5N-0431 Generator
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 736.6 mm (29.0 inch)     |
749.3 mm (29.5 inch)     |
-     | |
Slots     | 90     | -     | -     | |
Coil Throw     | 1 - 12     | -     | -     | |
Turns/Coil     | 2     | -     | -     | |
Turns/Pole     | -     | 147.5     | -     | |
No. & Wire Size     | 14 - #12     | 1 - 3.66 mm x 7.32 mm (.144 inch x .288 inch)     |
-     | |
Mean Length Turn     | 2336.8 mm (92.0 inch)     |
-     | -     | |
Copper Weight     | 179.9 kg (396.7 lb)     |
419.6 kg (925.1 lb)     |
-     | |
Inside Connection (1)     | 6 Parallel Star     | 6 in Series     | -     | |
Line Leads (No. & Size)     | 24 - #1     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0043 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.162 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 80 Hz     | |||
Exciter Poles     | 8     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 8     | 48     | ||
Turns (Coils)     | 160     | 8     | ||
No. & Size Wire     | 1 - #18 and 2 - #17     | 3 - #16     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 355.6 mm (14.0 inch)     |
436.9 mm (17.2 inch)     |
||
Copper Weight     | 6.4 kg (14.0 lb)     |
13.6 kg (29.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 762.0 mm (30.0 inch)     |
#10 304.8 mm (12.0 inch)     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #40 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram C |
5N-4999 Generator
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 381.0 mm (15.0 inch)     |
381.0 mm (15.0 inch)     |
-     | |
Slots     | 60     | -     | -     | |
Coil Throw     | 1 - 14     | -     | -     | |
Turns/Coil     | 2     | -     | -     | |
Turns/Pole     | -     | 110     | -     | |
No. & Wire Size     | 14 - #14     | 1 - #7     | -     | |
Mean Length Turn     | 1503.7 mm (59.2 inch)     |
-     | -     | |
Copper Weight     | 49.2 kg (108.5 lb)     |
49.1 kg (108.3 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 20 - #2     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     |
0.0048 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     |
-     | 0.895 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 101.6 mm (4.0 inch)     |
101.6 mm (4.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 140     | 6     | ||
No. & Size Wire     | 1 - #15.5     | 2 - #15     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 414.0 mm (16.3 inch)     |
355.6 mm (14.0 inch)     |
||
Copper Weight     | 4.7 kg (10.3 lb)     |
2.2 kg (4.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 965.2 mm (38.0 inch)     |
#10 114.3 mm (4.5 inch)     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #01 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram A |
5N-5000 Generator
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 381.0 mm (15.0 inch)     |
381.0 mm (15.0 inch)     |
-     | |
Slots     | 60     | -     | -     | |
Coil Throw     | 1 - 13     | -     | -     | |
Turns/Coil     | 2.6(2,2,3,3,3)     | -     | -     | |
Turns/Pole     | -     | 110     | -     | |
No. & Wire Size     | 13 - #15     | 1 - #7     | -     | |
Mean Length Turn     | 1452.9 mm (57.2 inch)     |
-     | -     | |
Copper Weight     | 45.5 kg (100.4 lb)     |
49.1 kg (108.3 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 20 - #4     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     |
0.0081 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     |
-     | 0.895 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 101.6 mm (4.0 inch)     |
101.6 mm (4.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 140     | 6     | ||
No. & Size Wire     | 1 - #15.5     | 2 - #15     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 414.0 mm (16.3 inch)     |
355.6 mm (14.0 inch)     |
||
Copper Weight     | 4.7 kg (10.3 lb)     |
2.2 kg (4.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 965.2 mm (38.0 inch)     |
#10 114.3 mm (4.5 inch)     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #13 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram A |
Note: Wires 20, 22, and 24 are brought out as tap connections between the 4th and 5th coil (14 turns from T0).
