SR4 and SR4B Electric Power Generation Rewind Data Caterpillar


Winding Data for 5N-0431 Generator through 5N-7207 Generator

Usage:

SR4B 1BN

5N-0431 Generator

Table 1
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR
(RANDOM WOUND)    
ROTOR
(FORM WOUND)    
Stack Height    
736.6 mm (29.0 inch)    

749.3 mm (29.5 inch)    
-    
Slots     90     -     -    
Coil Throw     1 - 12     -     -    
Turns/Coil     2     -     -    
Turns/Pole     -     147.5     -    
No. & Wire Size     14 - #12    
1 - 3.66 mm x 7.32 mm (.144 inch x .288 inch)    
-    
Mean Length Turn    
2336.8 mm (92.0 inch)    
-     -    
Copper Weight    
179.9 kg (396.7 lb)    

419.6 kg (925.1 lb)    
-    
Inside Connection (1)     6 Parallel Star     6 in Series     -    
Line Leads (No. & Size)     24 - #1     -     -    
Terminal bolt size     3/8 inch     -     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.0043 ohms     -     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.162 ohms     -    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     80 Hz    
Exciter Poles     8    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)    
Stack Length    
88.9 mm (3.5 inch)    

88.9 mm (3.5 inch)    
Coils/Group     1     2    
Slots (Coils)     8     48    
Turns (Coils)     160     8    
No. & Size Wire     1 - #18 and 2 - #17     3 - #16    
Coil Throw     1 - 2     1 - 6    
Mean Length Turn (Calc.)    
355.6 mm (14.0 inch)    

436.9 mm (17.2 inch)    
Copper Weight    
6.4 kg (14.0 lb)    

13.6 kg (29.9 lb)    
Insulation     Heavy Nytherm    
Connection (2)     Series     2 Parallel Star    
Line Leads     #14

762.0 mm (30.0 inch)    
#10

304.8 mm (12.0 inch)    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #40
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram C

5N-4999 Generator

Table 2
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR
(RANDOM WOUND)    
ROTOR
(FORM WOUND)    
Stack Height    
381.0 mm (15.0 inch)    

381.0 mm (15.0 inch)    
-    
Slots     60     -     -    
Coil Throw     1 - 14     -     -    
Turns/Coil     2     -     -    
Turns/Pole     -     110     -    
No. & Wire Size     14 - #14     1 - #7     -    
Mean Length Turn    
1503.7 mm (59.2 inch)    
-     -    
Copper Weight    
49.2 kg (108.5 lb)    

49.1 kg (108.3 lb)    
-    
Inside Connection (1)     4/2 Parallel Star     4 in Series     -    
Line Leads (No. & Size)     20 - #2     -     -    
Terminal bolt size     3/8 inch     -     -    
Low Voltage connected line
resistance at 25 ° C (77 ° F)    
0.0048 ohms     -     -    
Field lead resistance at
25 ° C (77 ° F)    
-     0.895 ohms     -    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)    
Stack Length    
101.6 mm (4.0 inch)    

101.6 mm (4.0 inch)    
Coils/Group     1     2    
Slots (Coils)     6     36    
Turns (Coils)     140     6    
No. & Size Wire     1 - #15.5     2 - #15    
Coil Throw     1 - 2     1 - 6    
Mean Length Turn (Calc.)    
414.0 mm (16.3 inch)    

355.6 mm (14.0 inch)    
Copper Weight    
4.7 kg (10.3 lb)    

2.2 kg (4.9 lb)    
Insulation     Heavy Nytherm    
Connection (2)     Series     2 Parallel Star    
Line Leads     #14

965.2 mm (38.0 inch)    
#10

114.3 mm (4.5 inch)    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #01
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram A

5N-5000 Generator

Table 3
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR
(RANDOM WOUND)    
ROTOR
(FORM WOUND)    
Stack Height    
381.0 mm (15.0 inch)    

381.0 mm (15.0 inch)    
-    
Slots     60     -     -    
Coil Throw     1 - 13     -     -    
Turns/Coil     2.6(2,2,3,3,3)     -     -    
Turns/Pole     -     110     -    
No. & Wire Size     13 - #15     1 - #7     -    
Mean Length Turn    
1452.9 mm (57.2 inch)    
-     -    
Copper Weight    
45.5 kg (100.4 lb)    

49.1 kg (108.3 lb)    
-    
Inside Connection (1)     4/2 Parallel Star     4 in Series     -    
Line Leads (No. & Size)     20 - #4     -     -    
Terminal bolt size     3/8 inch     -     -    
Low Voltage connected line
resistance at 25 ° C (77 ° F)    
0.0081 ohms     -     -    
Field lead resistance at
25 ° C (77 ° F)    
-     0.895 ohms     -    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)    
Stack Length    
101.6 mm (4.0 inch)    

101.6 mm (4.0 inch)    
Coils/Group     1     2    
Slots (Coils)     6     36    
Turns (Coils)     140     6    
No. & Size Wire     1 - #15.5     2 - #15    
Coil Throw     1 - 2     1 - 6    
Mean Length Turn (Calc.)    
414.0 mm (16.3 inch)    

355.6 mm (14.0 inch)    
Copper Weight    
4.7 kg (10.3 lb)    

2.2 kg (4.9 lb)    
Insulation     Heavy Nytherm    
Connection (2)     Series     2 Parallel Star    
Line Leads     #14

965.2 mm (38.0 inch)    
#10

114.3 mm (4.5 inch)    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #13
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram A

Note: Wires 20, 22, and 24 are brought out as tap connections between the 4th and 5th coil (14 turns from T0).

