 25 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
9Y-0375 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 495.3 mm (19.5 inch)     |
495.3 mm (19.5 inch)     |
|||||
Slots     | 48     | -     | |||||
Coil Throw     | 1 - 8.8580     | -     | |||||
Turns/Coil     | 3-2-2-1     | -     | |||||
Turns/Pole     | -     | 130     | |||||
No. & Wire Size     | 2 - #16 and 14 - #14 SQ     | 1 - #8 SQ     | |||||
Mean Length Turn     | 1633.2 mm (64.3 inch)     |
-     | |||||
Copper Weight     | 50.3 kg (110.8 lb)     |
66.5 kg (146.6 lb)     |
|||||
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 20 - #0     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0049 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.3678 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
-     | ||||
Coils/Group     | 1     | 2     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 150     | 8     | -     | ||||
No. & Size Wire     | 1 - #16 SQ     | 2 - #16 SQ     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 388.6 mm (15.3 inch)     |
350.5 mm (13.8 inch)     |
-     | ||||
Copper Weight     | 4.1 kg (9.1 lb)     |
2.2 kg (4.8 lb)     |
-     | ||||
Insulation     | Heavy Nytherm     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 33 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 25 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
9Y-0377 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 360.7 mm (14.2 inch)     |
360.7 mm (14.2 inch)     |
|||||
Slots     | 48     | -     | |||||
Coil Throw     | 1 - 10     | -     | |||||
Turns/Coil     | 2.5     | -     | |||||
Turns/Pole     | -     | 130     | |||||
No. & Wire Size     | 12 - #14     | #8 SQ     | |||||
Mean Length Turn     | 1386.8 mm (54.6 inch)     |
-     | |||||
Copper Weight     | 36.8 kg (81.1 lb)     |
53.6 kg (118.2 lb)     |
|||||
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 10 - #000     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0195 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.115 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
-     | ||||
Coils/Group     | 6     | 2     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 150     | 8     | -     | ||||
No. & Size Wire     | 1 - #16     | 2 - #16     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 388.6 mm (15.3 inch)     |
350.5 mm (13.8 inch)     |
-     | ||||
Copper Weight     | 4.1 kg (9.1 lb)     |
2.2 kg (4.8 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 02 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram A |
9Y-0378 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 419.1 mm (16.5 inch)     |
419.1 mm (16.5 inch)     |
|||||
Slots     | 48     | -     | |||||
Coil Throw     | 1 - 10     | -     | |||||
Turns/Coil     | 2.25 (2-2-2-3)     | -     | |||||
Turns/Pole     | -     | 130     | |||||
No. & Wire Size     | 10 - #14 and 5 - #15     | #8 SQ     | |||||
Mean Length Turn     | 1470.7 mm (57.9 inch)     |
-     | |||||
Copper Weight     | 41.7 kg (91.9 lb)     |
59.1 kg (130.4 lb)     |
|||||
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 20 - #1     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00459 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.225 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
-     | ||||
Coils/Group     | 6     | 2     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 150     | 8     | -     | ||||
No. & Size Wire     | 1 - #16     | 2 - #16     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 388.6 mm (15.3 inch)     |
350.5 mm (13.8 inch)     |
-     | ||||
Copper Weight     | 4.1 kg (9.1 lb)     |
2.2 kg (4.8 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 01 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram A |
9Y-0379 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 495.3 mm (19.5 inch)     |
495.3 mm (19.5 inch)     |
|||||
Slots     | 48     | -     | |||||
Coil Throw     | 1 - 10     | -     | |||||
Turns/Coil     | 2     | -     | |||||
Turns/Pole     | -     | 130     | |||||
No. & Wire Size     | 18 - #14     | #8 SQ     | |||||
Mean Length Turn     | 1645.9 mm (64.8 inch)     |
-     | |||||
Copper Weight     | 52.9 kg (116.7 lb)     |
66.4 kg (146.4 lb)     |
|||||
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 20 - #0     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.014 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.40 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
-     | ||||
Coils/Group     | 6     | 2     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 150     | 8     | -     | ||||
No. & Size Wire     | 1 - #16     | 2 - #16     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 388.6 mm (15.3 inch)     |
350.5 mm (13.8 inch)     |
-     | ||||
Copper Weight     | 4.1 kg (9.1 lb)     |
2.2 kg (4.8 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 01 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram A |
