Winding Data for 5N-7208 Generator through 5N-7232 Generator
5N-7208 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 419.1 mm (16.5 inch)     |
431.8 mm (17.0 inch)     |
-     | |
Slots     | 72     | -     | -     | |
Coil Throw     | 1 - 10     | -     | -     | |
Turns/Coil     | 2.5(2,3,2,3)     | -     | -     | |
Turns/Pole     | -     | 154.5     | -     | |
No. & Wire Size     | 17 - #13     | 1 - 3.3 mm x 6.4 mm (.13 inch x .25 inch)     |
-     | |
Mean Length Turn     | 1607.8 mm (63.3 inch)     |
-     | -     | |
Copper Weight     | 115.7 kg (255.0 lb)     |
220.3 kg (485.7 lb)     |
-     | |
Inside Connection (1)     | 6/3 Parallel Star     | 6 in Series     | -     | |
Line Leads (No. & Size)     | 30 - #00     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 °C (77 °F)     |
0.0087 ohms     | -     | -     | |
Field lead resistance at 25 °C (77 °F)     |
-     | 1.046 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 80 Hz     | |||
Exciter Poles     | 8     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 8     | 48     | ||
Turns (Coils)     | 160     | 8     | ||
No. & Size Wire     | 1 - #18 and 2 - #17     | 3 - #16     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 355.6 mm (14.0 inch)     |
436.9 mm (17.2 inch)     |
||
Copper Weight     | 6.4 kg (14.0 lb)     |
13.6 kg (29.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 762.0 mm (30.0 inch)     |
#10 304.8 mm (12.0 inch)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #38 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram C |
5N-7209 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 419.1 mm (16.5 inch)     |
431.8 mm (17.0 inch)     |
-     | |
Slots     | 72     | -     | -     | |
Coil Throw     | 1 - 10     | -     | -     | |
Turns/Coil     | 3     | -     | -     | |
Turns/Pole     | -     | 154.5     | -     | |
No. & Wire Size     | 14 - #13     | 1 - 3.3 mm x 6.4 mm (.13 inch x .25 inch)     |
-     | |
Mean Length Turn     | 1607.8 mm (63.3 inch)     |
-     | -     | |
Copper Weight     | 115.7 kg (255.0 lb)     |
220.3 kg (485.7 lb)     |
-     | |
Inside Connection (1)     | 6/3 Parallel Star     | 6 in Series     | -     | |
Line Leads (No. & Size)     | 30 - #1     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0126 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.046 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 80 Hz     | |||
Exciter Poles     | 8     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 8     | 48     | ||
Turns (Coils)     | 160     | 8     | ||
No. & Size Wire     | 1 - #18 and 2 - #17     | 3 - #16     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 355.6 mm (14.0 inch)     |
436.9 mm (17.2 inch)     |
||
Copper Weight     | 6.4 kg (14.0 lb)     |
13.6 kg (29.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 762.0 mm (30.0 inch)     |
#10 304.8 mm (12.0 inch)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #38 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram C |
5N-7210 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 419.1 mm (16.5 inch)     |
431.8 mm (17.0 inch)     |
-     | |
Slots     | 72     | -     | -     | |
Coil Throw     | 1 - 10     | -     | -     | |
Turns/Coil     | 2.5 (2,3,2,3)     | -     | -     | |
Turns/Pole     | -     | 154.5     | -     | |
No. & Wire Size     | 17 - #13     | 1 - 3.3 mm x 6.4 mm (.13 inch x .25 inch)     |
-     | |
Mean Length Turn     | 1607.8 mm (63.3 inch)     |
-     | -     | |
Copper Weight     | 115.7 kg (255.0 lb)     |
220.3 kg (485.7 lb)     |
-     | |
Inside Connection (1)     | 6/3 Parallel Star     | 6 in Series     | -     | |
Line Leads (No. & Size)     | 30 - #00     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0087 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.046 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 80 Hz     | |||
Exciter Poles     | 8     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 8     | 48     | ||
Turns (Coils)     | 160     | 8     | ||
No. & Size Wire     | 1 - #18 and 2 - #17     | 3 - #16     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 355.6 mm (14.0 inch)     |
436.9 mm (17.2 inch)     |
||
Copper Weight     | 6.4 kg (14.0 lb)     |
13.6 kg (29.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 762.0 mm (30.0 inch)     |
#10 304.8 mm (12.0 inch)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #38 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram C |
5N-7211 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 419.1 mm (16.5 inch)     |
431.8 mm (17.0 inch)     |
-     | |
Slots     | 72     | -     | -     | |
Coil Throw     | 1 - 10     | -     | -     | |
Turns/Coil     | 3     | -     | -     | |
Turns/Pole     | -     | 154.5     | -     | |
No. & Wire Size     | 14 - #13     | 1 - 3.3 mm x 6.4 mm (.13 inch x .25 inch)     |