5N-5001 Generator

Table 4
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR
(RANDOM WOUND)    
ROTOR
(FORM WOUND)    
Stack Height    
381.0 mm (15.0 inch)    

381.0 mm (15.0 inch)    
-    
Slots     60     -     -    
Coil Throw     1 - 14     -     -    
Turns/Coil     2     -     -    
Turns/Pole     -     110     -    
No. & Wire Size     14 - #14     1 - #7     -    
Mean Length Turn    
1503.7 mm (59.2 inch)    
-     -    
Copper Weight    
49.2 kg (108.5 lb)    

49.1 kg (108.3 lb)    
-    
Inside Connection (1)     4/2 Parallel Star     4 in Series     -    
Line Leads (No. & Size)     20 - #2     -     -    
Terminal bolt size     3/8 inch     -     -    
Low Voltage connected line
resistance at 25 ° C (77 ° F)    
0.0048 ohms     -     -    
Field lead resistance at
25 ° C (77 ° F)    
-     0.895 ohms     -    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)    
Stack Length    
101.6 mm (4.0 inch)    

101.6 mm (4.0 inch)    
Coils/Group     1     2    
Slots (Coils)     6     36    
Turns (Coils)     140     6    
No. & Size Wire     1 - #15.5     2 - #15    
Coil Throw     1 - 2     1 - 6    
Mean Length Turn (Calc.)    
414.0 mm (16.3 inch)    

355.6 mm (14.0 inch)    
Copper Weight    
4.7 kg (10.3 lb)    

2.2 kg (4.9 lb)    
Insulation     Heavy Nytherm    
Connection (2)     Series     2 Parallel Star    
Line Leads     #14

965.2 mm (38.0 inch)    
#10

114.3 mm (4.5 inch)    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #01
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram A

5N-5005 Generator

Table 5
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR
(RANDOM WOUND)    
ROTOR
(FORM WOUND)    
Stack Height    
406.4 mm (16.0 inch)    

424.2 mm (16.7 inch)    
-    
Slots     72     -     -    
Coil Throw     1 - 15     -     -    
Turns/Coil     2     -     -    
Turns/Pole     -     174     -    
No. & Wire Size     14 - #12    
1 - 3.66 mm x 7.32 mm (.144 inch x .288 inch)    
-    
Mean Length Turn    
1915.2 mm (75.4 inch)    
-     -    
Copper Weight    
115.8 kg (255.2 lb)    

237.7 kg (524.0 lb)    
-    
Inside Connection (1)     4 Parallel Star     4 in Series     -    
Line Leads (No. & Size)     16 - #00     -     -    
Terminal bolt size     3/8 inch     -     -    
Low Voltage connected line
resistance at 25 ° C (77 ° F)    
0.0045 ohms     -     -    
Field lead resistance at
25 ° C (77 ° F)    
-     0.686 ohms     -    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     120 Hz    
Exciter Poles     8    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)    
Stack Length    
63.5 mm (2.5 inch)    

63.5 mm (2.5 inch)    
Coils/Group     1     2    
Slots (Coils)     8     48    
Turns (Coils)     160     7    
No. & Size Wire     2 - #16.5     3 - #15    
Coil Throw     1 - 2     1 - 6    
Mean Length Turn (Calc.)    
330.2 mm (13.0 inch)    

386.1 mm (15.2 inch)    
Copper Weight    
10.0 kg (22.1 lb)    

6.2 kg (13.7 lb)    
Insulation     Heavy Nytherm    
Connection (2)     Series     2 Parallel Star    
Line Leads     #14

3048.0 mm (120.0 inch)    
#10

304.8 mm (12.0 inch)    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #10
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram C

5N-5006 Generator

Table 6
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR
(RANDOM WOUND)    
ROTOR
(FORM WOUND)    
Stack Height    
406.4 mm (16.0 inch)    

424.2 mm (16.7 inch)    
-    
Slots     72     -     -    
Coil Throw     1 - 14     -     -    
Turns/Coil     2.5(2,3,2,3,2,3)     -     -    
Turns/Pole     -     174     -    
No. & Wire Size     14 - #13    
1 - 3.66 mm x 7.32 mm (.144 inch x .288 inch)    
-    
Mean Length Turn    
1846.6 mm (72.7 inch)    
-     -    
Copper Weight    
110.6 kg (243.9 lb)    

237.7 kg (524.0 lb)    
-    
Inside Connection (1)     4 Parallel Star     4 in Series     -    
Line Leads (No. & Size)     16 - #1     -     -    
Terminal bolt size     3/8 inch     -     -    
Low Voltage connected line
resistance at 25 ° C (77 ° F)    
0.0068 ohms     -     -    
Field lead resistance at
25 ° C (77 ° F)    
-     0.686 ohms     -    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     120 Hz    
Exciter Poles     8    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)    
Stack Length    
63.5 mm (2.5 inch)    

63.5 mm (2.5 inch)    
Coils/Group     1     2    
Slots (Coils)     8     48    
Turns (Coils)     160     7    
No. & Size Wire     2 - #16.5     3 - #15    
Coil Throw     1 - 2     1 - 6    
Mean Length Turn (Calc.)    
330.2 mm (13.0 inch)    

386.1 mm (15.2 inch)    
Copper Weight    
10.0 kg (22.1 lb)    

6.2 kg (13.7 lb)    
Insulation     Heavy Nytherm    
Connection (2)     Series     2 Parallel Star    
Line Leads     #14

3048.0 mm (120.0 inch)    
#10

304.8 mm (12.0 inch)    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #10
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram C

5N-5007 Generator

Table 7
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR
(RANDOM WOUND)    
ROTOR
(FORM WOUND)    
Stack Height    
406.4 mm (16.0 inch)    

424.2 mm (16.7 inch)    
-    
Slots     72     -     -    
Coil Throw     1 - 15     -     -    
Turns/Coil     2     -     -    
Turns/Pole     -     174     -    
No. & Wire Size     14 - #12    
1 - 3.66 mm x 7.32 mm (.144 inch x .288 inch)    
-    
Mean Length Turn    
1915.2 mm (75.4 inch)    
-     -    
Copper Weight    
115.8 kg (255.2 lb)    

237.7 kg (524 lb)    
-    
Inside Connection (1)     4 Parallel Star     4 in Series     -    
Line Leads (No. & Size)     16 - #00     -     -    
Terminal bolt size     3/8 inch     -     -    
Low Voltage connected line
resistance at 25 ° C (77 ° F)    
0.0045 ohms     -     -    
Field lead resistance at
25 ° C (77 ° F)    
-     0.686 ohms     -    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     120 Hz    
Exciter Poles     8    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)    
Stack Length    
63.5 mm (2.5 inch)    

