SR4 and SR4B Electric Power Generation Rewind Data Caterpillar


Winding Data for 9Y-0157 Generator through 9Y-0389 Generator

Usage:

SR4B 1BN

9Y-0157 Generator

Table 1
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
330.2 mm (13.0 inch)    

342.9 mm (13.5 inch)    
Slots     60     -    
Coil Throw     1 - 12     -    
Turns/Coil     1.6     -    
Turns/Pole     -     216    
No. & Wire Size     29 - #14     #6 SQ    
Mean Length Turn    
1630.7 mm (64.2 inch)    
-    
Copper Weight    
85.7 kg (189.0 lb)    

157.8 kg (348.0 lb)    
Inside Connection (1)     2 Parallel Star     4 in Series    
Line Leads (No. & Size)     24 - #1/0     -    
Terminal bolt size     3/8 inch     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00857 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.166 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
127.0 mm (5.0 inch)    

127.0 mm (5.0 inch)    
-    
Coils/Group     1     1     -    
Slots (Coils)     6     36     -    
Turns (Coils)     140     8     -    
No. & Size Wire     1 - #15.5     2 - #16     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
464.8 mm (18.3 inch)    

464.8 mm (18.3 inch)    
-    
Copper Weight    
5.2 kg (11.5 lb)    

2.7 kg (6.0 lb)    
-    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14     3 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 42
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram B

9Y-0159 Generator

Table 2
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
355.6 mm (14.0 inch)    

368.3 mm (14.5 inch)    
Slots     60     -    
Coil Throw     1 - 13     -    
Turns/Coil     3     -    
Turns/Pole     -     216    
No. & Wire Size     15 - #13     #6 SQ    
Mean Length Turn    
1752.6 mm (69.0 inch)    
-    
Copper Weight    
112.9 kg (249.0 lb)    

164.2 kg (362.0 lb)    
Inside Connection (1)     4 Parallel Star     4 in Series    
Line Leads (No. & Size)     24 - #1/0     -    
Terminal bolt size     3/8 inch     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00647 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.214 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
127.0 mm (5.0 inch)    

127.0 mm (5.0 inch)    
-    
Coils/Group     1     1     -    
Slots (Coils)     6     36     -    
Turns (Coils)     140     8     -    
No. & Size Wire     1 - #15.5     2 - #16     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
464.8 mm (18.3 inch)    

464.8 mm (18.3 inch)    
-    
Copper Weight    
5.2 kg (11.5 lb)    

2.7 kg (6.0 lb)    
-    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14     3 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 19
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram B

9Y-0161 Generator

Table 3
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
381.0 mm (15.0 inch)    

393.7 mm (15.5 inch)    
Slots     84     -    
Coil Throw     1 - 16     -    
Turns/Coil     1     -    
Turns/Pole     -     216    
No. & Wire Size     31 - #13     #6 SQ    
Mean Length Turn    
1828.8 mm (72.0 inch)    
-    
Copper Weight    
113.4 kg (250.0 lb)    

170.8 kg (376.5 lb)    
Inside Connection (1)     2 Parallel Star     4 in Series    
Line Leads (No. & Size)     24 - #2/0     -    
Terminal bolt size     3/8 inch     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00627 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.27 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
127.0 mm (5.0 inch)    

127.0 mm (5.0 inch)    
-    
Coils/Group     1     1     -    
Slots (Coils)     6     36     -    
Turns (Coils)     140     8     -    
No. & Size Wire     1 - #15.5     2 - #16     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
464.8 mm (18.3 inch)    

464.8 mm (18.3 inch)    
-    
Copper Weight    
5.2 kg (11.5 lb)    

2.7 kg (6.0 lb)    
-    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14     3 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 42
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram B

9Y-0163 Generator

Table 4
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
431.8 mm (17.0 inch)    

444.5 mm (17.5 inch)    
Slots     72     -    
Coil Throw     1 - 15     -    
Turns/Coil     1     -    
Turns/Pole     -     216    
No. & Wire Size     39 - #13     #6 SQ    
Mean Length Turn    
1963.4 mm (77.3 inch)    
-    
Copper Weight    
144.2 kg (318.0 lb)    

183.7 kg (405.0 lb)    
Inside Connection (1)     2 Parallel Star     4 in Series    
Line Leads (No. & Size)     24 - #3/0     -    
Terminal bolt size     3/8 inch     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00461 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.380 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
127.0 mm (5.0 inch)    