-     | |
Mean Length Turn     | 1607.8 mm (63.3 inch)     |
-     | -     | |
Copper Weight     | 115.7 kg (255.0 lb)     |
220.3 kg (485.7 lb)     |
-     | |
Inside Connection (1)     | 6/3 Parallel Star     | 6 in Series     | -     | |
Line Leads (No. & Size)     | 30 - #1     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0126 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.046 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 80 Hz     | |||
Exciter Poles     | 8     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 8     | 48     | ||
Turns (Coils)     | 160     | 8     | ||
No. & Size Wire     | 1 - #18 and 2 - #17     | 3 - #16     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 355.6 mm (14.0 inch)     |
436.9 mm (17.2 inch)     |
||
Copper Weight     | 6.4 kg (14.0 lb)     |
13.6 kg (29.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 762.0 mm (30.0 inch)     |
#10 304.8 mm (12.0 inch)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #38 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram C |
5N-7212 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 487.7 mm (19.2 inch)     |
500.4 mm (19.7 inch)     |
-     | |
Slots     | 90     | -     | -     | |
Coil Throw     | 1 - 13     | -     | -     | |
Turns/Coil     | 3     | -     | -     | |
Turns/Pole     | -     | 154.5     | -     | |
No. & Wire Size     | 11 - #12     | 1 - 3.66 mm x 7.32 mm (.144 inch x .288 inch)     |
-     | |
Mean Length Turn     | 1981.2 mm (78.0 inch)     |
-     | -     | |
Copper Weight     | 192.5 kg (424.3 lb)     |
312.7 kg (689.3 lb)     |
-     | |
Inside Connection (1)     | 6/3 Parallel Star     | 6 in Series     | -     | |
Line Leads (No. & Size)     | 12 - #0000     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0049 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.866 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 80 Hz     | |||
Exciter Poles     | 8     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 8     | 48     | ||
Turns (Coils)     | 160     | 8     | ||
No. & Size Wire     | 1 - #18 and 2 - #17     | 3 - #16     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 355.6 mm (14.0 inch)     |
436.9 mm (17.2 inch)     |
||
Copper Weight     | 6.4 kg (14.0 lb)     |
13.6 kg (29.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 762.0 mm (30.0 inch)     |
#10 304.8 mm (12.0 inch)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #14 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram C |
5N-7213 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 487.7 mm (19.2 inch)     |
500.4 mm (19.7 inch)     |
-     | |
Slots     | 90     | -     | -     | |
Coil Throw     | 1 - 13     | -     | -     | |
Turns/Coil     | 3.8 (4,4,4,4,3)     | -     | -     | |
Turns/Pole     | -     | 154.5     | -     | |
No. & Wire Size     | 12 - #13     | 1 - 3.66 mm x 7.32 mm (.144 inch x .288 inch)     |
-     | |
Mean Length Turn     | 1981.2 mm (78.0 inch)     |
-     | -     | |
Copper Weight     | 193.3 kg (426.2 lb)     |
312.7 kg (689.3 lb)     |
-     | |
Inside Connection (1)     | 6/3 Parallel Star     | 6 in Series     | -     | |
Line Leads (No. & Size)     | 12 - #000     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0072 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.866 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 80 Hz     | |||
Exciter Poles     | 8     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 8     | 48     | ||
Turns (Coils)     | 160     | 8     | ||
No. & Size Wire     | 1 - #18 and 2 - #17     | 3 - #16     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 355.6 mm (14.0 inch)     |
436.9 mm (17.2 inch)     |
||
Copper Weight     | 6.4 kg (14.0 lb)     |
13.6 kg (29.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 762.0 mm (30.0 inch)     |
#10 304.8 mm (12.0 inch)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #14 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram C |
5N-7214 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 487.7 mm (19.2 inch)     |
500.4 mm (19.7 inch)     |
-     | |
Slots     | 90     | -     | -     | |
Coil Throw     | 1 - 13     | -     | -     | |
Turns/Coil     | 3     | -     | -     | |
Turns/Pole     | -     | 154.5     | -     | |
No. & Wire Size     | 11 - #12     | 1 - 3.66 mm x 7.32 mm (.144 inch x .288 inch)     |
-     | |
Mean Length Turn     | 1981.2 mm (78.0 inch)     |
-     | -     | |
Copper Weight     | 192.5 kg (424.3 lb)     |
312.7 kg (689.3 lb)     |
-     | |
Inside Connection (1)     | 6/3 Parallel Star     | 6 in Series     | -     | |
Line Leads (No. & Size)     | 12 - #0000     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     |
0.0049 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     |
-     | 0.866 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 80 Hz     | |||