63.5 mm (2.5 inch)    
Coils/Group     1     2    
Slots (Coils)     8     48    
Turns (Coils)     160     7    
No. & Size Wire     2 - #16.5     3 - #15    
Coil Throw     1 - 2     1 - 6    
Mean Length Turn (Calc.)    
330.2 mm (13.0 inch)    

386.1 mm (15.2 inch)    
Copper Weight    
10.0 kg (22.1 lb)    

6.2 kg (13.7 lb)    
Insulation     Heavy Nytherm    
Connection (2)     Series     2 Parallel Star    
Line Leads     #14

3048.0 mm (120.0 inch)    
#10

304.8 mm (12.0 inch)    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #10
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram C

5N-5008 Generator

Table 8
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR
(RANDOM WOUND)    
ROTOR
(FORM WOUND)    
Stack Height    
406.4 mm (16.0 inch)    

424.2 mm (16.7 inch)    
-    
Slots     72     -     -    
Coil Throw     1 - 14     -     -    
Turns/Coil     2.5(2,3,2,3,2,3)     -     -    
Turns/Pole     -     174     -    
No. & Wire Size     14 - #13    
1 - 3.66 mm x 7.32 mm (.144 inch x .288 inch)    
-    
Mean Length Turn    
1846.6 mm (72.7 inch)    
-     -    
Copper Weight    
110.6 kg (243.9 lb)    

237.7 kg (524.0 lb)    
-    
Inside Connection (1)     4 Parallel Star     4 in Series     -    
Line Leads (No. & Size)     16 - #1     -     -    
Terminal bolt size     3/8 inch     -     -    
Low Voltage connected line
resistance at 25 ° C (77 ° F)    
0.0068 ohms     -     -    
Field lead resistance at
25 ° C (77 ° F)    
-     0.686 ohms     -    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     120 Hz    
Exciter Poles     8    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)    
Stack Length    
63.5 mm (2.5 inch)    

63.5 mm (2.5 inch)    
Coils/Group     1     2    
Slots (Coils)     8     48    
Turns (Coils)     160     7    
No. & Size Wire     2 - #16.5     3 - #15    
Coil Throw     1 - 2     1 - 6    
Mean Length Turn (Calc.)    
330.2 mm (13.0 inch)    

386.1 mm (15.2 inch)    
Copper Weight    
10.0 kg (22.1 lb)    

6.2 kg (13.7 lb)    
Insulation     Heavy Nytherm    
Connection (2)     Series     2 Parallel Star    
Line Leads     #14

3048.0 mm (120.0 inch)    
#10

304.8 mm (12.0 inch)    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #10
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram C

5N-5026 Generator

Table 9
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR
(RANDOM WOUND)    
ROTOR
(FORM WOUND)    
Stack Height    
424.2 mm (16.7 inch)    

431.8 mm (17.0 inch)    
-    
Slots     84     -     -    
Coil Throw     1 - 19     -     -    
Turns/Coil     1     -     -    
Turns/Pole     -     160     -    
No. & Wire Size     18 - #13     1 - #7 sq     -    
Mean Length Turn    
1724.7 mm (67.9 inch)    
-     -    
Copper Weight    
63.5 kg (139.9 lb)    

98.5 kg (217.1 lb)    
-    
Inside Connection (1)     4/2 Parallel Star     4 in Series     -    
Line Leads (No. & Size)     20 - #000     -     -    
Terminal bolt size     3/8 inch     -     -    
Low Voltage connected line
resistance at 25 ° C (77 ° F)    
0.0023 ohms     -     -    
Field lead resistance at
25 ° C (77 ° F)    
-     1.17 ohms     -    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)    
Stack Length    
127.0 mm (5.0 inch)    

127.0 mm (5.0 inch)    
Coils/Group     1     2    
Slots (Coils)     6     36    
Turns (Coils)     125     6    
No. & Size Wire     1 - #15     2 - #15    
Coil Throw     1 - 2     1 - 6    
Mean Length Turn (Calc.)    
464.8 mm (18.3 inch)    

406.4 mm (16.0 inch)    
Copper Weight    
5.2 kg (11.5 lb)    

2.7 kg (5.9 lb)    
Insulation     Heavy Nytherm    
Connection (2)     Series     2 Parallel Star    
Line Leads     #14

965.2 mm (38.0 inch)    
#10

152.4 mm (6.0 inch)    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #01
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram A

5N-7064 Generator

Table 10
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR
(RANDOM WOUND)    
ROTOR
(FORM WOUND)    
Stack Height    
215.9 mm (8.5 inch)    

215.9 mm (8.5 inch)    
-    
Slots     60     -     -    
Coil Throw     1 - 12     -     -    
Turns/Coil     3     -     -    
Turns/Pole     -     160     -    
No. & Wire Size     9 - #13     1 - #7 sq     -    
Mean Length Turn    
1214.1 mm (47.8 inch)    
-     -    
Copper Weight    
46.7 kg (103.0 lb)    

69.3 kg (152.7 lb)    
-    
Inside Connection (1)     4/2 Parallel Star     4 in Series     -    
Line Leads (No. & Size)     20 - #1     -     -    
Terminal bolt size     3/8 inch     -     -    
Low Voltage connected line
resistance at 25 ° C (77 ° F)    
0.0278 ohms     -     -    
Field lead resistance at
25 ° C (77 ° F)    
-     0.829 ohms     -    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)    
Stack Length    
101.6 mm (4.0 inch)    

101.6 mm (4.0 inch)    
Coils/Group     1     2    
Slots (Coils)     6     36    
Turns (Coils)     140     6    
No. & Size Wire     1 - #15.5     2 - #15    
Coil Throw     1 - 2     1 - 6    
Mean Length Turn (Calc.)    
414.0 mm (16.3 inch)    

355.6 mm (14.0 inch)    
Copper Weight    
4.7 kg (10.3 lb)    

2.2 kg (4.9 lb)    
Insulation     Heavy Nytherm    
Connection (2)     Series     2 Parallel Star    
Line Leads     #14

965.2 mm (38.0 inch)    
#10

152.4 mm (6.0 inch)    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #02
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram A

5N-7065 Generator

Table 11
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR
(RANDOM WOUND)    
ROTOR
(FORM WOUND)    
Stack Height    
215.9 mm (8.5 inch)    