5N-5001 Generator
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 381.0 mm (15.0 inch)     |
381.0 mm (15.0 inch)     |
-     | |
Slots     | 60     | -     | -     | |
Coil Throw     | 1 - 14     | -     | -     | |
Turns/Coil     | 2     | -     | -     | |
Turns/Pole     | -     | 110     | -     | |
No. & Wire Size     | 14 - #14     | 1 - #7     | -     | |
Mean Length Turn     | 1503.7 mm (59.2 inch)     |
-     | -     | |
Copper Weight     | 49.2 kg (108.5 lb)     |
49.1 kg (108.3 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 20 - #2     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     |
0.0048 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     |
-     | 0.895 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 101.6 mm (4.0 inch)     |
101.6 mm (4.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 140     | 6     | ||
No. & Size Wire     | 1 - #15.5     | 2 - #15     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 414.0 mm (16.3 inch)     |
355.6 mm (14.0 inch)     |
||
Copper Weight     | 4.7 kg (10.3 lb)     |
2.2 kg (4.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 965.2 mm (38.0 inch)     |
#10 114.3 mm (4.5 inch)     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #01 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram A |
5N-5005 Generator
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 406.4 mm (16.0 inch)     |
424.2 mm (16.7 inch)     |
-     | |
Slots     | 72     | -     | -     | |
Coil Throw     | 1 - 15     | -     | -     | |
Turns/Coil     | 2     | -     | -     | |
Turns/Pole     | -     | 174     | -     | |
No. & Wire Size     | 14 - #12     | 1 - 3.66 mm x 7.32 mm (.144 inch x .288 inch)     |
-     | |
Mean Length Turn     | 1915.2 mm (75.4 inch)     |
-     | -     | |
Copper Weight     | 115.8 kg (255.2 lb)     |
237.7 kg (524.0 lb)     |
-     | |
Inside Connection (1)     | 4 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 16 - #00     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     |
0.0045 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     |
-     | 0.686 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 120 Hz     | |||
Exciter Poles     | 8     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 63.5 mm (2.5 inch)     |
63.5 mm (2.5 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 8     | 48     | ||
Turns (Coils)     | 160     | 7     | ||
No. & Size Wire     | 2 - #16.5     | 3 - #15     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 330.2 mm (13.0 inch)     |
386.1 mm (15.2 inch)     |
||
Copper Weight     | 10.0 kg (22.1 lb)     |
6.2 kg (13.7 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 3048.0 mm (120.0 inch)     |
#10 304.8 mm (12.0 inch)     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #10 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram C |
5N-5006 Generator
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 406.4 mm (16.0 inch)     |
424.2 mm (16.7 inch)     |
-     | |
Slots     | 72     | -     | -     | |
Coil Throw     | 1 - 14     | -     | -     | |
Turns/Coil     | 2.5(2,3,2,3,2,3)     | -     | -     | |
Turns/Pole     | -     | 174     | -     | |
No. & Wire Size     | 14 - #13     | 1 - 3.66 mm x 7.32 mm (.144 inch x .288 inch)     |
-     | |
Mean Length Turn     | 1846.6 mm (72.7 inch)     |
-     | -     | |
Copper Weight     | 110.6 kg (243.9 lb)     |
237.7 kg (524.0 lb)     |
-     | |
Inside Connection (1)     | 4 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 16 - #1     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     |
0.0068 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     |
-     | 0.686 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 120 Hz     | |||
Exciter Poles     | 8     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 63.5 mm (2.5 inch)     |
63.5 mm (2.5 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 8     | 48     | ||
Turns (Coils)     | 160     | 7     | ||
No. & Size Wire     | 2 - #16.5     | 3 - #15     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 330.2 mm (13.0 inch)     |
386.1 mm (15.2 inch)     |
||
Copper Weight     | 10.0 kg (22.1 lb)     |
6.2 kg (13.7 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 3048.0 mm (120.0 inch)     |
#10 304.8 mm (12.0 inch)     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #10 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram C |
5N-5007 Generator
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 406.4 mm (16.0 inch)     |
424.2 mm (16.7 inch)     |
-     | |
Slots     | 72     | -     | -     | |
Coil Throw     | 1 - 15     | -     | -     | |
Turns/Coil     | 2     | -     | -     | |
Turns/Pole     | -     | 174     | -     | |