Exciter Poles     | 8     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 8     | 48     | ||
Turns (Coils)     | 160     | 8     | ||
No. & Size Wire     | 1 - #18 and 2 - #17     | 3 - #16     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 355.6 mm (14.0 inch)     |
436.9 mm (17.2 inch)     |
||
Copper Weight     | 6.4 kg (14.0 lb)     |
13.6 kg (29.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 762.0 mm (30.0 inch)     |
#10 304.8 mm (12.0 inch)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #14 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram C |
5N-7215 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 487.7 mm (19.2 inch)     |
500.4 mm (19.7 inch)     |
-     | |
Slots     | 90     | -     | -     | |
Coil Throw     | 1 - 13     | -     | -     | |
Turns/Coil     | 3.8 (4,4,4,4,3)     | -     | -     | |
Turns/Pole     | -     | 154.5     | -     | |
No. & Wire Size     | 12 - #13     | 1 - 3.66 mm x 7.32 mm (.144 inch x .288 inch)     |
-     | |
Mean Length Turn     | 1981.2 mm (78.0 inch)     |
-     | -     | |
Copper Weight     | 193.3 kg (426.2 lb)     |
312.7 kg (689.3 lb)     |
-     | |
Inside Connection (1)     | 6/3 Parallel Star     | 6 in Series     | -     | |
Line Leads (No. & Size)     | 12 - #000     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     |
0.0072 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     |
-     | 0.866 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 80 Hz     | |||
Exciter Poles     | 8     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 8     | 48     | ||
Turns (Coils)     | 160     | 8     | ||
No. & Size Wire     | 1 - #18 and 2 - #17     | 3 - #16     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 355.6 mm (14.0 inch)     |
436.9 mm (17.2 inch)     |
||
Copper Weight     | 6.4 kg (14.0 lb)     |
13.6 kg (29.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 762.0 mm (30.0 inch)     |
#10 304.8 mm (12.0 inch)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #14 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram C |
5N-7216 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 386.1 mm (15.2 inch)     |
396.2 mm (15.6 inch)     |
396.2 mm (15.6 inch)     |
|
Slots     | 72     | -     | -     | |
Coil Throw     | 1 - 10     | -     | -     | |
Turns/Coil     | 3     | -     | -     | |
Turns/Pole     | -     | 110     | 128     | |
No. & Wire Size     | 9 - #13     | 4 - #12     | 1 - #7 sq     | |
Mean Length Turn     | 1419.9 mm (55.9 inch)     |
-     | -     | |
Copper Weight     | 65.6 kg (144.7 lb)     |
91.7 kg (202.1 lb)     |
105.9 kg (233.4 lb)     |
|
Inside Connection (1)     | 6/3 Parallel Star     | 6 in Series     | 6 in Series     | |
Line Leads (No. & Size)     | 30 - #4     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     |
0.0173 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     |
-     | 1.039 ohms     | 1.27 ohms     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 80 Hz     | |||
Exciter Poles     | 8     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 8     | 48     | ||
Turns (Coils)     | 160     | 8     | ||
No. & Size Wire     | 1 - #18 and 2 - #17     | 3 - #16     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 355.6 mm (14.0 inch)     |
436.9 mm (17.2 inch)     |
||
Copper Weight     | 6.4 kg (14.0 lb)     |
13.6 kg (29.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 762.0 mm (30.0 inch)     |
#10 304.8 mm (12.0 inch)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #38 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram C |
5N-7217 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 386.1 mm (15.2 inch)     |
396.2 mm (15.6 inch)     |
396.2 mm (15.6 inch)     |
|
Slots     | 72     | -     | -     | |
Coil Throw     | 1 - 10     | -     | -     | |
Turns/Coil     | 3.75 (3,4,4,4)     | -     | -     | |
Turns/Pole     | -     | 110     | 128     | |
No. & Wire Size     | 9 - #14     | 4 - #12     | 1 - #7 sq     | |
Mean Length Turn     | 1419.9 mm (55.9 inch)     |
-     | -     | |
Copper Weight     | 65.0 kg (143.4 lb)     |
91.7 kg (202.1 lb)     |
105.9 kg (233.4 lb)     |
|
Inside Connection (1)     | 6/3 Parallel Star     | 6 in Series     | 6 in Series     | |
Line Leads (No. & Size)     | 30 - #4     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0273 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.039 ohms     | 1.27 ohms     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 80 Hz     | |||
Exciter Poles     | 8     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 8     | 48     | ||
Turns (Coils)     | 160     | 8     | ||
No. & Size Wire     | 1 - #18 and 2 - #17     | 3 - #16     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 355.6 mm (14.0 inch)     |
436.9 mm (17.2 inch)     |
||
Copper Weight     | 6.4 kg (14.0 lb)     |