215.9 mm (8.5 inch)    
-    
Slots     60     -     -    
Coil Throw     1 - 12     -     -    
Turns/Coil     3.8(3,4,4,4,4)     -     -    
Turns/Pole     -     160     -    
No. & Wire Size     9 - #14     1 - #7 sq     -    
Mean Length Turn    
1214.1 mm (47.8 inch)    
-     -    
Copper Weight    
46.9 kg (103.6 lb)    

69.3 kg (152.7 lb)    
-    
Inside Connection (1)     4/2 Parallel Star     4 in Series     -    
Line Leads (No. & Size)     20 - #2     -     -    
Terminal bolt size     3/8 inch     -     -    
Low Voltage connected line
resistance at 25 ° C (77 ° F)    
0.0111 ohms     -     -    
Field lead resistance at
25 ° C (77 ° F)    
-     0.829 ohms     -    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)    
Stack Length    
101.6 mm (4.0 inch)    

101.6 mm (4.0 inch)    
Coils/Group     1     2    
Slots (Coils)     6     36    
Turns (Coils)     140     6    
No. & Size Wire     1 - #15.5     2 - #15    
Coil Throw     1 - 2     1 - 6    
Mean Length Turn (Calc.)    
414.0 mm (16.3 inch)    

355.6 mm (14.0 inch)    
Copper Weight    
4.7 kg (10.3 lb)    

2.2 kg (4.9 lb)    
Insulation     Heavy Nytherm    
Connection (2)     Series     2 Parallel Star    
Line Leads     #14

965.2 mm (38.0 inch)    
#10

152.4 mm (6.0 inch)    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #13
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram A

5N-7066 Generator

Table 12
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR
(RANDOM WOUND)    
ROTOR
(FORM WOUND)    
Stack Height    
266.7 mm (10.5 inch)    

266.7 mm (10.5 inch)    
-    
Slots     72     -     -    
Coil Throw     1 - 14     -     -    
Turns/Coil     2     -     -    
Turns/Pole     -     160     -    
No. & Wire Size     11 - #13     1 - #7 sq     -    
Mean Length Turn    
1270.0 mm (50.0 inch)    
-     -    
Copper Weight    
50.8 kg (112.0 lb)    

76.7 kg (169.1 lb)    
-    
Inside Connection (1)     4/2 Parallel Star     4 in Series     -    
Line Leads (No. & Size)     20 - #1     -     -    
Terminal bolt size     3/8 inch     -     -    
Low Voltage connected line
resistance at 25 ° C (77 ° F)    
0.005 ohms     -     -    
Field lead resistance at
25 ° C (77 ° F)    
-     0.916 ohms     -    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)    
Stack Length    
101.6 mm (4.0 inch)    

101.6 mm (4.0 inch)    
Coils/Group     1     2    
Slots (Coils)     6     36    
Turns (Coils)     140     6    
No. & Size Wire     1 - #15.5     2 - #15    
Coil Throw     1 - 2     1 - 6    
Mean Length Turn (Calc.)    
414.0 mm (16.3 inch)    

355.6 mm (14.0 inch)    
Copper Weight    
4.7 kg (10.3 lb)    

2.2 kg (4.9 lb)    
Insulation     Heavy Nytherm    
Connection (2)     Series     2 Parallel Star    
Line Leads     #14

965.2 mm (38.0 inch)    
#10

152.4 mm (6.0 inch)    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #01
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram A

5N-7067 Generator

Table 13
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR
(RANDOM WOUND)    
ROTOR
(FORM WOUND)    
Stack Height    
266.7 mm (10.5 inch)    

266.7 mm (10.5 inch)    
-    
Slots     72     -     -    
Coil Throw     1 - 14     -     -    
Turns/Coil     2.5(2,3,2,3,2,3)     -     -    
Turns/Pole     -     160     -    
No. & Wire Size     9 - #13     1 - #7 sq     -    
Mean Length Turn    
1270.0 mm (50.0 inch)    
-     -    
Copper Weight    
51.7 kg (114.0 lb)    

76.7 kg (169.1 lb)    
-    
Inside Connection (1)     4/2 Parallel Star     4 in Series     -    
Line Leads (No. & Size)     20 - #2     -     -    
Terminal bolt size     3/8 inch     -     -    
Low Voltage connected line
resistance at 25 ° C (77 ° F)    
0.0076 ohms     -     -    
Field lead resistance at
25 ° C (77 ° F)    
-     0.916 ohms     -    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)    
Stack Length    
101.6 mm (4.0 inch)    

101.6 mm (4.0 inch)    
Coils/Group     1     2    
Slots (Coils)     6     36    
Turns (Coils)     140     6    
No. & Size Wire     1 - #15.5     2 - #15    
Coil Throw     1 - 2     1 - 6    
Mean Length Turn (Calc.)    
414.0 mm (16.3 inch)    

355.6 mm (14.0 inch)    
Copper Weight    
4.7 kg (10.3 lb)    

2.2 kg (4.9 lb)    
Insulation     Heavy Nytherm    
Connection (2)     Series     2 Parallel Star    
Line Leads     #14

965.2 mm (38.0 inch)    
#10

152.4 mm (6.0 inch)    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #13
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram A

Note: Wires 20, 22, and 24 are brought out as tap connections between the 4th and 5th coil (14 turns from T0).