No. & Wire Size     | 14 - #12     | 1 - 3.66 mm x 7.32 mm (.144 inch x .288 inch)     |
-     | |
Mean Length Turn     | 1915.2 mm (75.4 inch)     |
-     | -     | |
Copper Weight     | 115.8 kg (255.2 lb)     |
237.7 kg (524 lb)     |
-     | |
Inside Connection (1)     | 4 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 16 - #00     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     |
0.0045 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     |
-     | 0.686 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 120 Hz     | |||
Exciter Poles     | 8     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 63.5 mm (2.5 inch)     |
63.5 mm (2.5 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 8     | 48     | ||
Turns (Coils)     | 160     | 7     | ||
No. & Size Wire     | 2 - #16.5     | 3 - #15     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 330.2 mm (13.0 inch)     |
386.1 mm (15.2 inch)     |
||
Copper Weight     | 10.0 kg (22.1 lb)     |
6.2 kg (13.7 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 3048.0 mm (120.0 inch)     |
#10 304.8 mm (12.0 inch)     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #10 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram C |
5N-5008 Generator
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 406.4 mm (16.0 inch)     |
424.2 mm (16.7 inch)     |
-     | |
Slots     | 72     | -     | -     | |
Coil Throw     | 1 - 14     | -     | -     | |
Turns/Coil     | 2.5(2,3,2,3,2,3)     | -     | -     | |
Turns/Pole     | -     | 174     | -     | |
No. & Wire Size     | 14 - #13     | 1 - 3.66 mm x 7.32 mm (.144 inch x .288 inch)     |
-     | |
Mean Length Turn     | 1846.6 mm (72.7 inch)     |
-     | -     | |
Copper Weight     | 110.6 kg (243.9 lb)     |
237.7 kg (524.0 lb)     |
-     | |
Inside Connection (1)     | 4 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 16 - #1     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     |
0.0068 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     |
-     | 0.686 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 120 Hz     | |||
Exciter Poles     | 8     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 63.5 mm (2.5 inch)     |
63.5 mm (2.5 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 8     | 48     | ||
Turns (Coils)     | 160     | 7     | ||
No. & Size Wire     | 2 - #16.5     | 3 - #15     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 330.2 mm (13.0 inch)     |
386.1 mm (15.2 inch)     |
||
Copper Weight     | 10.0 kg (22.1 lb)     |
6.2 kg (13.7 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 3048.0 mm (120.0 inch)     |
#10 304.8 mm (12.0 inch)     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #10 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram C |
5N-5026 Generator
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 424.2 mm (16.7 inch)     |
431.8 mm (17.0 inch)     |
-     | |
Slots     | 84     | -     | -     | |
Coil Throw     | 1 - 19     | -     | -     | |
Turns/Coil     | 1     | -     | -     | |
Turns/Pole     | -     | 160     | -     | |
No. & Wire Size     | 18 - #13     | 1 - #7 sq     | -     | |
Mean Length Turn     | 1724.7 mm (67.9 inch)     |
-     | -     | |
Copper Weight     | 63.5 kg (139.9 lb)     |
98.5 kg (217.1 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 20 - #000     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     |
0.0023 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     |
-     | 1.17 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 127.0 mm (5.0 inch)     |
127.0 mm (5.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 125     | 6     | ||
No. & Size Wire     | 1 - #15     | 2 - #15     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 464.8 mm (18.3 inch)     |
406.4 mm (16.0 inch)     |
||
Copper Weight     | 5.2 kg (11.5 lb)     |
2.7 kg (5.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 965.2 mm (38.0 inch)     |
#10 152.4 mm (6.0 inch)     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #01 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram A |
5N-7064 Generator
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 215.9 mm (8.5 inch)     |
215.9 mm (8.5 inch)     |
-     | |
Slots     | 60     | -     | -     | |
Coil Throw     | 1 - 12     | -     | -     | |
Turns/Coil     | 3     | -     | -     | |
Turns/Pole     | -     | 160     | -     | |
No. & Wire Size     | 9 - #13     | 1 - #7 sq     | -     | |
Mean Length Turn     | 1214.1 mm (47.8 inch)     |
-     | -     | |
Copper Weight     | 46.7 kg (103.0 lb)     |
69.3 kg (152.7 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 20 - #1     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     |