127.0 mm (5.0 inch)    
-    
Coils/Group     1     1     -    
Slots (Coils)     6     36     -    
Turns (Coils)     140     8     -    
No. & Size Wire     1 - #15.5     2 - #16     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
464.8 mm (18.3 inch)    

464.8 mm (18.3 inch)    
-    
Copper Weight    
5.2 kg (11.5 lb)    

2.7 kg (6.0 lb)    
-    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14     3 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 42
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram B

9Y-0165 Generator

Table 5
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
508.0 mm (20.0 inch)    

520.7 mm (20.5 inch)    
Slots     60     -    
Coil Throw     1 - 13     -    
Turns/Coil     2     -    
Turns/Pole     -     216    
No. & Wire Size     22 - #13     #6 SQ    
Mean Length Turn    
2082.8 mm (82.0 inch)    
-    
Copper Weight    
130.6 kg (288.0 lb)    

203.7 kg (449.0 lb)    
Inside Connection (1)     4 Parallel Star     4 in Series    
Line Leads (No. & Size)     24 - #4/0     -    
Terminal bolt size     3/8 inch     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00360 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.503 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
127.0 mm (5.0 inch)    

127.0 mm (5.0 inch)    
-    
Coils/Group     1     1     -    
Slots (Coils)     6     36     -    
Turns (Coils)     140     8     -    
No. & Size Wire     1 - #15.5     2 - #16     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
464.8 mm (18.3 inch)    

464.8 mm (18.3 inch)    
-    
Copper Weight    
5.2 kg (11.5 lb)    

2.7 kg (6.0 lb)    
-    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14     3 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 19
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram B

9Y-0167 Generator

Table 6
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
711.2 mm (28.0 inch)    

723.9 mm (28.5 inch)    
Slots     60     -    
Coil Throw     1 - 11     -    
Turns/Coil     3     -    
Turns/Pole     -     225.5    
No. & Wire Size     2 -
5.0 mm (0.197 inch)×
6.0 mm (0.236 inch)    

3.7 mm (0.145 inch)×
7.7 mm (0.302 inch) HF    
Mean Length Turn    
2489.2 mm (98.0 inch)    
-    
Copper Weight    
244.0 kg (537.9 lb)    

207.2 kg (456.8 lb)    
Inside Connection (1)     1 Series Star     4 in Series    
Line Leads (No. & Size)     6 - #4/0     -    
Terminal bolt size     3/8 inch     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.0912 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.184 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     120 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     8    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
63.5 mm (2.5 inch)    

63.5 mm (2.5 inch)    
-    
Coils/Group     1     2     -    
Slots (Coils)     8     48     -    
Turns (Coils)     160     7     -    
No. & Size Wire     1 - #14     2 - #16     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
330.2 mm (13.0 inch)    

386.1 mm (15.2 inch)    
-    
Copper Weight    
11.1 kg (24.5 lb)    

6.2 kg (13.7 lb)    
-    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14     3 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 12
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram I

9Y-0169 Generator

Table 7
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
558.8 mm (22.0 inch)    

571.5 mm (22.5 inch)    
Slots     60     -    
Coil Throw     1 - 11     -    
Turns/Coil     2     -    
Turns/Pole     -     216    
No. & Wire Size     26 - #13     #6 SQ    
Mean Length Turn    
2049.8 mm (80.7 inch)    
-    
Copper Weight    
152.0 kg (335.0 lb)    

216.4 kg (477.0 lb)    
Inside Connection (1)     4 Parallel Star     4 in Series    
Line Leads (No. & Size)     24 - #4/0     -    
Terminal bolt size     3/8 inch     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00306 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.600 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
152.4 mm (6.0 inch)    

152.4 mm (6.0 inch)    
-    
Coils/Group     1     2     -    
Slots (Coils)     6     36     -    
Turns (Coils)     140     9     -    
No. & Size Wire     1 - #15.5     1 - #16     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
515.6 mm (20.3 inch)    

431.8 mm (17.0 inch)    
-    
Copper Weight    
6.0 kg (13.3 lb)    

3.2 kg (7.0 lb)    
-    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14     3 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 19
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram D

9Y-0353 Generator

Table 8
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
182.9 mm (7.2 inch)    