5N-7068 Generator

Table 14
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR
(RANDOM WOUND)    
ROTOR
(FORM WOUND)    
Stack Height    
289.6 mm (11.4 inch)    

289.6 mm (11.4 inch)    
-    
Slots     66 (1)     -     -    
Coil Throw     1 - 13     -     -    
Turns/Coil     1     -     -    
Turns/Pole     -     160     -    
No. & Wire Size     25 - #13     1 - #7     -    
Mean Length Turn    
1374.1 mm (54.1 inch)    
-     -    
Copper Weight    
52.8 kg (116.5 lb)    

77.2 kg (170.2 lb)    
-    
Inside Connection (2)     4 in Series     4 in Series     -    
Line Leads (No. & Size)     20 - #1     -     -    
Terminal bolt size     3/8 inch     -     -    
Low Voltage connected line
resistance at 25 ° C (77 ° F)    
0.0041 ohms     -     -    
Field lead resistance at
25 ° C (77 ° F)    
-     0.966 ohms     -    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)    
Stack Length    
101.6 mm (4.0 inch)    

101.6 mm (4.0 inch)    
Coils/Group     1     2    
Slots (Coils)     6     36    
Turns (Coils)     140     6    
No. & Size Wire     1 - #15.5     2 - #15    
Coil Throw     1 - 2     1 - 6    
Mean Length Turn (Calc.)    
414.0 mm (16.3 inch)    

355.6 mm (14.0 inch)    
Copper Weight    
4.7 kg (10.3 lb)    

2.2 kg (4.9 lb)    
Insulation     Heavy Nytherm    
Connection (3)     Series     2 Parallel Star    
Line Leads     #14

965.2 mm (38.0 inch)    
#10

152.4 mm (6.0 inch)    
( 1 ) Wind 6 coil groups with 5 coils per group, wind 6 coil groups with 6 coils per group. Put coil groups in stator (5,6,5,6-etc).
( 2 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #34
( 3 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram A

5N-7069 Generator

Table 15
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR
(RANDOM WOUND)    
ROTOR
(FORM WOUND)    
Stack Height    
289.6 mm (11.4 inch)    

289.6 mm (11.4 inch)    
-    
Slots     84     -     -    
Coil Throw     1 - 17     -     -    
Turns/Coil     2     -     -    
Turns/Pole     -     160     -    
No. & Wire Size     10 - #13     1 - #7     -    
Mean Length Turn    
1501.1 mm (59.1 inch)    
-     -    
Copper Weight    
57.6 kg (126.9 lb)    

77.2 kg (170.2 lb)    
-    
Inside Connection (2)     4/2 Parallel Star     4 in Series     -    
Line Leads (No. & Size)     10 - #0000     -     -    
Terminal bolt size     3/8 inch     -     -    
Low Voltage connected line
resistance at 25 ° C (77 ° F)    
0.0072 ohms     -     -    
Field lead resistance at
25 ° C (77 ° F)    
-     0.966 ohms     -    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)    
Stack Length    
101.6 mm (4.0 inch)    

101.6 mm (4.0 inch)    
Coils/Group     1     2    
Slots (Coils)     6     36    
Turns (Coils)     140     6    
No. & Size Wire     1 - #15.5     2 - #15    
Coil Throw     1 - 2     1 - 6    
Mean Length Turn (Calc.)    
414.0 mm (16.3 inch)    

355.6 mm (14.0 inch)    
Copper Weight    
4.7 kg (10.3 lb)    

2.2 kg (4.9 lb)    
Insulation     Heavy Nytherm    
Connection (3)     Series     2 Parallel Star    
Line Leads     #14

965.2 mm (38.0 inch)    
#10

152.4 mm (6.0 inch)    
( 2 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #37
( 3 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram A

Note: Wires 20 and 22 are brought out as tap connections between the 5th and 6th coil (10 turns from T0).

Note: Wire 24 is brought out as a tap connection between the 6th and 7th coil (12 turns from T0).

5N-7070 Generator

Table 16
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR
(RANDOM WOUND)    
ROTOR
(FORM WOUND)    
Stack Height    
424.2 mm (16.7 inch)    

431.8 mm (17.0 inch)    
-    
Slots     84     -     -    
Coil Throw     1 - 19     -     -    
Turns/Coil     1     -     -    
Turns/Pole     -     160     -    
No. & Wire Size     18 - #13     1 - #7 sq     -    
Mean Length Turn    
1724.7 mm (67.9 inch)    
-     -    
Copper Weight    
63.5 kg (139.9 lb)    

98.5 kg (217.1 lb)    
-    
Inside Connection (1)     4/2 Parallel Star     4 in Series     -    
Line Leads (No. & Size)     20 - #000     -     -    
Terminal bolt size     3/8 inch     -     -    
Low Voltage connected line
resistance at 25 ° C (77 ° F)    
0.0023 ohms     -     -    
Field lead resistance at
25 ° C (77 ° F)    
-     1.17 ohms     -    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)    
Stack Length    
127.0 mm (5.0 inch)    

127.0 mm (5.0 inch)    
Coils/Group     1     2    
Slots (Coils)     6     36    
Turns (Coils)     125     6    
No. & Size Wire     1 - #15     2 - #15    
Coil Throw     1 - 2     1 - 6    
Mean Length Turn (Calc.)    
464.8 mm (18.3 inch)    

406.4 mm (16.0 inch)    
Copper Weight    
5.2 kg (11.5 lb)    

2.7 kg (5.9 lb)    
Insulation     Heavy Nytherm    
Connection (2)     Series     2 Parallel Star    
Line Leads     #14

965.2 mm (38.0 inch)    
#10

152.4 mm (6.0 inch)    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #01
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram A

5N-7071 Generator

Table 17
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR
(RANDOM WOUND)    
ROTOR
(FORM WOUND)    
Stack Height    
424.2 mm (16.7 inch)    

431.8 mm (17.0 inch)    
-    
Slots     54 (1)     -     -    
Coil Throw     1 - 12     -     -    
Turns/Coil     1     -     -    
Turns/Pole     -     160     -    
No. & Wire Size     30 - #13     1 - #7 sq     -    
Mean Length Turn    
1714.5 mm (67.5 inch)    
-     -    
Copper Weight    
64.2 kg (141.5 lb)    

98.4744 kg (217.1 lb)    
-    
Inside Connection (2)     4/2 Parallel Star     4 in Series     -    
Line Leads (No. & Size)     20 - #00     -     -    
Terminal bolt size     3/8 inch     -     -    
Low Voltage connected line
resistance at 25 ° C (77 ° F)    
0.0033 ohms     -     -    
Field lead resistance at
25 ° C (77 ° F)    
-     1.17 ohms     -    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)    
Stack Length    
127.0 mm (5.0 inch)    

127.0 mm (5.0 inch)    
Coils/Group     1     2    
Slots (Coils)     6     36    
Turns (Coils)     125     6    
No. & Size Wire     1 - #15     2 - #15    
Coil Throw     1 - 2     1 - 6    
Mean Length Turn (Calc.)    
464.8 mm (18.3 inch)    