13.6 kg (29.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 762.0 mm (30.0 inch)     |
#10 304.8 mm (12.0 inch)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #17 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram C |
5N-7218 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 386.1 mm (15.2 inch)     |
396.2 mm (15.6 inch)     |
396.2 mm (15.6 inch)     |
|
Slots     | 72     | -     | -     | |
Coil Throw     | 1 - 10     | -     | -     | |
Turns/Coil     | 3     | -     | -     | |
Turns/Pole     | -     | 110     | 128     | |
No. & Wire Size     | 9 - #13     | 4 - #12     | 1 - #7 sq     | |
Mean Length Turn     | 1419.9 mm (55.9 inch)     |
-     | -     | |
Copper Weight     | 65.6 kg (144.7 lb)     |
91.7 kg (202.1 lb)     |
105.9 kg (233.4 lb)     |
|
Inside Connection (1)     | 6/3 Parallel Star     | 6 in Series     | 6 in Series     | |
Line Leads (No. & Size)     | 30 - #4     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0173 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.039 ohms     | 1.27 ohms     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 80 Hz     | |||
Exciter Poles     | 8     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 8     | 48     | ||
Turns (Coils)     | 160     | 8     | ||
No. & Size Wire     | 1 - #18 and 2 - #17     | 3 - #16     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 355.6 mm (14.0 inch)     |
436.9 mm (17.2 inch)     |
||
Copper Weight     | 6.4 kg (14.0 lb)     |
13.6 kg (29.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 762.0 mm (30.0 inch)     |
#10 304.8 mm (12.0 inch)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #38 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram C |
5N-7219 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 386.1 mm (15.2 inch)     |
396.2 mm (15.6 inch)     |
396.2 mm (15.6 inch)     |
|
Slots     | 72     | -     | -     | |
Coil Throw     | 1 - 10     | -     | -     | |
Turns/Coil     | 3.75 (3,4,4,4)     | -     | -     | |
Turns/Pole     | -     | 110     | 128     | |
No. & Wire Size     | 9 - #14     | 4 - #12     | 1 - #7 sq     | |
Mean Length Turn     | 1419.9 mm (55.9 inch)     |
-     | -     | |
Copper Weight     | 65.0 kg (143.4 lb)     |
91.7 kg (202.1 lb)     |
105.9 kg (233.4 lb)     |
|
Inside Connection (1)     | 6/3 Parallel Star     | 6 in Series     | 6 in Series     | |
Line Leads (No. & Size)     | 30 - #4     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0273 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.039 ohms     | 1.27 ohms     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 80 Hz     | |||
Exciter Poles     | 8     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 8     | 48     | ||
Turns (Coils)     | 160     | 8     | ||
No. & Size Wire     | 1 - #18 and 2 - #17     | 3 - #16     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 355.6 mm (14.0 inch)     |
436.9 mm (17.2 inch)     |
||
Copper Weight     | 6.4 kg (14.0 lb)     |
13.6 kg (29.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 762.0 mm (30.0 inch)     |
#10 304.8 mm (12.0 inch)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #17 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram C |
5N-7220 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 520.7 mm (20.5 inch)     |
538.5 mm (21.2 inch)     |
-     | |
Slots     | 72     | -     | -     | |
Coil Throw     | 1 - 14     | -     | -     | |
Turns/Coil     | 1.5(1,2,1,2,1,2)     | -     | -     | |
Turns/Pole     | -     | 174     | -     | |
No. & Wire Size     | 18 - #12     | 1 - 3.66 mm x 7.32 mm (.144 inch x .288 inch)     |
-     | |
Mean Length Turn     | 2075.2 mm (81.7 inch)     |
-     | -     | |
Copper Weight     | 122.9 kg (270.9 lb)     |
275.5 kg (607.4 lb)     |
-     | |
Inside Connection (1)     | 4 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 16 - #0000     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0028 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.795 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 120 Hz     | |||
Exciter Poles     | 8     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 63.5 mm (2.5 inch)     |
63.5 mm (2.5 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 8     | 48     | ||
Turns (Coils)     | 160     | 7     | ||
No. & Size Wire     | 2 - #16.5     | 3 - #15     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 330.2 mm (13.0 inch)     |
386.1 mm (15.2 inch)     |
||
Copper Weight     | 10.0 kg (22.1 lb)     |
6.2 kg (13.7 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 3048.0 mm (120.0 inch)     |
#10 304.8 mm (12.0 inch)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #10 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram C |
5N-7221 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 520.7 mm (20.5 inch)     |
538.5 mm (21.2 inch)     |
-     | |