182.9 mm (7.2 inch)    
Slots     48     -    
Coil Throw     1 - 11.3748     -    
Turns/Coil     12 - 9 - 4     -    
Turns/Pole     -     96    
No. & Wire Size     1 - #15 and 3 - #16 SQ     1 - #8 3/4 RD    
Mean Length Turn    
901.7 mm (35.5 inch)    
-    
Copper Weight    
13.6 kg (30.0 lb)    

16.1 kg (35.4 lb)    
Inside Connection (1)     4/2 Parallel Star     4 in Series    
Line Leads (No. & Size)     12 - #6     -    
Terminal bolt size     3/8 inch     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.0367 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     0.7237 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
50.8 mm (2.0 inch)    

50.8 mm (2.0 inch)    
-    
Coils/Group     1     2     -    
Slots (Coils)     6     36     -    
Turns (Coils)     180     10     -    
No. & Size Wire     1 - #17.0 SQ     1 - #14.5 SQ     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
315.0 mm (12.4 inch)    

254.0 mm (10.0 inch)    
-    
Copper Weight    
2.7 kg (6.0 lb)    

1.4 kg (3.1 lb)    
-    
Insulation     Heavy Nytherm    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14     3 - #12     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 24
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram D

9Y-0356 Generator

Table 9
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
215.9 mm (8.5 inch)    

215.9 mm (8.5 inch)    
Slots     48     -    
Coil Throw     1 - 10     -    
Turns/Coil     5.50 (5-6-5-6)     -    
Turns/Pole     -     96    
No. & Wire Size     4 - #15 SQ     1 - #8 3/4 RD    
Mean Length Turn    
909.3 mm (35.8 inch)    
-    
Copper Weight    
14.4 kg (31.7 lb)    

17.6 kg (38.8 lb)    
Inside Connection (1)     4/2 Parallel Star     4 in Series    
Line Leads (No. & Size)     12 - #4     -    
Terminal bolt size     3/8 inch     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.0317 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     0.7924 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
50.8 mm (2.0 inch)    

50.8 mm (2.0 inch)    
-    
Coils/Group     1     2     -    
Slots (Coils)     6     36     -    
Turns (Coils)     180     10     -    
No. & Size Wire     1 - #17.0 SQ     1 - #14.5 SQ     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
315.0 mm (12.4 inch)    

254.0 mm (10.0 inch)    
-    
Copper Weight    
2.7 kg (6.0 lb)    

1.4 kg (3.1 lb)    
-    
Insulation     Heavy Nytherm    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14     3 - #12     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 04
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram D

9Y-0363 Generator

Table 10
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
254.0 mm (10.0 inch)    

254.0 mm (10.0 inch)    
Slots     48     -    
Coil Throw     1 - 8.2512     -    
Turns/Coil     4-4-4-3     -    
Turns/Pole     -     130    
No. & Wire Size     8 - #14.0 SQ     1 - #8 SQ    
Mean Length Turn    
1104.9 mm (43.5 inch)    
-    
Copper Weight    
30.0 kg (66.2 lb)    

43.5 kg (95.9 lb)    
Inside Connection (1)     4/2 Parallel Star     4 in Series    
Line Leads (No. & Size)     24 - #4     -    
Terminal bolt size     3/8 inch     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.0119 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     0.8472 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
76.2 mm (3.0 inch)    

76.2 mm (3.0 inch)    
-    
Coils/Group     1     2     -    
Slots (Coils)     6     36     -    
Turns (Coils)     150     7     -    
No. & Size Wire     1 - #16.0 SQ     2 - #15.5 SQ     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
363.2 mm (14.3 inch)    

325.1 mm (12.8 inch)    
-    
Copper Weight    
3.9 kg (8.5 lb)    

2.2 kg (4.8 lb)    
-    
Insulation     Heavy Nytherm    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14     3 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 27
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram D

9Y-0364 Generator

Table 11
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
276.9 mm (10.9 inch)    

276.9 mm (10.9 inch)    
Slots     48     -    
Coil Throw     1 - 9.2464     -    
Turns/Coil     5-4-3-1     -    
Turns/Pole     -     130    
No. & Wire Size     9 - #14.0 SQ     1 - #8 SQ    
Mean Length Turn    
1209.0 mm (47.6 inch)    
-    
Copper Weight    
32.1 kg (70.7 lb)    