406.4 mm (16.0 inch)    
Copper Weight    
5.2 kg (11.5 lb)    

2.7 kg (5.9 lb)    
Insulation     Heavy Nytherm    
Connection (3)     Series     2 Parallel Star    
Line Leads     #14

965.2 mm (38.0 inch)    
#10

152.4 mm (6.0 inch)    
( 1 ) Wind 6 coil groups with 4 coils per group, wind 6 coil groups with 5 coils per group. Put coil groups in stator (4,5,4,5-etc).
( 2 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #31
( 3 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram A

5N-7200 Generator

Table 18
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR
(RANDOM WOUND)    
ROTOR
(FORM WOUND)    
Stack Height    
467.4 mm (18.4 inch)    

480.1 mm (18.9 inch)    
-    
Slots     72     -     -    
Coil Throw     1 - 11     -     -    
Turns/Coil     2     -     -    
Turns/Pole     -     147.5     -    
No. & Wire Size     20 - #13    
1 - 3.3 mm x 6.4 mm (.13 inch x .25 inch)    
-    
Mean Length Turn    
1772.9 mm (69.8 inch)    
-     -    
Copper Weight    
121.5 kg (267.9 lb)    

237.0 kg (522.6 lb)    
-    
Inside Connection (1)     6/3 Parallel Star     6 in Series     -    
Line Leads (No. & Size)     30 - #00     -     -    
Terminal bolt size     3/8 inch     -     -    
Low Voltage connected line
resistance at 25 ° C (77 ° F)    
0.0065 ohms     -     -    
Field lead resistance at
25 ° C (77 ° F)    
-     1.126 ohms     -    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     80 Hz    
Exciter Poles     8    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)    
Stack Length    
88.9 mm (3.5 inch)    

88.9 mm (3.5 inch)    
Coils/Group     1     2    
Slots (Coils)     8     48    
Turns (Coils)     160     8    
No. & Size Wire     1 - #18
2 - #17    
3 - #16    
Coil Throw     1 - 2     1 - 6    
Mean Length Turn (Calc.)    
355.6 mm (14.0 inch)    

436.9 mm (17.2 inch)    
Copper Weight    
6.4 kg (14.0 lb)    

13.6 kg (29.9 lb)    
Insulation     Heavy Nytherm    
Connection (2)     Series     2 Parallel Star    
Line Leads     #14

762.0 mm (30.0 inch)    
#10

304.8 mm (12.0 inch)    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #38
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram C

5N-7201 Generator

Table 19
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR
(RANDOM WOUND)    
ROTOR
(FORM WOUND)    
Stack Height    
467.4 mm (18.4 inch)    

480.1 mm (18.9 inch)    
-    
Slots     72     -     -    
Coil Throw     1 - 10     -     -    
Turns/Coil     2.75(3,3,3,2)     -     -    
Turns/Pole     -     154.6     -    
No. & Wire Size     14 - #13    
1 - 3.3 mm x 6.4 mm (.13 inch x .25 inch)    
-    
Mean Length Turn    
1704.3 mm (67.1 inch)    
-     -    
Copper Weight    
112.4 kg (247.8 lb)    

237.0 kg (522.6 lb)    
-    
Inside Connection (1)     6/3 Parallel Star     6 in Series     -    
Line Leads (No. & Size)     30 - #0     -     -    
Terminal bolt size     3/8 inch     -     -    
Low Voltage connected line
resistance at 25 ° C (77 ° F)    
0.0122 ohms     -     -    
Field lead resistance at
25 ° C (77 ° F)    
-     1.126 ohms     -    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     80 Hz    
Exciter Poles     8    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)    
Stack Length    
88.9 mm (3.5 inch)    

88.9 mm (3.5 inch)    
Coils/Group     1     2    
Slots (Coils)     8     48    
Turns (Coils)     160     8    
No. & Size Wire     1 - #18
2 - #17    
3 - #16    
Coil Throw     1 - 2     1 - 6    
Mean Length Turn (Calc.)    
355.6 mm (14.0 inch)    

436.9 mm (17.2 inch)    
Copper Weight    
6.4 kg (14.0 lb)    

13.6 kg (29.9 lb)    
Insulation     Heavy Nytherm    
Connection (2)     Series     2 Parallel Star    
Line Leads     #14

762.0 mm (30.0 inch)    
#10

304.8 mm (12.0 inch)    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #38
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram C

5N-7202 Generator

Table 20
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR
(RANDOM WOUND)    
ROTOR
(FORM WOUND)    
Stack Height    
467.4 mm (18.4 inch)    

480.1 mm (18.9 inch)    
-    
Slots     72     -     -    
Coil Throw     1 - 11     -     -    
Turns/Coil     2     -     -    
Turns/Pole     -     147.5     -    
No. & Wire Size     20 - #13    
1 - 3.3 mm x 6.4 mm (.13 inch x .25 inch)    
-    
Mean Length Turn    
1772.9 mm (69.8 inch)    
-     -    
Copper Weight    
121.5 kg (267.9 lb)    

237.0 kg (522.6 lb)    
-    
Inside Connection (1)     6/3 Parallel Star     6 in Series     -    
Line Leads (No. & Size)     30 - #00     -     -    
Terminal bolt size     3/8 inch     -     -    
Low Voltage connected line
resistance at 25 ° C (77 ° F)    
0.0065 ohms     -     -    
Field lead resistance at
25 ° C (77 ° F)    
-     1.126 ohms     -    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     80 Hz    
Exciter Poles     8    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)    
Stack Length    
88.9 mm (3.5 inch)    

88.9 mm (3.5 inch)    
Coils/Group     1     2    
Slots (Coils)     8     48    
Turns (Coils)     160     8    
No. & Size Wire     1 - #18
2 - #17    
3 - #16    
Coil Throw     1 - 2     1 - 6    
Mean Length Turn (Calc.)    
355.6 mm (14.0 inch)    

436.9 mm (17.2 inch)    
Copper Weight    
6.4 kg (14.0 lb)    

13.6 kg (29.9 lb)    
Insulation     Heavy Nytherm    
Connection (2)     Series     2 Parallel Star    
Line Leads     #14