Slots     | 72     | -     | -     | |
Coil Throw     | 1 - 14     | -     | -     | |
Turns/Coil     | 2     | -     | -     | |
Turns/Pole     | -     | 174     | -     | |
No. & Wire Size     | 14 - #12     | 1 - 3.66 mm x 7.32 mm (.144 inch x .288 inch)     |
-     | |
Mean Length Turn     | 2075.2 mm (81.7 inch)     |
-     | -     | |
Copper Weight     | 127.5 kg (281.0 lb)     |
275.5 kg (607.4 lb)     |
-     | |
Inside Connection (1)     | 4 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 16 - #00     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0048 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.795 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 120 Hz     | |||
Exciter Poles     | 8     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 63.5 mm (2.5 inch)     |
63.5 mm (2.5 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 8     | 48     | ||
Turns (Coils)     | 160     | 7     | ||
No. & Size Wire     | 2 - #16.5     | 3 - #15     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 330.2 mm (13.0 inch)     |
386.1 mm (15.2 inch)     |
||
Copper Weight     | 10.0 kg (22.1 lb)     |
6.2 kg (13.7 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 3048.0 mm (120.0 inch)     |
#10 304.8 mm (12.0 inch)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #10 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram C |
5N-7222 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 520.7 mm (20.5 inch)     |
538.5 mm (21.2 inch)     |
-     | |
Slots     | 72     | -     | -     | |
Coil Throw     | 1 - 14     | -     | -     | |
Turns/Coil     | 1.5(1,2,1,2,1,2)     | -     | -     | |
Turns/Pole     | -     | 174     | -     | |
No. & Wire Size     | 18 - #12     | 1 - 3.66 mm x 7.32 mm (.144 inch x .288 inch)     |
-     | |
Mean Length Turn     | 2075.2 mm (81.7 inch)     |
-     | -     | |
Copper Weight     | 122.9 kg (270.9 lb)     |
275.5 kg (607.4 lb)     |
-     | |
Inside Connection (1)     | 4 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 16 - #0000     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0028 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.795 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 120 Hz     | |||
Exciter Poles     | 8     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 63.5 mm (2.5 inch)     |
63.5 mm (2.5 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 8     | 48     | ||
Turns (Coils)     | 160     | 7     | ||
No. & Size Wire     | 2 - #16.5     | 3 - #15     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 330.2 mm (13.0 inch)     |
386.1 mm (15.2 inch)     |
||
Copper Weight     | 10.0 kg (22.1 lb)     |
6.2 kg (13.7 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 3048.0 mm (120.0 inch)     |
#10 304.8 mm (12.0 inch)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #10 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram C |
5N-7223 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 520.7 mm (20.5 inch)     |
538.5 mm (21.2 inch)     |
-     | |
Slots     | 72     | -     | -     | |
Coil Throw     | 1 - 14     | -     | -     | |
Turns/Coil     | 2     | -     | -     | |
Turns/Pole     | -     | 174     | -     | |
No. & Wire Size     | 14 - #12     | 1 - 3.66 mm x 7.32 mm (.144 inch x .288 inch)     |
-     | |
Mean Length Turn     | 2075.2 mm (81.7 inch)     |
-     | -     | |
Copper Weight     | 127.5 kg (281.0 lb)     |
275.5 kg (607.4 lb)     |
-     | |
Inside Connection (1)     | 4 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 16 - #00     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0048 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.795 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 120 Hz     | |||
Exciter Poles     | 8     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 63.5 mm (2.5 inch)     |
63.5 mm (2.5 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 8     | 48     | ||
Turns (Coils)     | 160     | 7     | ||
No. & Size Wire     | 2 - #16.5     | 3 - #15     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 330.2 mm (13.0 inch)     |
386.1 mm (15.2 inch)     |
||
Copper Weight     | 10.0 kg (22.1 lb)     |
6.2 kg (13.7 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 3048.0 mm (120.0 inch)     |
#10 304.8 mm (12.0 inch)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #10 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram C |
5N-7224 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 342.9 mm (13.5 inch)     |
355.6 mm (14.0 inch)     |
-     | |
Slots     | 96     | -     | -     | |
Coil Throw     | 1 - 19     | -     | -     | |
Turns/Coil     | 1     | -     | -     | |
Turns/Pole     | -     | 203     | -     | |
No. & Wire Size     | 22 - #13     | 1 - #6 sq     | -     | |
Mean Length Turn     | 1742.4 mm (68.6 inch)     |
-     | -     | |