45.7 kg (100.7 lb)    
Inside Connection (1)     4/2 Parallel Star     4 in Series    
Line Leads (No. & Size)     24 - #4     -    
Terminal bolt size     3/8 inch     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00892 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     0.9610 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
88.9 mm (3.5 inch)    

88.9 mm (3.5 inch)    
-    
Coils/Group     1     2     -    
Slots (Coils)     6     36     -    
Turns (Coils)     150     8     -    
No. & Size Wire     1 - #16 SQ     2 - #16 SQ     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
388.6 mm (15.3 inch)    

350.5 mm (13.8 inch)    
-    
Copper Weight    
4.1 kg (9.1 lb)    

2.2 kg (4.8 lb)    
-    
Insulation     Heavy Nytherm    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14     33 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 27
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram D

9Y-0365 Generator

Table 12
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
304.8 mm (12.0 inch)    

304.8 mm (12.0 inch)    
Slots     48     -    
Coil Throw     1 - 9.0708     -    
Turns/Coil     4-4-3-1     -    
Turns/Pole     -     130    
No. & Wire Size     10 - #14.0 SQ     1 - #8 SQ    
Mean Length Turn    
1252.2 mm (49.3 inch)    
-    
Copper Weight    
34.0 kg (75.0 lb)    

48.4 kg (106.6 lb)    
Inside Connection (1)     4/2 Parallel Star     4 in Series    
Line Leads (No. & Size)     10 - #000     -    
Terminal bolt size     3/8 inch     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.0071 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     0.9414 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
88.9 mm (3.5 inch)    

88.9 mm (3.5 inch)    
-    
Coils/Group     1     2     -    
Slots (Coils)     6     36     -    
Turns (Coils)     150     8     -    
No. & Size Wire     1 - #16 SQ     2 - #16 SQ     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
388.6 mm (15.3 inch)    

350.5 mm (13.8 inch)    
-    
Copper Weight    
4.1 kg (9.1 lb)    

2.2 kg (4.8 lb)    
-    
Insulation     Heavy Nytherm    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14     33 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 25
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram D

9Y-0367 Generator

Table 13
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
419.1 mm (16.5 inch)    

419.1 mm (16.5 inch)    
Slots     48     -    
Coil Throw     1 - 10     -    
Turns/Coil     2.25 (2-2-2-3)     -    
Turns/Pole     -     130    
No. & Wire Size     10 - #14 and 5 - #15     #8 SQ    
Mean Length Turn    
1470.7 mm (57.9 inch)    
-    
Copper Weight    
41.7 kg (91.9 lb)    

59.1 kg (130.4 lb)    
Inside Connection (1)     4/2 Parallel Star     4 in Series    
Line Leads (No. & Size)     20 - #1     -    
Terminal bolt size     3/8 inch     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00459 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.225 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
88.9 mm (3.5 inch)    

88.9 mm (3.5 inch)    
-    
Coils/Group     6     2     -    
Slots (Coils)     6     36     -    
Turns (Coils)     150     8     -    
No. & Size Wire     1 - #16     2 - #16     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
388.6 mm (15.3 inch)    

350.5 mm (13.8 inch)    
-    
Copper Weight    
4.1 kg (9.1 lb)    

2.2 kg (4.8 lb)    
-    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14     3 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 01
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram A

9Y-0368 Generator

Table 14
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
223.5 mm (8.8 inch)    

223.5 mm (8.8 inch)    
Slots     48     -    
Coil Throw     1 - 10     -    
Turns/Coil     4     -    
Turns/Pole     -     130    
No. & Wire Size     8 - #14 and 1 - #15     #8 SQ    
Mean Length Turn    
1079.5 mm (42.5 inch)    
-    
Copper Weight    
34.4 kg (75.9 lb)    

40.6 kg (89.4 lb)    
Inside Connection (1)     2 Parallel Star     4 in Series    
Line Leads (No. & Size)     24 - #4     -    
Terminal bolt size     3/8 inch     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00982 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     0.828 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
76.2 mm (3.0 inch)    

76.2 mm (3.0 inch)    
-    
Coils/Group     1     2     -    
Slots (Coils)     6     36     -    
Turns (Coils)     150     7     -    
No. & Size Wire     1 - #16     2 - #15.5     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
363.2 mm (14.3 inch)    