0.0278 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     |
-     | 0.829 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 101.6 mm (4.0 inch)     |
101.6 mm (4.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 140     | 6     | ||
No. & Size Wire     | 1 - #15.5     | 2 - #15     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 414.0 mm (16.3 inch)     |
355.6 mm (14.0 inch)     |
||
Copper Weight     | 4.7 kg (10.3 lb)     |
2.2 kg (4.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 965.2 mm (38.0 inch)     |
#10 152.4 mm (6.0 inch)     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #02 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram A |
5N-7065 Generator
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 215.9 mm (8.5 inch)     |
215.9 mm (8.5 inch)     |
-     | |
Slots     | 60     | -     | -     | |
Coil Throw     | 1 - 12     | -     | -     | |
Turns/Coil     | 3.8(3,4,4,4,4)     | -     | -     | |
Turns/Pole     | -     | 160     | -     | |
No. & Wire Size     | 9 - #14     | 1 - #7 sq     | -     | |
Mean Length Turn     | 1214.1 mm (47.8 inch)     |
-     | -     | |
Copper Weight     | 46.9 kg (103.6 lb)     |
69.3 kg (152.7 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 20 - #2     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     |
0.0111 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     |
-     | 0.829 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 101.6 mm (4.0 inch)     |
101.6 mm (4.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 140     | 6     | ||
No. & Size Wire     | 1 - #15.5     | 2 - #15     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 414.0 mm (16.3 inch)     |
355.6 mm (14.0 inch)     |
||
Copper Weight     | 4.7 kg (10.3 lb)     |
2.2 kg (4.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 965.2 mm (38.0 inch)     |
#10 152.4 mm (6.0 inch)     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #13 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram A |
5N-7066 Generator
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 266.7 mm (10.5 inch)     |
266.7 mm (10.5 inch)     |
-     | |
Slots     | 72     | -     | -     | |
Coil Throw     | 1 - 14     | -     | -     | |
Turns/Coil     | 2     | -     | -     | |
Turns/Pole     | -     | 160     | -     | |
No. & Wire Size     | 11 - #13     | 1 - #7 sq     | -     | |
Mean Length Turn     | 1270.0 mm (50.0 inch)     |
-     | -     | |
Copper Weight     | 50.8 kg (112.0 lb)     |
76.7 kg (169.1 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 20 - #1     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     |
0.005 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     |
-     | 0.916 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 101.6 mm (4.0 inch)     |
101.6 mm (4.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 140     | 6     | ||
No. & Size Wire     | 1 - #15.5     | 2 - #15     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 414.0 mm (16.3 inch)     |
355.6 mm (14.0 inch)     |
||
Copper Weight     | 4.7 kg (10.3 lb)     |
2.2 kg (4.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 965.2 mm (38.0 inch)     |
#10 152.4 mm (6.0 inch)     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #01 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram A |
5N-7067 Generator
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 266.7 mm (10.5 inch)     |
266.7 mm (10.5 inch)     |
-     | |
Slots     | 72     | -     | -     | |
Coil Throw     | 1 - 14     | -     | -     | |
Turns/Coil     | 2.5(2,3,2,3,2,3)     | -     | -     | |
Turns/Pole     | -     | 160     | -     | |
No. & Wire Size     | 9 - #13     | 1 - #7 sq     | -     | |
Mean Length Turn     | 1270.0 mm (50.0 inch)     |
-     | -     | |
Copper Weight     | 51.7 kg (114.0 lb)     |
76.7 kg (169.1 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 20 - #2     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     |
0.0076 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     |
-     | 0.916 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 101.6 mm (4.0 inch)     |
101.6 mm (4.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 140     | 6     | ||
No. & Size Wire     | 1 - #15.5     | 2 - #15     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 414.0 mm (16.3 inch)     |
355.6 mm (14.0 inch)     |
||
Copper Weight     | 4.7 kg (10.3 lb)     |
2.2 kg (4.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 965.2 mm (38.0 inch)     |
#10 152.4 mm (6.0 inch)     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #13 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram A |
Note: Wires 20, 22, and 24 are brought out as tap connections between the 4th and 5th coil (14 turns from T0).
