Winding Data for 102-2415 Generator through 108-3052 Generator
102-2415 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 304.8 mm (12 inch)     |
304.8 mm (12 inch)     |
|||||
Slots     | 48     | -     | |||||
Coil Throw     | 1 - 10     | -     | |||||
Turns/Coil     | 3.75 (4-4-4-3)     | -     | |||||
Turns/Pole     | -     | 130     | |||||
No. & Wire Size     | 8 - #14     | #8 SQ     | |||||
Mean Length Turn     | 1242.1 mm (48.9 inch)     |
-     | |||||
Copper Weight     | 33.7 kg (74.4 lb)     |
48.3 kg (106.5 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 4 - #0     | -     | |||||
Terminal bolt size     | 3/8 in     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.04355 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.015 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
-     | ||||
Coils/Group     | 6     | 2     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 150     | 8     | -     | ||||
No. & Size Wire     | 1 - #16     | 2 - #16     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 388.6 mm (15.3 inch)     |
350.5 mm (13.8 inch)     |
-     | ||||
Copper Weight     | 4.1 kg (9.1 lb)     |
2.2 kg (4.8 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 21 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
102-2417 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 419.1 mm (16.5 inch)     |
419.1 mm (16.5 inch)     |
|||||
Slots     | 48     | -     | |||||
Coil Throw     | 1 - 10     | -     | |||||
Turns/Coil     | 3     | -     | |||||
Turns/Pole     | -     | 130     | |||||
No. & Wire Size     | 12 - #14     | #8 SQ     | |||||
Mean Length Turn     | 1470.7 mm (57.9 inch)     |
-     | |||||
Copper Weight     | 47.9 kg (105.7 lb)     |
59.1 kg (130.4 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 4 - #000     | -     | |||||
Terminal bolt size     | 3/8 in     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0291 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.225 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
-     | ||||
Coils/Group     | 6     | 2     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 150     | 8     | -     | ||||
No. & Size Wire     | 1 - #16     | 2 - #16     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 388.6 mm (15.3 inch)     |
350.5 mm (13.8 inch)     |
-     | ||||
Copper Weight     | 4.1 kg (9.1 lb)     |
2.2 kg (4.8 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 21 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
103-1254 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 424.2 mm (16.7 inch)     |
431.8 mm (17 inch)     |
|||||
Slots     | 84     | -     | |||||
Coil Throw     | 1 - 19     | -     | |||||
Turns/Coil     | 2     | -     | |||||
Turns/Pole     | -     | 165     | |||||
No. & Wire Size     | 9 - #13     | #7 SQ     | |||||
Mean Length Turn     | 1724.7 mm (67.9 inch)     |
-     | |||||
Copper Weight     | 62.1 kg (137 lb)     |
102.0 kg (224.8 lb)     |
|||||
Inside Connection (1)     | 4 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 24 - #2     | -     | |||||
Terminal bolt size     | 3/8 in     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0104 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.25 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | 240 Hz     | ||||
Exciter Poles     | 6     | 16     | |||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 127.0 mm (5.0 inch)     |
127.0 mm (5.0 inch)     |
25.4 mm (1 inch)     |
||||
Coils/Group     | 1     | 2     | 1     | ||||
Slots (Coils)     | 6     | 36     | 48     | ||||
Turns (Coils)     | 140     | 7     | 12     | ||||
No. & Size Wire     | 1 - #15.5     | 2 - #15.5     | 4 - #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1 - 4     | ||||
Mean Length Turn (Calc.)     | 464.8 mm (18.3 inch)     |
406.4 mm (16.0 inch)     |
208.3 mm (8.2 inch)     |
||||
Copper Weight     | 5.2 kg (11.5 lb)     |
2.7 kg (6.0 lb)     |
1.8 kg (4.0 lb)     |
||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | 1 Series     | ||||
Line Leads     | 1 - #14     | 3 - #10     | 3 - #14     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 41 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
106-3578 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 566.4 mm (22.3 inch)     |
566.4 mm (22.3 inch)     |
|||||
Slots     | 60     | -     | |||||
Coil Throw     | 1 - 13     | -     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 180     | |||||
No. & Wire Size     | 40 - #14     | #6.5 RD     | |||||
Mean Length Turn     | 19873.7 mm (78.1 inch)     |
-     | |||||
Copper Weight     | 93.9 kg (207 lb)     |
123.4 kg (272.0 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Star     | Series     | |||||
Line Leads (No. & Size)     | 24 - #0     | -     | |||||