325.1 mm (12.8 inch)    
-    
Copper Weight    
3.9 kg (8.5 lb)    

2.2 kg (4.8 lb)    
-    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14     3 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 03
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram A

9Y-0373 Generator

Table 15
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
360.7 mm (14.2 inch)    

360.7 mm (14.2 inch)    
Slots     48     -    
Coil Throw     1 - 9.34276     -    
Turns/Coil     3-3-3-2     -    
Turns/Pole     -     130    
No. & Wire Size     3 - #15 and 9 - #14 SQ     1 - #8 SQ    
Mean Length Turn    
1364.0 mm (53.7 inch)    
-    
Copper Weight    
37.0 kg (81.6 lb)    

53.7 kg (118.3 lb)    
Inside Connection (1)     4/2 Parallel Star     4 in Series    
Line Leads (No. & Size)     10 - #000     -    
Terminal bolt size     3/8 inch     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.0074 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.1140 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
88.9 mm (3.5 inch)    

88.9 mm (3.5 inch)    
-    
Coils/Group     1     2     -    
Slots (Coils)     6     36     -    
Turns (Coils)     150     8     -    
No. & Size Wire     1 - #16 SQ     2 - #16 SQ     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
388.6 mm (15.3 inch)    

350.5 mm (13.8 inch)    
-    
Copper Weight    
4.1 kg (9.1 lb)    

2.2 kg (4.8 lb)    
-    
Insulation     Heavy Nytherm    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14     33 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 25
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram D

9Y-0374 Generator

Table 16
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
419.1 mm (16.5 inch)    

419.1 mm (16.5 inch)    
Slots     48     -    
Coil Throw     1 - 9.1220     -    
Turns/Coil     4-2-2-1     -    
Turns/Pole     -     130    
No. & Wire Size     5 - #15 and 10 - #14 SQ     1 - #8 SQ    
Mean Length Turn    
1480.8 mm (58.3 inch)    
-    
Copper Weight    
42.1 kg (92.8 lb)    

59.2 kg (130.6 lb)    
Inside Connection (1)     4/2 Parallel Star     4 in Series    
Line Leads (No. & Size)     20 - #1     -    
Terminal bolt size     3/8 inch     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.0051 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.2250 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
88.9 mm (3.5 inch)    

88.9 mm (3.5 inch)    
-    
Coils/Group     1     2     -    
Slots (Coils)     6     36     -    
Turns (Coils)     150     8     -    
No. & Size Wire     1 - #16 SQ     2 - #16 SQ     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
388.6 mm (15.3 inch)    

350.5 mm (13.8 inch)    
-    
Copper Weight    
4.1 kg (9.1 lb)    

2.2 kg (4.8 lb)    
-    
Insulation     Heavy Nytherm    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14     33 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 25
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram D

9Y-0375 Generator

Table 17
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
495.3 mm (19.5 inch)    

495.3 mm (19.5 inch)    
Slots     48     -    
Coil Throw     1 - 8.8580     -    
Turns/Coil     3-2-2-1     -    
Turns/Pole     -     130    
No. & Wire Size     2 - #16 and 14 - #14 SQ     1 - #8 SQ    
Mean Length Turn    
1633.2 mm (64.3 inch)    
-    
Copper Weight    
50.3 kg (110.8 lb)    

66.5 kg (146.6 lb)    
Inside Connection (1)     4/2 Parallel Star     4 in Series    
Line Leads (No. & Size)     20 - #0     -    
Terminal bolt size     3/8 inch     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.0049 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.3678 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
88.9 mm (3.5 inch)    

88.9 mm (3.5 inch)    
-    
Coils/Group     1     2     -    
Slots (Coils)     6     36     -    
Turns (Coils)     150     8     -    
No. & Size Wire     1 - #16 SQ     2 - #16 SQ     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
388.6 mm (15.3 inch)    

350.5 mm (13.8 inch)    
-    
Copper Weight    
4.1 kg (9.1 lb)    

2.2 kg (4.8 lb)    
-    
Insulation     Heavy Nytherm    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14     33 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 25
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram D

9Y-0377 Generator

Table 18
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
360.7 mm (14.2 inch)    