5N-7068 Generator
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 289.6 mm (11.4 inch)     |
289.6 mm (11.4 inch)     |
-     | |
Slots     | 66 (1)     | -     | -     | |
Coil Throw     | 1 - 13     | -     | -     | |
Turns/Coil     | 1     | -     | -     | |
Turns/Pole     | -     | 160     | -     | |
No. & Wire Size     | 25 - #13     | 1 - #7     | -     | |
Mean Length Turn     | 1374.1 mm (54.1 inch)     |
-     | -     | |
Copper Weight     | 52.8 kg (116.5 lb)     |
77.2 kg (170.2 lb)     |
-     | |
Inside Connection (2)     | 4 in Series     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 20 - #1     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     |
0.0041 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     |
-     | 0.966 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 101.6 mm (4.0 inch)     |
101.6 mm (4.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 140     | 6     | ||
No. & Size Wire     | 1 - #15.5     | 2 - #15     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 414.0 mm (16.3 inch)     |
355.6 mm (14.0 inch)     |
||
Copper Weight     | 4.7 kg (10.3 lb)     |
2.2 kg (4.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (3)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 965.2 mm (38.0 inch)     |
#10 152.4 mm (6.0 inch)     |
( 1 ) | Wind 6 coil groups with 5 coils per group, wind 6 coil groups with 6 coils per group. Put coil groups in stator (5,6,5,6-etc). |
( 2 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #34 |
( 3 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram A |
5N-7069 Generator
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 289.6 mm (11.4 inch)     |
289.6 mm (11.4 inch)     |
-     | |
Slots     | 84     | -     | -     | |
Coil Throw     | 1 - 17     | -     | -     | |
Turns/Coil     | 2     | -     | -     | |
Turns/Pole     | -     | 160     | -     | |
No. & Wire Size     | 10 - #13     | 1 - #7     | -     | |
Mean Length Turn     | 1501.1 mm (59.1 inch)     |
-     | -     | |
Copper Weight     | 57.6 kg (126.9 lb)     |
77.2 kg (170.2 lb)     |
-     | |
Inside Connection (2)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 10 - #0000     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     |
0.0072 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     |
-     | 0.966 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 101.6 mm (4.0 inch)     |
101.6 mm (4.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 140     | 6     | ||
No. & Size Wire     | 1 - #15.5     | 2 - #15     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 414.0 mm (16.3 inch)     |
355.6 mm (14.0 inch)     |
||
Copper Weight     | 4.7 kg (10.3 lb)     |
2.2 kg (4.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (3)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 965.2 mm (38.0 inch)     |
#10 152.4 mm (6.0 inch)     |
( 2 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #37 |
( 3 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram A |
Note: Wires 20 and 22 are brought out as tap connections between the 5th and 6th coil (10 turns from T0).
Note: Wire 24 is brought out as a tap connection between the 6th and 7th coil (12 turns from T0).
5N-7070 Generator
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 424.2 mm (16.7 inch)     |
431.8 mm (17.0 inch)     |
-     | |
Slots     | 84     | -     | -     | |
Coil Throw     | 1 - 19     | -     | -     | |
Turns/Coil     | 1     | -     | -     | |
Turns/Pole     | -     | 160     | -     | |
No. & Wire Size     | 18 - #13     | 1 - #7 sq     | -     | |
Mean Length Turn     | 1724.7 mm (67.9 inch)     |
-     | -     | |
Copper Weight     | 63.5 kg (139.9 lb)     |
98.5 kg (217.1 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 20 - #000     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     |
0.0023 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     |
-     | 1.17 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 127.0 mm (5.0 inch)     |
127.0 mm (5.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 125     | 6     | ||
No. & Size Wire     | 1 - #15     | 2 - #15     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 464.8 mm (18.3 inch)     |
406.4 mm (16.0 inch)     |
||
Copper Weight     | 5.2 kg (11.5 lb)     |
2.7 kg (5.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 965.2 mm (38.0 inch)     |
#10 152.4 mm (6.0 inch)     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #01 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram A |