Copper Weight     | 90.5 kg (199.5 lb)     |
144.2 kg (317.8 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 40 - #2     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0087 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.08 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 120 Hz     | |||
Exciter Poles     | 8     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 63.5 mm (2.5 inch)     |
63.5 mm (2.5 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 8     | 48     | ||
Turns (Coils)     | 160     | 7     | ||
No. & Size Wire     | 2 - #16.5     | 3 - #15     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 330.2 mm (13.0 inch)     |
386.1 mm (15.2 inch)     |
||
Copper Weight     | 10.0 kg (22.1 lb)     |
6.2 kg (13.7 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 3048.0 mm (120.0 inch)     |
#10 304.8 mm (12.0 inch)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #07 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram C |
5N-7225 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 342.9 mm (13.5 inch)     |
355.6 mm (14.0 inch)     |
-     | |
Slots     | 84     | -     | -     | |
Coil Throw     | 1 - 18     | -     | -     | |
Turns/Coil     | 1.43 (1,1,2,2,2,1,1)     | -     | -     | |
Turns/Pole     | -     | 203     | -     | |
No. & Wire Size     | 20 - #14     | 1 - #6 sq     | -     | |
Mean Length Turn     | 1757.7 mm (69.2 inch)     |
-     | -     | |
Copper Weight     | 86.7 kg (191.2 lb)     |
144.2 kg (317.8 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 20 - #00     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0041 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.08 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 120 Hz     | |||
Exciter Poles     | 8     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 63.5 mm (2.5 inch)     |
63.5 mm (2.5 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 8     | 48     | ||
Turns (Coils)     | 160     | 7     | ||
No. & Size Wire     | 2 - #16.5     | 3 - #15     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 330.2 mm (13.0 inch)     |
386.1 mm (15.2 inch)     |
||
Copper Weight     | 10.0 kg (22.1 lb)     |
6.2 kg (13.7 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 3048.0 mm (120.0 inch)     |
#10 304.8 mm (12.0 inch)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #57 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram C |
5N-7226 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 342.9 mm (13.5 inch)     |
355.6 mm (14.0 inch)     |
-     | |
Slots     | 96     | -     | -     | |
Coil Throw     | 1 - 19     | -     | -     | |
Turns/Coil     | 1     | -     | -     | |
Turns/Pole     | -     | 203     | -     | |
No. & Wire Size     | 22 - #13     | 1 - #6 sq     | -     | |
Mean Length Turn     | 1742.4 mm (68.6 inch)     |
-     | -     | |
Copper Weight     | 90.5 kg (199.5 lb)     |
144.2 kg (317.8 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 40 - #2     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0087 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.08 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 120 Hz     | |||
Exciter Poles     | 8     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 63.5 mm (2.5 inch)     |
63.5 mm (2.5 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 8     | 48     | ||
Turns (Coils)     | 160     | 7     | ||
No. & Size Wire     | 2 - #16.5     | 3 - #15     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 330.2 mm (13.0 inch)     |
386.1 mm (15.2 inch)     |
||
Copper Weight     | 10.0 kg (22.1 lb)     |
6.2 kg (13.7 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 3048.0 mm (120.0 inch)     |
#10 304.8 mm (12.0 inch)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #07 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram C |
5N-7227 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 342.9 mm (13.5 inch)     |
355.6 mm (14.0 inch)     |
-     | |
Slots     | 84     | -     | -     | |
Coil Throw     | 1 - 18     | -     | -     | |
Turns/Coil     | 1.43 (1,1,2,2,2,1,1)     | -     | -     | |
Turns/Pole     | -     | 203     | -     | |
No. & Wire Size     | 20 - #14     | 1 - #6 sq     | -     | |
Mean Length Turn     | 1757.7 mm (69.2 inch)     |
-     | -     | |
Copper Weight     | 86.7 kg (191.2 lb)     |
144.2 kg (317.8 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 20 - #00     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0041 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.08 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 120 Hz     | |||
Exciter Poles     | 8     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 63.5 mm (2.5 inch)     |
63.5 mm (2.5 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 8     | 48     | ||
Turns (Coils)     | 160     | 7     | ||