360.7 mm (14.2 inch)    
Slots     48     -    
Coil Throw     1 - 10     -    
Turns/Coil     2.5     -    
Turns/Pole     -     130    
No. & Wire Size     12 - #14     #8 SQ    
Mean Length Turn    
1386.8 mm (54.6 inch)    
-    
Copper Weight    
36.8 kg (81.1 lb)    

53.6 kg (118.2 lb)    
Inside Connection (1)     4/2 Parallel Star     4 in Series    
Line Leads (No. & Size)     10 - #000     -    
Terminal bolt size     3/8 inch     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.0195 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.115 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
88.9 mm (3.5 inch)    

88.9 mm (3.5 inch)    
-    
Coils/Group     6     2     -    
Slots (Coils)     6     36     -    
Turns (Coils)     150     8     -    
No. & Size Wire     1 - #16     2 - #16     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
388.6 mm (15.3 inch)    

350.5 mm (13.8 inch)    
-    
Copper Weight    
4.1 kg (9.1 lb)    

2.2 kg (4.8 lb)    
-    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14     3 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 02
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram A

9Y-0378 Generator

Table 19
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
419.1 mm (16.5 inch)    

419.1 mm (16.5 inch)    
Slots     48     -    
Coil Throw     1 - 10     -    
Turns/Coil     2.25 (2-2-2-3)     -    
Turns/Pole     -     130    
No. & Wire Size     10 - #14 and 5 - #15     #8 SQ    
Mean Length Turn    
1470.7 mm (57.9 inch)    
-    
Copper Weight    
41.7 kg (91.9 lb)    

59.1 kg (130.4 lb)    
Inside Connection (1)     4/2 Parallel Star     4 in Series    
Line Leads (No. & Size)     20 - #1     -    
Terminal bolt size     3/8 inch     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00459 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.225 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
88.9 mm (3.5 inch)    

88.9 mm (3.5 inch)    
-    
Coils/Group     6     2     -    
Slots (Coils)     6     36     -    
Turns (Coils)     150     8     -    
No. & Size Wire     1 - #16     2 - #16     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
388.6 mm (15.3 inch)    

350.5 mm (13.8 inch)    
-    
Copper Weight    
4.1 kg (9.1 lb)    

2.2 kg (4.8 lb)    
-    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14     3 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 01
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram A

9Y-0379 Generator

Table 20
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
495.3 mm (19.5 inch)    

495.3 mm (19.5 inch)    
Slots     48     -    
Coil Throw     1 - 10     -    
Turns/Coil     2     -    
Turns/Pole     -     130    
No. & Wire Size     18 - #14     #8 SQ    
Mean Length Turn    
1645.9 mm (64.8 inch)    
-    
Copper Weight    
52.9 kg (116.7 lb)    

66.4 kg (146.4 lb)    
Inside Connection (1)     4/2 Parallel Star     4 in Series    
Line Leads (No. & Size)     20 - #0     -    
Terminal bolt size     3/8 inch     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.014 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.40 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
88.9 mm (3.5 inch)    

88.9 mm (3.5 inch)    
-    
Coils/Group     6     2     -    
Slots (Coils)     6     36     -    
Turns (Coils)     150     8     -    
No. & Size Wire     1 - #16     2 - #16     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
388.6 mm (15.3 inch)    

350.5 mm (13.8 inch)    
-    
Copper Weight    
4.1 kg (9.1 lb)    

2.2 kg (4.8 lb)    
-    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14     3 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 01
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram A

9Y-0382 Generator

Table 21
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
335.3 mm (13.2 inch)    

335.3 mm (13.2 inch)    
Slots     60     -    
Coil Throw     1 - 13     -    
Turns/Coil     1.8 (1-2-2-2-2)     -    
Turns/Pole     -     180    
No. & Wire Size     24 - #14     #6.5 RD    
Mean Length Turn    
1585.0 mm (62.4 inch)    
-    
Copper Weight    
77.5 kg (170.8 lb)    

87.5 kg (193.0 lb)    
Inside Connection (1)     4/2 Parallel Star     4 in Series    
Line Leads (No. & Size)     24 - #000     -    
Terminal bolt size     3/8 inch     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00288 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.27 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
127.0 mm (5.0 inch)    

127.0 mm (5.0 inch)    
-    
Coils/Group     1     1     -    
Slots (Coils)     6     36     -    
Turns (Coils)     140     8     -    
No. & Size Wire     1 - #15.5     2 - #16     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
464.8 mm (18.3 inch)    