5N-7071 Generator
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 424.2 mm (16.7 inch)     |
431.8 mm (17.0 inch)     |
-     | |
Slots     | 54 (1)     | -     | -     | |
Coil Throw     | 1 - 12     | -     | -     | |
Turns/Coil     | 1     | -     | -     | |
Turns/Pole     | -     | 160     | -     | |
No. & Wire Size     | 30 - #13     | 1 - #7 sq     | -     | |
Mean Length Turn     | 1714.5 mm (67.5 inch)     |
-     | -     | |
Copper Weight     | 64.2 kg (141.5 lb)     |
98.4744 kg (217.1 lb)     |
-     | |
Inside Connection (2)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 20 - #00     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     |
0.0033 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     |
-     | 1.17 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 127.0 mm (5.0 inch)     |
127.0 mm (5.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 125     | 6     | ||
No. & Size Wire     | 1 - #15     | 2 - #15     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 464.8 mm (18.3 inch)     |
406.4 mm (16.0 inch)     |
||
Copper Weight     | 5.2 kg (11.5 lb)     |
2.7 kg (5.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (3)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 965.2 mm (38.0 inch)     |
#10 152.4 mm (6.0 inch)     |
( 1 ) | Wind 6 coil groups with 4 coils per group, wind 6 coil groups with 5 coils per group. Put coil groups in stator (4,5,4,5-etc). |
( 2 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #31 |
( 3 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram A |
5N-7200 Generator
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 467.4 mm (18.4 inch)     |
480.1 mm (18.9 inch)     |
-     | |
Slots     | 72     | -     | -     | |
Coil Throw     | 1 - 11     | -     | -     | |
Turns/Coil     | 2     | -     | -     | |
Turns/Pole     | -     | 147.5     | -     | |
No. & Wire Size     | 20 - #13     | 1 - 3.3 mm x 6.4 mm (.13 inch x .25 inch)     |
-     | |
Mean Length Turn     | 1772.9 mm (69.8 inch)     |
-     | -     | |
Copper Weight     | 121.5 kg (267.9 lb)     |
237.0 kg (522.6 lb)     |
-     | |
Inside Connection (1)     | 6/3 Parallel Star     | 6 in Series     | -     | |
Line Leads (No. & Size)     | 30 - #00     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     |
0.0065 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     |
-     | 1.126 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 80 Hz     | |||
Exciter Poles     | 8     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 8     | 48     | ||
Turns (Coils)     | 160     | 8     | ||
No. & Size Wire     | 1 - #18 2 - #17     |
3 - #16     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 355.6 mm (14.0 inch)     |
436.9 mm (17.2 inch)     |
||
Copper Weight     | 6.4 kg (14.0 lb)     |
13.6 kg (29.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 762.0 mm (30.0 inch)     |
#10 304.8 mm (12.0 inch)     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #38 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram C |
5N-7201 Generator
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 467.4 mm (18.4 inch)     |
480.1 mm (18.9 inch)     |
-     | |
Slots     | 72     | -     | -     | |
Coil Throw     | 1 - 10     | -     | -     | |
Turns/Coil     | 2.75(3,3,3,2)     | -     | -     | |
Turns/Pole     | -     | 154.6     | -     | |
No. & Wire Size     | 14 - #13     | 1 - 3.3 mm x 6.4 mm (.13 inch x .25 inch)     |
-     | |
Mean Length Turn     | 1704.3 mm (67.1 inch)     |
-     | -     | |
Copper Weight     | 112.4 kg (247.8 lb)     |
237.0 kg (522.6 lb)     |
-     | |
Inside Connection (1)     | 6/3 Parallel Star     | 6 in Series     | -     | |
Line Leads (No. & Size)     | 30 - #0     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     |
0.0122 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     |
-     | 1.126 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 80 Hz     | |||
Exciter Poles     | 8     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 8     | 48     | ||
Turns (Coils)     | 160     | 8     | ||
No. & Size Wire     | 1 - #18 2 - #17     |
3 - #16     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 355.6 mm (14.0 inch)     |
436.9 mm (17.2 inch)     |
||
Copper Weight     | 6.4 kg (14.0 lb)     |
13.6 kg (29.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 762.0 mm (30.0 inch)     |
#10 304.8 mm (12.0 inch)     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #38 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram C |