762.0 mm (30.0 inch)    
#10

304.8 mm (12.0 inch)    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #38
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram C

5N-7203 Generator

Table 21
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR
(RANDOM WOUND)    
ROTOR
(FORM WOUND)    
Stack Height    
467.4 mm (18.4 inch)    

480.1 mm (18.9 inch)    
-    
Slots     72     -     -    
Coil Throw     1 - 10     -     -    
Turns/Coil     2.75(3,3,3,2)     -     -    
Turns/Pole     -     154.6     -    
No. & Wire Size     14 - #13    
1 - 3.3 mm x 6.4 mm (.13 inch x .25 inch)    
-    
Mean Length Turn    
1704.3 mm (67.1 inch)    
-     -    
Copper Weight    
112.4 kg (247.8 lb)    

237.0 kg (522.6 lb)    
-    
Inside Connection (1)     6/3 Parallel Star     6 in Series     -    
Line Leads (No. & Size)     30 - #0     -     -    
Terminal bolt size     3/8 inch     -     -    
Low Voltage connected line
resistance at 25 ° C (77 ° F)    
0.0122 ohms     -     -    
Field lead resistance at
25 ° C (77 ° F)    
-     1.126 ohms     -    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     80 Hz    
Exciter Poles     8    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)    
Stack Length    
88.9 mm (3.5 inch)    

88.9 mm (3.5 inch)    
Coils/Group     1     2    
Slots (Coils)     8     48    
Turns (Coils)     160     8    
No. & Size Wire     1 - #18
2 - #17    
3 - #16    
Coil Throw     1 - 2     1 - 6    
Mean Length Turn (Calc.)    
355.6 mm (14.0 inch)    

436.9 mm (17.2 inch)    
Copper Weight    
6.4 kg (14.0 lb)    

13.6 kg (29.9 lb)    
Insulation     Heavy Nytherm    
Connection (2)     Series     2 Parallel Star    
Line Leads     #14

762.0 mm (30.0 inch)    
#10

304.8 mm (12.0 inch)    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #38
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram C

5N-7204 Generator

Table 22
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR
(RANDOM WOUND)    
ROTOR
(FORM WOUND)    
Stack Height    
269.2 mm (10.6 inch)    

281.9 mm (11.1 inch)    
-    
Slots     72     -     -    
Coil Throw     1 - 10     -     -    
Turns/Coil     3.5(3,4,3,4)     -     -    
Turns/Pole     -     154.5     -    
No. & Wire Size     12 - #13    
1 - 3.3 mm x 6.4 mm (.13 inch x .25 inch)    
-    
Mean Length Turn    
1308.1 mm (51.5 inch)    
-     -    
Copper Weight    
94.1 kg (207.5 lb)    

168.9 kg (372.5 lb)    
-    
Inside Connection (1)     6/3 Parallel Star     6 in Series     -    
Line Leads (No. & Size)     30 - #2     -     -    
Terminal bolt size     3/8 inch     -     -    
Low Voltage connected line
resistance at 25 ° C (77 ° F)    
0.0139 ohms     -     -    
Field lead resistance at
25 ° C (77 ° F)    
-     0.802 ohms     -    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     80 Hz    
Exciter Poles     8    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)    
Stack Length    
88.9 mm (3.5 inch)    

88.9 mm (3.5 inch)    
Coils/Group     1     2    
Slots (Coils)     8     48    
Turns (Coils)     160     8    
No. & Size Wire     1 - #18
2 - #17    
3 - #16    
Coil Throw     1 - 2     1 - 6    
Mean Length Turn (Calc.)    
355.6 mm (14.0 inch)    

436.9 mm (17.2 inch)    
Copper Weight    
6.4 kg (14.0 lb)    

13.6 kg (29.9 lb)    
Insulation     Heavy Nytherm    
Connection (2)     Series     2 Parallel Star    
Line Leads     #14

762.0 mm (30.0 inch)    
#10

304.8 mm (12.0 inch)    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #38
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram C

5N-7205 Generator

Table 23
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR
(RANDOM WOUND)    
ROTOR
(FORM WOUND)    
Stack Height    
269.2 mm (10.6 inch)    

281.9 mm (11.1 inch)    
-    
Slots     72     -     -    
Coil Throw     1 - 10     -     -    
Turns/Coil     4.5(4,5,4,5)     -     -    
Turns/Pole     -     154.5     -    
No. & Wire Size     9 - #13    
1 - 3.3 mm x 6.4 mm (.13 inch x .25 inch)    
-    
Mean Length Turn    
1308.1 mm (51.5 inch)    
-     -    
Copper Weight    
90.8 kg (200.1 lb)    

168.9 kg (372.5 lb)    
-    
Inside Connection (1)     6/3 Parallel Star     6 in Series     -    
Line Leads (No. & Size)     30 - #2     -     -    
Terminal bolt size     3/8 inch     -     -    
Low Voltage connected line
resistance at 25 ° C (77 ° F)    
0.0239 ohms     -     -    
Field lead resistance at
25 ° C (77 ° F)    
-     0.802 ohms     -    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     80 Hz    
Exciter Poles     8    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)    
Stack Length    
88.9 mm (3.5 inch)    

88.9 mm (3.5 inch)    
Coils/Group     1     2    
Slots (Coils)     8     48    
Turns (Coils)     160     8    
No. & Size Wire     1 - #18
2 - #17    
3 - #16    
Coil Throw     1 - 2     1 - 6    
Mean Length Turn (Calc.)    
355.6 mm (14.0 inch)    

436.9 mm (17.2 inch)    
Copper Weight    
6.4 kg (14.0 lb)    

13.6 kg (29.9 lb)    
Insulation     Heavy Nytherm    
Connection (2)     Series     2 Parallel Star    
Line Leads     #14

762.0 mm (30.0 inch)    
#10

304.8 mm (12.0 inch)    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #38
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram C

5N-7206 Generator

Table 24
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR
(RANDOM WOUND)    
ROTOR
(FORM WOUND)    
Stack Height    
269.2 mm (10.6 inch)    