464.8 mm (18.3 inch)    
-    
Copper Weight    
5.2 kg (11.5 lb)    

2.9 kg (6.4 lb)    
-    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     1 - #14     3 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 47
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram D

9Y-0383 Generator

Table 22
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
414.0 mm (16.3 inch)    

414.0 mm (16.3 inch)    
Slots     60     -    
Coil Throw     1 - 12     -    
Turns/Coil     1.4 (1-2-1-2-1)     -    
Turns/Pole     -     180    
No. & Wire Size     27 - #14     #6.5 RD    
Mean Length Turn    
1678.9 mm (66.1 inch)    
-    
Copper Weight    
71.8 kg (158.3 lb)    

99.8 kg (220.0 lb)    
Inside Connection (1)     4/2 Parallel Star     4 in Series    
Line Leads (No. & Size)     24 - #000     -    
Terminal bolt size     3/8 inch     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00218 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.44 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
127.0 mm (5.0 inch)    

127.0 mm (5.0 inch)    
-    
Coils/Group     1     1     -    
Slots (Coils)     6     36     -    
Turns (Coils)     140     8     -    
No. & Size Wire     1 - #15.5     2 - #16     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
464.8 mm (18.3 inch)    

464.8 mm (18.3 inch)    
-    
Copper Weight    
5.2 kg (11.5 lb)    

2.9 kg (6.4 lb)    
-    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     1 - #14     3 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 47
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram D

9Y-0384 Generator

Table 23
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
431.8 mm (17.0 inch)    

431.8 mm (17.0 inch)    
Slots     60     -    
Coil Throw     1 - 12     -    
Turns/Coil     1.4 (1-2-1-2-1)     -    
Turns/Pole     -     180    
No. & Wire Size     29 - #14     #6.5 RD    
Mean Length Turn    
1714.5 mm (67.5 inch)    
-    
Copper Weight    
78.9 kg (174.0 lb)    

102.5 kg (225.9 lb)    
Inside Connection (1)     4/2 Parallel Star     4 in Series    
Line Leads (No. & Size)     48 - #2     -    
Terminal bolt size     3/8 inch     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00215 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.545 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
127.0 mm (5.0 inch)    

127.0 mm (5.0 inch)    
-    
Coils/Group     1     1     -    
Slots (Coils)     6     36     -    
Turns (Coils)     140     8     -    
No. & Size Wire     1 - #15.5     2 - #16     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
464.8 mm (18.3 inch)    

464.8 mm (18.3 inch)    
-    
Copper Weight    
5.2 kg (11.5 lb)    

2.9 kg (6.4 lb)    
-    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     1 - #14     3 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 47
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram D

9Y-0385 Generator

Table 24
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
457.2 mm (18.0 inch)    

457.2 mm (18.0 inch)    
Slots     60     -    
Coil Throw     1 - 12     -    
Turns/Coil     1.4 (1-2-1-2-1)     -    
Turns/Pole     -     180    
No. & Wire Size     34 - #14     #6.5 RD    
Mean Length Turn    
1765.3 mm (69.5 inch)    
-    
Copper Weight    
95.3 kg (210.0 lb)    

106.6 kg (235.0 lb)    
Inside Connection (1)     2 Parallel Star     4 in Series    
Line Leads (No. & Size)     12 - #0000     -    
Terminal bolt size     3/8 inch     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00628 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.53 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
127.0 mm (5.0 inch)    

127.0 mm (5.0 inch)    
-    
Coils/Group     1     1     -    
Slots (Coils)     6     36     -    
Turns (Coils)     140     8     -    
No. & Size Wire     1 - #15.5     2 - #16     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
464.8 mm (18.3 inch)    

464.8 mm (18.3 inch)    
-    
Copper Weight    
5.2 kg (11.5 lb)    

2.9 kg (6.4 lb)    
-    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     1 - #14     3 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 55
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram D

9Y-0386 Generator

Table 25
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
558.8 mm (22.0 inch)    

566.4 mm (22.3 inch)    
Slots     60     -    
Coil Throw     1 - 14     -    
Turns/Coil     1     -    
Turns/Pole     -     180    
No. & Wire Size     35 - #14     #6.5 RD    
Mean Length Turn    
2095.5 mm (82.5 inch)    
-    
Copper Weight    
80.3 kg (177.0 lb)    