9Y-0382 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 335.3 mm (13.2 inch)     |
335.3 mm (13.2 inch)     |
|||||
Slots     | 60     | -     | |||||
Coil Throw     | 1 - 13     | -     | |||||
Turns/Coil     | 1.8 (1-2-2-2-2)     | -     | |||||
Turns/Pole     | -     | 180     | |||||
No. & Wire Size     | 24 - #14     | #6.5 RD     | |||||
Mean Length Turn     | 1585.0 mm (62.4 inch)     |
-     | |||||
Copper Weight     | 77.5 kg (170.8 lb)     |
87.5 kg (193.0 lb)     |
|||||
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 24 - #000     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00288 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.27 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 127.0 mm (5.0 inch)     |
127.0 mm (5.0 inch)     |
-     | ||||
Coils/Group     | 1     | 1     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 140     | 8     | -     | ||||
No. & Size Wire     | 1 - #15.5     | 2 - #16     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 464.8 mm (18.3 inch)     |
464.8 mm (18.3 inch)     |
-     | ||||
Copper Weight     | 5.2 kg (11.5 lb)     |
2.9 kg (6.4 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 1 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 47 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
9Y-0383 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 414.0 mm (16.3 inch)     |
414.0 mm (16.3 inch)     |
|||||
Slots     | 60     | -     | |||||
Coil Throw     | 1 - 12     | -     | |||||
Turns/Coil     | 1.4 (1-2-1-2-1)     | -     | |||||
Turns/Pole     | -     | 180     | |||||
No. & Wire Size     | 27 - #14     | #6.5 RD     | |||||
Mean Length Turn     | 1678.9 mm (66.1 inch)     |
-     | |||||
Copper Weight     | 71.8 kg (158.3 lb)     |
99.8 kg (220.0 lb)     |
|||||
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 24 - #000     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00218 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.44 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 127.0 mm (5.0 inch)     |
127.0 mm (5.0 inch)     |
-     | ||||
Coils/Group     | 1     | 1     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 140     | 8     | -     | ||||
No. & Size Wire     | 1 - #15.5     | 2 - #16     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 464.8 mm (18.3 inch)     |
464.8 mm (18.3 inch)     |
-     | ||||
Copper Weight     | 5.2 kg (11.5 lb)     |
2.9 kg (6.4 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 1 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 47 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
9Y-0384 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 431.8 mm (17.0 inch)     |
431.8 mm (17.0 inch)     |
|||||
Slots     | 60     | -     | |||||
Coil Throw     | 1 - 12     | -     | |||||
Turns/Coil     | 1.4 (1-2-1-2-1)     | -     | |||||
Turns/Pole     | -     | 180     | |||||
No. & Wire Size     | 29 - #14     | #6.5 RD     | |||||
Mean Length Turn     | 1714.5 mm (67.5 inch)     |
-     | |||||
Copper Weight     | 78.9 kg (174.0 lb)     |
102.5 kg (225.9 lb)     |
|||||
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 48 - #2     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00215 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.545 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 127.0 mm (5.0 inch)     |
127.0 mm (5.0 inch)     |
-     | ||||
Coils/Group     | 1     | 1     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 140     | 8     | -     | ||||
No. & Size Wire     | 1 - #15.5     | 2 - #16     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 464.8 mm (18.3 inch)     |
464.8 mm (18.3 inch)     |
-     | ||||
Copper Weight     | 5.2 kg (11.5 lb)     |
2.9 kg (6.4 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 1 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 47 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
9Y-0385 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 457.2 mm (18.0 inch)     |
457.2 mm (18.0 inch)     |
|||||
Slots     | 60     | -     | |||||
Coil Throw     | 1 - 12     | -     | |||||
Turns/Coil     | 1.4 (1-2-1-2-1)     | -     | |||||
Turns/Pole     | -     | 180     | |||||
No. & Wire Size     | 34 - #14     | #6.5 RD     | |||||
Mean Length Turn     | 1765.3 mm (69.5 inch)     |
-     | |||||
Copper Weight     | 95.3 kg (210.0 lb)     |
106.6 kg (235.0 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 12 - #0000     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00628 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.53 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 127.0 mm (5.0 inch)     |
127.0 mm (5.0 inch)     |
-     | ||||
Coils/Group     | 1     | 1     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 140     | 8     | -     | ||||
No. & Size Wire     | 1 - #15.5     | 2 - #16     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 464.8 mm (18.3 inch)     |