Terminal bolt size     | 3/8 in     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00485 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.732 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | 240 Hz     | ||||
Exciter Poles     | 6     | 16     | |||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 127.0 mm (5.0 inch)     |
127.0 mm (5.0 inch)     |
25.4 mm (1 inch)     |
||||
Coils/Group     | 1     | 1     | 1     | ||||
Slots (Coils)     | 6     | 36     | 48     | ||||
Turns (Coils)     | 140     | 8     | 12     | ||||
No. & Size Wire     | 1 - #15.5     | 2 - #16     | 4 - #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1 - 4     | ||||
Mean Length Turn (Calc.)     | 464.8 mm (18.3 inch)     |
464.8 mm (18.3 inch)     |
208.3 mm (8.2 inch)     |
||||
Copper Weight     | 5.2 kg (11.5 lb)     |
2.9 kg (6.4 lb)     |
1.8 kg (4.0 lb)     |
||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | 1 Series     | ||||
Line Leads     | 1 - #14     | 3 - #10     | 3 - #14     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 41 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
106-3579 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 566.4 mm (22.3 inch)     |
566.4 mm (22.3 inch)     |
|||||
Slots     | 60     | -     | |||||
Coil Throw     | 1 - 13     | -     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 180     | |||||
No. & Wire Size     | 40 - #14     | #6.5 RD     | |||||
Mean Length Turn     | 19873.7 mm (78.1 inch)     |
-     | |||||
Copper Weight     | 93.9 kg (207 lb)     |
123.4 kg (272.0 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Star     | Series     | |||||
Line Leads (No. & Size)     | 24 - #0     | -     | |||||
Terminal bolt size     | 3/8 in     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00485 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 1.732 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | 240 Hz     | ||||
Exciter Poles     | 6     | 16     | |||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 127.0 mm (5.0 inch)     |
127.0 mm (5.0 inch)     |
25.4 mm (1 inch)     |
||||
Coils/Group     | 1     | 1     | 1     | ||||
Slots (Coils)     | 6     | 36     | 48     | ||||
Turns (Coils)     | 140     | 8     | 12     | ||||
No. & Size Wire     | 1 - #15.5     | 2 - #16     | 4 - #18     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | 1 - 4     | ||||
Mean Length Turn (Calc.)     | 464.8 mm (18.3 inch)     |
464.8 mm (18.3 inch)     |
208.3 mm (8.2 inch)     |
||||
Copper Weight     | 5.2 kg (11.5 lb)     |
2.9 kg (6.4 lb)     |
1.8 kg (4.0 lb)     |
||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | 1 Series     | ||||
Line Leads     | 1 - #14     | 3 - #10     | 3 - #14     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 41 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
106-3652 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 660.4 mm (26 inch)     |
673.1 mm (26.5 inch)     |
|||||
Slots     | 60     | -     | |||||
Coil Throw     | 1 - 13     | -     | |||||
Turns/Coil     | 3     | -     | |||||
Turns/Pole     | -     | 174     | |||||
No. & Wire Size     | 2 - 4.3 mm (0.168 inch) × 5.8 mm (0.228 inch)     |
3.7 mm (0.144 inch) × 7.3 mm (0.288 inch)     |
|||||
Mean Length Turn     | 2517.1 mm (99.1 inch)     |
-     | |||||
Copper Weight     | 213.0 kg (469.5 lb)     |
320.1 kg (705.6 lb)     |
|||||
Inside Connection (1)     | 1 Series Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 6 - #2/0     | -     | |||||
Terminal bolt size     | 3/8 in     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.119 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.895 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 120 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 8     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
-     | ||||
Coils/Group     | 1     | 2     | -     | ||||
Slots (Coils)     | 8     | 48     | -     | ||||
Turns (Coils)     | 160     | 8     | -     | ||||
No. & Size Wire     | 2 - #17 and 1 - #18     | 3 - #16     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 355.6 mm (14 inch)     |
436.9 mm (17.2 inch)     |
-     | ||||
Copper Weight     | 14.0 kg (30.9 lb)     |
6.4 kg (14 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 12 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram C |
107-2967 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 172.7 mm (6.8 inch)     |
172.7 mm (6.8 inch)     |
|||||
Slots     | 48     | -     | |||||
Coil Throw     | 1 - 9     | -     | |||||
Turns/Coil     | Winding #1 (1) 5.5 (5-6-5-6)     |
Winding #2 5.5 (6-5-6-5)     |
    | ||||
Turns/Pole     | -     | -     | 130     | ||||
No. & Wire Size     | 6 - #16     | 3 - #16     | #8 SQ     | ||||
Mean Length Turn     | -     | -     | -     | ||||
Copper Weight     | 25.9 kg (57.2 lb)     |
35.7 kg (78.7 lb)     |
|||||