281.9 mm (11.1 inch)    
-    
Slots     72     -     -    
Coil Throw     1 - 10     -     -    
Turns/Coil     3.5(3,4,3,4)     -     -    
Turns/Pole     -     154.5     -    
No. & Wire Size     12 - #13    
1 - 3.3 mm x 6.4 mm (.13 inch x .25 inch)    
-    
Mean Length Turn    
1308.1 mm (51.5 inch)    
-     -    
Copper Weight    
94.1 kg (207.5 lb)    

168.9 kg (372.5 lb)    
-    
Inside Connection (1)     6/3 Parallel Star     6 in Series     -    
Line Leads (No. & Size)     30 - #2     -     -    
Terminal bolt size     3/8 inch     -     -    
Low Voltage connected line
resistance at 25 ° C (77 ° F)    
0.0139 ohms     -     -    
Field lead resistance at
25 ° C (77 ° F)    
-     0.802 ohms     -    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     80 Hz    
Exciter Poles     8    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)    
Stack Length    
88.9 mm (3.5 inch)    

88.9 mm (3.5 inch)    
Coils/Group     1     2    
Slots (Coils)     8     48    
Turns (Coils)     160     8    
No. & Size Wire     1 - #18
2 - #17    
3 - #16    
Coil Throw     1 - 2     1 - 6    
Mean Length Turn (Calc.)    
355.6 mm (14.0 inch)    

436.9 mm (17.2 inch)    
Copper Weight    
6.4 kg (14.0 lb)    

13.6 kg (29.9 lb)    
Insulation     Heavy Nytherm    
Connection (2)     Series     2 Parallel Star    
Line Leads     #14

762.0 mm (30.0 inch)    
#10

304.8 mm (12.0 inch)    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #38
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram C

5N-7207 Generator

Table 25
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR
(RANDOM WOUND)    
ROTOR
(FORM WOUND)    
Stack Height    
269.2 mm (10.6 inch)    

281.9 mm (11.1 inch)    
-    
Slots     72     -     -    
Coil Throw     1 - 10     -     -    
Turns/Coil     4.5(4,5,4,5)     -     -    
Turns/Pole     -     154.5     -    
No. & Wire Size     9 - #13    
1 - 3.3 mm x 6.4 mm (.13 inch x .25 inch)    
-    
Mean Length Turn    
1308.1 mm (51.5 inch)    
-     -    
Copper Weight    
90.8 kg (200.1 lb)    

168.9 kg (372.5 lb)    
-    
Inside Connection (1)     6/3 Parallel Star     6 in Series     -    
Line Leads (No. & Size)     30 - #2     -     -    
Terminal bolt size     3/8 inch     -     -    
Low Voltage connected line
resistance at 25 ° C (77 ° F)    
0.0239 ohms     -     -    
Field lead resistance at
25 ° C (77 ° F)    
-     0.802 ohms     -    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     80 Hz    
Exciter Poles     8    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)    
Stack Length    
88.9 mm (3.5 inch)    

88.9 mm (3.5 inch)    
Coils/Group     1     2    
Slots (Coils)     8     48    
Turns (Coils)     160     8    
No. & Size Wire     1 - #18
2 - #17    
3 - #16    
Coil Throw     1 - 2     1 - 6    
Mean Length Turn (Calc.)    
355.6 mm (14.0 inch)    

436.9 mm (17.2 inch)    
Copper Weight    
6.4 kg (14.0 lb)    

13.6 kg (29.9 lb)    
Insulation     Heavy Nytherm    
Connection (2)     Series     2 Parallel Star    
Line Leads     #14

762.0 mm (30.0 inch)    
#10

304.8 mm (12.0 inch)    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #38
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram C

Caterpillar Information System:

SR4 and SR4B Electric Power Generation Rewind Data Winding Data for <B>5N-0076</B> Generator through <B>5N-0090</B> Generator
Disassembly and Assembly of the TPL61 Turbocharger{1052} Disassembly and Assembly of the TPL61 Turbocharger{1052}
G3516B Engines Electronic Service Tool Will Not Communicate with ECM - The Caterpillar Electronic Technician (ET) Will Not Communicate With the Electronic Control Module (ECM) and/or the Integrated Temperature Sensing Module (ITSM)
G3516B Engines Intermittent Engine Shutdown
3618 Engine Connecting Rod
3618 Engine Fuel Transfer Pump - Assemble
3114, 3116, and 3126 Engines for Caterpillar Built Machines Turbocharger - Remove
3500B Engines Auxiliary Water Pump - Install - Auxiliary Pump
3500B Engines Auxiliary Water Pump - Remove - Auxiliary Pump
3114, 3116, and 3126 Engines Lubrication System
345B Excavator Engine Air Filter Primary Element - Clean/Replace
325D and 329D Excavators Hydraulic System Stick Drift Reduction Valve
3114, 3116, and 3126 Engines Cooling System
3512B Petroleum Engines Engine Oil Pressure
3512B Petroleum Engine Before Starting Engine
3512B Petroleum Engine Cold Weather Starting
Connection Diagrams: SR4 and SR4B Generators, Voltage Regulators, Options VR3F Voltage Regulator Connections (SR4B for 3500 Engines)
Connection Diagrams: SR4 and SR4B Generators, Voltage Regulators, Options Main Revolving Field Connections (All Except SR4B for 3500 Engines)
Connection Diagrams: SR4 and SR4B Generators, Voltage Regulators, Options Digital Voltage Regulator Connections (All Except SR4B for 3500 Engines)
Connection Diagrams: SR4 and SR4B Generators, Voltage Regulators, Options Options (All Except SR4B for 3500 Engines)
Connection Diagrams: SR4 and SR4B Generators, Voltage Regulators, Options VR3F Voltage Regulator Connections (All Except SR4B for 3500 Engines)
Connection Diagrams: SR4 and SR4B Generators, Voltage Regulators, Options Main Revolving Field Connections (SR4B for 3500 Engines)
Connection Diagrams: SR4 and SR4B Generators, Voltage Regulators, Options VR3 Voltage Regulator Connections (SR4B for 3500 Engines)
Connection Diagrams: SR4 and SR4B Generators, Voltage Regulators, Options Digital Voltage Regulator Connections (SR4B for 3500 Engines)
Back to top