123.4 kg (272.0 lb)    
Inside Connection (1)     2 Parallel Star     4 in Series    
Line Leads (No. & Size)     24 - #1     -    
Terminal bolt size     3/8 inch     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00574 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.732 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
127.0 mm (5.0 inch)    

127.0 mm (5.0 inch)    
-    
Coils/Group     1     1     -    
Slots (Coils)     6     36     -    
Turns (Coils)     140     8     -    
No. & Size Wire     1 - #15.5     2 - #16     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
464.8 mm (18.3 inch)    

464.8 mm (18.3 inch)    
-    
Copper Weight    
5.2 kg (11.5 lb)    

2.9 kg (6.4 lb)    
-    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     1 - #14     3 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 41
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram B

9Y-0389 Generator

Table 26
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
335.3 mm (13.2 inch)    

335.3 mm (13.2 inch)    
Slots     60     -    
Coil Throw     1 - 13     -    
Turns/Coil     1.8 (1-2-2-2-2)     -    
Turns/Pole     -     180    
No. & Wire Size     24 - #14     #6.5 RD    
Mean Length Turn    
1585.0 mm (62.4 inch)    
-    
Copper Weight    
77.5 kg (170.8 lb)    

87.5 kg (193.0 lb)    
Inside Connection (1)     4/2 Parallel Star     4 in Series    
Line Leads (No. & Size)     24 - #000     -    
Terminal bolt size     3/8 inch     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00288 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.27 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     240 Hz    
Exciter Poles     6     16    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
127.0 mm (5.0 inch)    

127.0 mm (5.0 inch)    

25.4 mm (1.0 inch)    
Coils/Group     1     1     1    
Slots (Coils)     6     36     48    
Turns (Coils)     140     8     12    
No. & Size Wire     1 - #15.5     2 - #16     4 - #18    
Coil Throw     1 - 2     1 - 6     1 - 4    
Mean Length Turn (Calc.)    
464.8 mm (18.3 inch)    

464.8 mm (18.3 inch)    

208.3 mm (8.2 inch)    
Copper Weight    
5.2 kg (11.5 lb)    

2.9 kg (6.4 lb)    

1.8 kg (4.0 lb)    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     1 Series    
Line Leads     1 - #14     3 - #10     3 - #14    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 47
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram D

Caterpillar Information System:

3126B and 3126E On-highway Engines Engine Speed/Timing Sensor - Calibrate
3406C Industrial Engine Manual Stop Procedure
Electronic Modular Control Panel II+ (EMCP II+) Display of Voltage or Current Is Zero (for MUI 3412C, 3508, 3512, 3516 and EUI and PEEC Engines)
Electronic Modular Control Panel II+ (EMCP II+) Component Location - For 3406E and 3500B EUI Engines With Paralleling
HT400 Pumper Reference Material
JF Series Starting Motor Starting Motor
PM3500 Power Modules Cooling System Coolant Level - Check
Programmable Relay Control Module (PRCM) PRCM CID 0477 - FMI 03
2001/06/01 New Software Is Available For The Engines That Follow {7620}
3306C Truck Engine Connecting Rod Bearings - Inspect
3406C Industrial Engine Refill Capacities
Electronic Modular Control Panel II+ (EMCP II+) Display of Voltage or Current Is Zero (for MUI 3306B, 3406C Engines)
3406C Industrial Engine Fuel Control Linkage - Check/Lubricate
3500 Generator Set Engines Fuel System Operation
EMCPII+ for Gas Engines GSC Operation Is Erratic
3500 Generator Set Engines Fuel Injection Control Linkage
3500 Generator Set Engines Fuel Transfer Pump
3500 Generator Set Engines Fuel Injector
3500 Generator Set Engines Fuel Injection Cycle
Programmable Relay Control Module (PRCM) PRCM CID 0477 - FMI 04
Programmable Relay Control Module (PRCM) PRCM CID 0478 - FMI 03
Programmable Relay Control Module (PRCM) PRCM CID 0478 - FMI 04
3126B and 3126E On-highway Engines Injector Solenoid Circuit - Test
Installation Of The 194-5338 Speed Sensor Gp and 194-5341 Speed Sensor Gp Service Repair Kits{1000} Installation Of The 194-5338 Speed Sensor Gp and 194-5341 Speed Sensor Gp Service Repair Kits{1000}
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.