464.8 mm (18.3 inch)     |
-     | ||||
Copper Weight     | 5.2 kg (11.5 lb)     |
2.9 kg (6.4 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 1 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 55 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
9Y-0386 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 558.8 mm (22.0 inch)     |
566.4 mm (22.3 inch)     |
|||||
Slots     | 60     | -     | |||||
Coil Throw     | 1 - 14     | -     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 180     | |||||
No. & Wire Size     | 35 - #14     | #6.5 RD     | |||||
Mean Length Turn     | 2095.5 mm (82.5 inch)     |
-     | |||||
Copper Weight     | 80.3 kg (177.0 lb)     |
123.4 kg (272.0 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 24 - #1     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00574 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.732 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 127.0 mm (5.0 inch)     |
127.0 mm (5.0 inch)     |
-     | ||||
Coils/Group     | 1     | 1     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 140     | 8     | -     | ||||
No. & Size Wire     | 1 - #15.5     | 2 - #16     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 464.8 mm (18.3 inch)     |
464.8 mm (18.3 inch)     |
-     | ||||
Copper Weight     | 5.2 kg (11.5 lb)     |
2.9 kg (6.4 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 1 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 41 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram B |
9Y-0389 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 335.3 mm (13.2 inch)     |
335.3 mm (13.2 inch)     |
|||||
Slots     | 60     | -     | |||||
Coil Throw     | 1 - 13     | -     | |||||
Turns/Coil     | 1.8 (1-2-2-2-2)     | -     | |||||
Turns/Pole     | -     | 180     | |||||
No. & Wire Size     | 24 - #14     | #6.5 RD     | |||||
Mean Length Turn     | 1585.0 mm (62.4 inch)     |
-     | |||||
Copper Weight     | 77.5 kg (170.8 lb)     |
87.5 kg (193.0 lb)     |
|||||
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 24 - #000     | -     | |||||
Terminal bolt size     | 3/8 inch     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00288 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.27 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | 240 Hz     | ||||
Exciter Poles     | 6     | 16     | |||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 127.0 mm (5.0 inch)     |
127.0 mm (5.0 inch)     |
25.4 mm (1.0 inch)     |
||||
Coils/Group     | 1     | 1     | 1     | ||||
Slots (Coils)     | 6     | 36     | 48     | ||||
Turns (Coils)     | 140     | 8     | 12     | ||||
No. & Size Wire     | 1 - #15.5     | 2 - #16     | 4 - #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1 - 4     | ||||
Mean Length Turn (Calc.)     | 464.8 mm (18.3 inch)     |
464.8 mm (18.3 inch)     |
208.3 mm (8.2 inch)     |
||||
Copper Weight     | 5.2 kg (11.5 lb)     |
2.9 kg (6.4 lb)     |
1.8 kg (4.0 lb)     |
||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | 1 Series     | ||||
Line Leads     | 1 - #14     | 3 - #10     | 3 - #14     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 47 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
Caterpillar Information System:
3126B and 3126E On-highway Engines Engine Speed/Timing Sensor - Calibrate
3406C Industrial Engine Manual Stop Procedure
Electronic Modular Control Panel II+ (EMCP II+) Display of Voltage or Current Is Zero (for MUI 3412C, 3508, 3512, 3516 and EUI and PEEC Engines)
Electronic Modular Control Panel II+ (EMCP II+) Component Location - For 3406E and 3500B EUI Engines With Paralleling
HT400 Pumper Reference Material
JF Series Starting Motor Starting Motor
PM3500 Power Modules Cooling System Coolant Level - Check
Programmable Relay Control Module (PRCM) PRCM CID 0477 - FMI 03
2001/06/01 New Software Is Available For The Engines That Follow {7620}
3306C Truck Engine Connecting Rod Bearings - Inspect
3406C Industrial Engine Refill Capacities
Electronic Modular Control Panel II+ (EMCP II+) Display of Voltage or Current Is Zero (for MUI 3306B, 3406C Engines)
3406C Industrial Engine Fuel Control Linkage - Check/Lubricate
3500 Generator Set Engines Fuel System Operation
EMCPII+ for Gas Engines GSC Operation Is Erratic
3500 Generator Set Engines Fuel Injection Control Linkage
3500 Generator Set Engines Fuel Transfer Pump
3500 Generator Set Engines Fuel Injector
3500 Generator Set Engines Fuel Injection Cycle
Programmable Relay Control Module (PRCM) PRCM CID 0477 - FMI 04
Programmable Relay Control Module (PRCM) PRCM CID 0478 - FMI 03
Programmable Relay Control Module (PRCM) PRCM CID 0478 - FMI 04
3126B and 3126E On-highway Engines Injector Solenoid Circuit - Test
Installation Of The 194-5338 Speed Sensor Gp and 194-5341 Speed Sensor Gp Service Repair Kits{1000} Installation Of The 194-5338 Speed Sensor Gp and 194-5341 Speed Sensor Gp Service Repair Kits{1000}