No. & Size Wire     | 2 - #16.5     | 3 - #15     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 330.2 mm (13.0 inch)     |
386.1 mm (15.2 inch)     |
||
Copper Weight     | 10.0 kg (22.1 lb)     |
6.2 kg (13.7 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 3048.0 mm (120.0 inch)     |
#10 304.8 mm (12.0 inch)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #57 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram C |
5N-7228 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 292.1 mm (11.5 inch)     |
304.8 mm (12.0 inch)     |
-     | |
Slots     | 72     | -     | -     | |
Coil Throw     | 1 - 11     | -     | -     | |
Turns/Coil     | 3.25 (3,3,3,4)     | -     | -     | |
Turns/Pole     | -     | 154.5     | -     | |
No. & Wire Size     | 12 - #13     | 1 - 3.3 mm x 6.4 mm (.13 inch x .25 inch)     |
-     | |
Mean Length Turn     | 1422.4 mm (56.0 inch)     |
-     | -     | |
Copper Weight     | 95.1 kg (209.6 lb)     |
176.8 kg (389.8 lb)     |
-     | |
Inside Connection (1)     | 6/3 Parallel Star     | 6 in Series     | -     | |
Line Leads (No. & Size)     | 30 - #1     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0141 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.839 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 80 Hz     | |||
Exciter Poles     | 8     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 8     | 48     | ||
Turns (Coils)     | 160     | 8     | ||
No. & Size Wire     | 1 - #18 and 2 - #17     | 3 - #16     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 355.6 mm (14.0 inch)     |
436.9 mm (17.2 inch)     |
||
Copper Weight     | 6.4 kg (14.0 lb)     |
13.6 kg (29.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 762.0 mm (30.0 inch)     |
#10 304.8 mm (12.0 inch)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #38 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram C |
5N-7229 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 292.1 mm (11.5 inch)     |
304.8 mm (12.0 inch)     |
-     | |
Slots     | 72     | -     | -     | |
Coil Throw     | 1 - 11     | -     | -     | |
Turns/Coil     | 4     | -     | -     | |
Turns/Pole     | -     | 154.5     | -     | |
No. & Wire Size     | 12 - #14     | 1 - 3.3 mm x 6.4 mm (.13 inch x .25 inch)     |
-     | |
Mean Length Turn     | 1422.4 mm (56.0 inch)     |
-     | -     | |
Copper Weight     | 92.8 kg (204.6 lb)     |
176.8 kg (389.8 lb)     |
-     | |
Inside Connection (1)     | 6/3 Parallel Star     | 6 in Series     | -     | |
Line Leads (No. & Size)     | 30 - #2     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0219 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.839 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 80 Hz     | |||
Exciter Poles     | 8     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 8     | 48     | ||
Turns (Coils)     | 160     | 8     | ||
No. & Size Wire     | 1 - #18 and 2 - #17     | 3 - #16     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 355.6 mm (14.0 inch)     |
436.9 mm (17.2 inch)     |
||
Copper Weight     | 6.4 kg (14.0 lb)     |
13.6 kg (29.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 762.0 mm (30.0 inch)     |
#10 304.8 mm (12.0 inch)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #38 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram C |
5N-7230 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 292.1 mm (11.5 inch)     |
304.8 mm (12.0 inch)     |
-     | |
Slots     | 72     | -     | -     | |
Coil Throw     | 1 - 11     | -     | -     | |
Turns/Coil     | 3.25 (3,3,3,4)     | -     | -     | |
Turns/Pole     | -     | 154.5     | -     | |
No. & Wire Size     | 12 - #13     | 1 - 3.3 mm x 6.4 mm (.13 inch x .25 inch)     |
-     | |
Mean Length Turn     | 1422.4 mm (56.0 inch)     |
-     | -     | |
Copper Weight     | 95.1 kg (209.6 lb)     |
176.8 kg (389.8 lb)     |
-     | |
Inside Connection (1)     | 6/3 Parallel Star     | 6 in Series     | -     | |
Line Leads (No. & Size)     | 30 - #1     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0141 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.839 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 80 Hz     | |||
Exciter Poles     | 8     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 8     | 48     | ||
Turns (Coils)     | 160     | 8     | ||
No. & Size Wire     | 1 - #18 and 2 - #17     | 3 - #16     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 355.6 mm (14.0 inch)     |
436.9 mm (17.2 inch)     |
||
Copper Weight     | 6.4 kg (14.0 lb)     |
13.6 kg (29.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 762.0 mm (30.0 inch)     |
#10 304.8 mm (12.0 inch)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #38 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram C |
5N-7231 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 292.1 mm (11.5 inch)     |