5N-7202 Generator
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 467.4 mm (18.4 inch)     |
480.1 mm (18.9 inch)     |
-     | |
Slots     | 72     | -     | -     | |
Coil Throw     | 1 - 11     | -     | -     | |
Turns/Coil     | 2     | -     | -     | |
Turns/Pole     | -     | 147.5     | -     | |
No. & Wire Size     | 20 - #13     | 1 - 3.3 mm x 6.4 mm (.13 inch x .25 inch)     |
-     | |
Mean Length Turn     | 1772.9 mm (69.8 inch)     |
-     | -     | |
Copper Weight     | 121.5 kg (267.9 lb)     |
237.0 kg (522.6 lb)     |
-     | |
Inside Connection (1)     | 6/3 Parallel Star     | 6 in Series     | -     | |
Line Leads (No. & Size)     | 30 - #00     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     |
0.0065 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     |
-     | 1.126 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 80 Hz     | |||
Exciter Poles     | 8     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 8     | 48     | ||
Turns (Coils)     | 160     | 8     | ||
No. & Size Wire     | 1 - #18 2 - #17     |
3 - #16     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 355.6 mm (14.0 inch)     |
436.9 mm (17.2 inch)     |
||
Copper Weight     | 6.4 kg (14.0 lb)     |
13.6 kg (29.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 762.0 mm (30.0 inch)     |
#10 304.8 mm (12.0 inch)     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #38 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram C |
5N-7203 Generator
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 467.4 mm (18.4 inch)     |
480.1 mm (18.9 inch)     |
-     | |
Slots     | 72     | -     | -     | |
Coil Throw     | 1 - 10     | -     | -     | |
Turns/Coil     | 2.75(3,3,3,2)     | -     | -     | |
Turns/Pole     | -     | 154.6     | -     | |
No. & Wire Size     | 14 - #13     | 1 - 3.3 mm x 6.4 mm (.13 inch x .25 inch)     |
-     | |
Mean Length Turn     | 1704.3 mm (67.1 inch)     |
-     | -     | |
Copper Weight     | 112.4 kg (247.8 lb)     |
237.0 kg (522.6 lb)     |
-     | |
Inside Connection (1)     | 6/3 Parallel Star     | 6 in Series     | -     | |
Line Leads (No. & Size)     | 30 - #0     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     |
0.0122 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     |
-     | 1.126 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 80 Hz     | |||
Exciter Poles     | 8     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 8     | 48     | ||
Turns (Coils)     | 160     | 8     | ||
No. & Size Wire     | 1 - #18 2 - #17     |
3 - #16     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 355.6 mm (14.0 inch)     |
436.9 mm (17.2 inch)     |
||
Copper Weight     | 6.4 kg (14.0 lb)     |
13.6 kg (29.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 762.0 mm (30.0 inch)     |
#10 304.8 mm (12.0 inch)     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #38 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram C |
5N-7204 Generator
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 269.2 mm (10.6 inch)     |
281.9 mm (11.1 inch)     |
-     | |
Slots     | 72     | -     | -     | |
Coil Throw     | 1 - 10     | -     | -     | |
Turns/Coil     | 3.5(3,4,3,4)     | -     | -     | |
Turns/Pole     | -     | 154.5     | -     | |
No. & Wire Size     | 12 - #13     | 1 - 3.3 mm x 6.4 mm (.13 inch x .25 inch)     |
-     | |
Mean Length Turn     | 1308.1 mm (51.5 inch)     |
-     | -     | |
Copper Weight     | 94.1 kg (207.5 lb)     |
168.9 kg (372.5 lb)     |
-     | |
Inside Connection (1)     | 6/3 Parallel Star     | 6 in Series     | -     | |
Line Leads (No. & Size)     | 30 - #2     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     |
0.0139 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     |
-     | 0.802 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 80 Hz     | |||
Exciter Poles     | 8     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 8     | 48     | ||
Turns (Coils)     | 160     | 8     | ||
No. & Size Wire     | 1 - #18 2 - #17     |
3 - #16     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 355.6 mm (14.0 inch)     |
436.9 mm (17.2 inch)     |
||
Copper Weight     | 6.4 kg (14.0 lb)     |
13.6 kg (29.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 762.0 mm (30.0 inch)     |
#10 304.8 mm (12.0 inch)     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #38 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram C |