304.8 mm (12.0 inch)     |
-     | |
Slots     | 72     | -     | -     | |
Coil Throw     | 1 - 11     | -     | -     | |
Turns/Coil     | 4     | -     | -     | |
Turns/Pole     | -     | 154.5     | -     | |
No. & Wire Size     | 12 - #14     | 1 - 3.3 mm x 6.4 mm (.13 inch x .25 inch)     |
-     | |
Mean Length Turn     | 1422.4 mm (56.0 inch)     |
-     | -     | |
Copper Weight     | 92.8 kg (204.6 lb)     |
176.8 kg (389.8 lb)     |
-     | |
Inside Connection (1)     | 6/3 Parallel Star     | 6 in Series     | -     | |
Line Leads (No. & Size)     | 30 - #2     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0219 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.839 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 80 Hz     | |||
Exciter Poles     | 8     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 8     | 48     | ||
Turns (Coils)     | 160     | 8     | ||
No. & Size Wire     | 1 - #18 and 2 - #17     | 3 - #16     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 355.6 mm (14.0 inch)     |
436.9 mm (17.2 inch)     |
||
Copper Weight     | 6.4 kg (14.0 lb)     |
13.6 kg (29.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 762.0 mm (30.0 inch)     |
#10 304.8 mm (12.0 inch)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #38 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram C |
5N-7232 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 584.2 mm (23.0 inch)     |
596.9 mm (23.5 inch)     |
-     | |
Slots     | 72     | -     | -     | |
Coil Throw     | 1 - 10     | -     | -     | |
Turns/Coil     | 3     | -     | -     | |
Turns/Pole     | -     | 147.5     | -     | |
No. & Wire Size     | 11 - #12     | 1 - 3.66 mm x 7.32 mm (.144 inch x .288 inch)     |
-     | |
Mean Length Turn     | 2001.5 mm (78.8 inch)     |
-     | -     | |
Copper Weight     | 140.9 kg (310.8 lb)     |
348.7 kg (768.7 lb)     |
-     | |
Inside Connection (1)     | 6/3 Parallel Star     | 6 in Series     | -     | |
Line Leads (No. & Size)     | 12 - #0000     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.004 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.98 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 80 Hz     | |||
Exciter Poles     | 8     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 8     | 48     | ||
Turns (Coils)     | 160     | 8     | ||
No. & Size Wire     | 1 - #18 and 2 - #17     | 3 - #16     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 355.6 mm (14.0 inch)     |
436.9 mm (17.2 inch)     |
||
Copper Weight     | 6.4 kg (14.0 lb)     |
13.6 kg (29.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 762.0 mm (30.0 inch)     |
#10 304.8 mm (12.0 inch)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #38 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram C |
Caterpillar Information System:
3034 Engine for Caterpillar Built Machines Inlet and Exhaust Valve Guides - Remove and Install
3114, 3116, and 3126 Engines Gear Group (Front) - Time
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for <B>129-1502</B> Generator through <B>129-5034</B> Generator
TK711, TK721, TK722 and TK732 Track Feller Bunchers Crushing Prevention and Cutting Prevention
2000/04/01 New Expansion Tank is now Available {1354}
2000/05/01 Check The Fuel Injection Control Linkage For A Loose Rivet {1298}
2001/05/01 Image Gallery CD-ROM Is Now Available For The Caterpillar HEUI HI300 And EUI Fuel Systems {1250}
2000/04/01 Image Gallery CD-ROM Is Now Available For The Caterpillar HEUI HI300 And EUI Fuel Systems {1250}
3114, 3116, and 3126 Engines Unit Injector Synchronization - Adjust
Connection Diagrams: SR4 and SR4B Generators, Voltage Regulators, Options Selection Guide for Voltage Regulator (SR4B for 3500 Engines)
325, 325B and 325L Excavators Final Drive Oil Sample - Obtain
2000/04/01 New Turbocharger Compressor Cover is now Available {1052}
325, 325B and 325L Excavators Final Drive
3034 Engine for Caterpillar Built Machines Inlet and Exhaust Valve Seat Inserts - Remove and Install
3114, 3116, and 3126 Engines for Caterpillar Built Machines Inlet Manifold - Remove
3114, 3116, and 3126 Engines for Caterpillar Built Machines Inlet Manifold - Install
325, 325B and 325L Excavators Final Drive
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for <B>5N-7233</B> Generator through <B>5N-7309</B> Generator
3500B Engines for Caterpillar Built Power Modules with the ADEM 3 Electronic Control Module System Overview
2000/09/11 Use 159-9404 Counterbore Tool Group In Order to Bore Cylinder Block {0705, 1000}
C-10 and C-12 Industrial Engines Piston and Rings
2000/05/01 Check The Fuel Injection Control Linkage For A Loose Rivet {1298}
C-10, C-12, 3406E, C-15, C-16 and C-18 Engines - Electronic PTO Installation and Application PTO Shutdown Timer - Test
TK711, TK721, TK722 and TK732 Track Feller Bunchers Burn Prevention