5N-7205 Generator
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 269.2 mm (10.6 inch)     |
281.9 mm (11.1 inch)     |
-     | |
Slots     | 72     | -     | -     | |
Coil Throw     | 1 - 10     | -     | -     | |
Turns/Coil     | 4.5(4,5,4,5)     | -     | -     | |
Turns/Pole     | -     | 154.5     | -     | |
No. & Wire Size     | 9 - #13     | 1 - 3.3 mm x 6.4 mm (.13 inch x .25 inch)     |
-     | |
Mean Length Turn     | 1308.1 mm (51.5 inch)     |
-     | -     | |
Copper Weight     | 90.8 kg (200.1 lb)     |
168.9 kg (372.5 lb)     |
-     | |
Inside Connection (1)     | 6/3 Parallel Star     | 6 in Series     | -     | |
Line Leads (No. & Size)     | 30 - #2     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     |
0.0239 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     |
-     | 0.802 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 80 Hz     | |||
Exciter Poles     | 8     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 8     | 48     | ||
Turns (Coils)     | 160     | 8     | ||
No. & Size Wire     | 1 - #18 2 - #17     |
3 - #16     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 355.6 mm (14.0 inch)     |
436.9 mm (17.2 inch)     |
||
Copper Weight     | 6.4 kg (14.0 lb)     |
13.6 kg (29.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 762.0 mm (30.0 inch)     |
#10 304.8 mm (12.0 inch)     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #38 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram C |
5N-7206 Generator
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 269.2 mm (10.6 inch)     |
281.9 mm (11.1 inch)     |
-     | |
Slots     | 72     | -     | -     | |
Coil Throw     | 1 - 10     | -     | -     | |
Turns/Coil     | 3.5(3,4,3,4)     | -     | -     | |
Turns/Pole     | -     | 154.5     | -     | |
No. & Wire Size     | 12 - #13     | 1 - 3.3 mm x 6.4 mm (.13 inch x .25 inch)     |
-     | |
Mean Length Turn     | 1308.1 mm (51.5 inch)     |
-     | -     | |
Copper Weight     | 94.1 kg (207.5 lb)     |
168.9 kg (372.5 lb)     |
-     | |
Inside Connection (1)     | 6/3 Parallel Star     | 6 in Series     | -     | |
Line Leads (No. & Size)     | 30 - #2     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     |
0.0139 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     |
-     | 0.802 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 80 Hz     | |||
Exciter Poles     | 8     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 8     | 48     | ||
Turns (Coils)     | 160     | 8     | ||
No. & Size Wire     | 1 - #18 2 - #17     |
3 - #16     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 355.6 mm (14.0 inch)     |
436.9 mm (17.2 inch)     |
||
Copper Weight     | 6.4 kg (14.0 lb)     |
13.6 kg (29.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 762.0 mm (30.0 inch)     |
#10 304.8 mm (12.0 inch)     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #38 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram C |
5N-7207 Generator
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 269.2 mm (10.6 inch)     |
281.9 mm (11.1 inch)     |
-     | |
Slots     | 72     | -     | -     | |
Coil Throw     | 1 - 10     | -     | -     | |
Turns/Coil     | 4.5(4,5,4,5)     | -     | -     | |
Turns/Pole     | -     | 154.5     | -     | |
No. & Wire Size     | 9 - #13     | 1 - 3.3 mm x 6.4 mm (.13 inch x .25 inch)     |
-     | |
Mean Length Turn     | 1308.1 mm (51.5 inch)     |
-     | -     | |
Copper Weight     | 90.8 kg (200.1 lb)     |
168.9 kg (372.5 lb)     |
-     | |
Inside Connection (1)     | 6/3 Parallel Star     | 6 in Series     | -     | |
Line Leads (No. & Size)     | 30 - #2     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     |
0.0239 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     |
-     | 0.802 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 80 Hz     | |||
Exciter Poles     | 8     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 8     | 48     | ||
Turns (Coils)     | 160     | 8     | ||
No. & Size Wire     | 1 - #18 2 - #17     |
3 - #16     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 355.6 mm (14.0 inch)     |
436.9 mm (17.2 inch)     |
||
Copper Weight     | 6.4 kg (14.0 lb)     |
13.6 kg (29.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 762.0 mm (30.0 inch)     |
#10 304.8 mm (12.0 inch)     |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #38 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram C |