Inside Connection (1)     | 4 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 12 - #2     | 6 - #2     | -     | ||||
Terminal bolt size     | 3/8 in     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.0175 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.083 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 76.2 mm (3.0 inch)     |
76.2 mm (3.0 inch)     |
-     | ||||
Coils/Group     | 1     | 2     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 150     | 7     | -     | ||||
No. & Size Wire     | 1 - #16     | 2 - #15.5     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 363.2 mm (14.3 inch)     |
325.1 mm (12.8 inch)     |
-     | ||||
Copper Weight     | 3.9 kg (8.5 lb)     |
2.2 kg (4.8 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | Tap lead X1 three turns from finish in coil group 10 (Phase 1). |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 54 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
107-3133 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 172.7 mm (6.8 inch)     |
172.7 mm (6.8 inch)     |
|||||
Slots     | 48     | -     | |||||
Coil Throw     | 1 - 10     | -     | |||||
Turns/Coil     | 7     | -     | |||||
Turns/Pole     | -     | 130     | |||||
No. & Wire Size     | 5 - #14     | #8 SQ     | |||||
Mean Length Turn     | 977.9 mm (38.5 inch)     |
-     | |||||
Copper Weight     | 31.0 kg (68.4 lb)     |
35.7 kg (78.7 lb)     |
|||||
Inside Connection (1)     | 2 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 4 - #4     | -     | |||||
Terminal bolt size     | 3/8 in     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.1015 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.753 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 90 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 6     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 76.2 mm (3.0 inch)     |
76.2 mm (3.0 inch)     |
-     | ||||
Coils/Group     | 1     | 2     | -     | ||||
Slots (Coils)     | 6     | 36     | -     | ||||
Turns (Coils)     | 150     | 7     | -     | ||||
No. & Size Wire     | 1 - #16     | 2 - #15.5     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 363.2 mm (14.3 inch)     |
325.1 mm (12.8 inch)     |
-     | ||||
Copper Weight     | 3.9 kg (8.5 lb)     |
2.2 kg (4.8 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 21 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram D |
108-3052 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | |||||||
---|---|---|---|---|---|---|---|
ITEM     | STATOR     | ROTOR     | |||||
Stack Height     | 660.4 mm (26 inch)     |
673.1 mm (26.5 inch)     |
|||||
Slots     | 84     | -     | |||||
Coil Throw     | 1 - 17     | -     | |||||
Turns/Coil     | 1     | -     | |||||
Turns/Pole     | -     | 174     | |||||
No. & Wire Size     | 2 - 3.8 mm (0.148 inch) × 3.9 mm (0.153 inch)     |
3.7 mm (0.144 inch) × 7.3 mm (0.288 inch)     |
|||||
Mean Length Turn     | 2608.6 mm (102.7 inch)     |
-     | |||||
Copper Weight     | 195.1 kg (430.1 lb)     |
320.1 kg (705.6 lb)     |
|||||
Inside Connection (1)     | 4 Parallel Star     | 4 in Series     | |||||
Line Leads (No. & Size)     | 48 - #2/0     | -     | |||||
Terminal bolt size     | 3/8 in     | -     | |||||
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.00209 ohms     | -     | |||||
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.895 ohms     | |||||
EXCITER WINDING DATA     | |||||||
Exciter Frequency (Hz)     | 120 Hz     | Permanent Magnet Frequency     | - Hz     | ||||
Exciter Poles     | 8     | ||||||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | Permanent Magnet Stator     | ||||
Stack Length     | 88.9 mm (3.5 inch)     |
88.9 mm (3.5 inch)     |
-     | ||||
Coils/Group     | 1     | 2     | -     | ||||
Slots (Coils)     | 8     | 48     | -     | ||||
Turns (Coils)     | 160     | 8     | -     | ||||
No. & Size Wire     | 2 - #17 and 1 - #18     | 3 - #16     | -     | ||||
Coil Throw     | 1 - 2     | 1 - 6     | -     | ||||
Mean Length Turn (Calc.)     | 355.6 mm (14 inch)     |
436.9 mm (17.2 inch)     |
-     | ||||
Copper Weight     | 14.0 kg (30.9 lb)     |
6.4 kg (14 lb)     |
-     | ||||
Insulation     | Heavy Polyester Polyamide Imide     | ||||||
Connection (2)     | Series     | 2 Parallel Star     | -     | ||||
Line Leads     | 2 - #14     | 3 - #10     | -     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 43 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram C |
Caterpillar Information System:
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for <B>5N-0001</B> Generator through <B>5N-0025</B> Generator
Electronic Modular Control Panel II (EMCP II) Component Location - For 3412C PEEC Engines
3608 Engine Gauges and Indicators
3608 Engine Safety Messages
3608 Engine Model View Illustrations
3608 Engine Accessory Drive
G3304 and G3306 Engines Pressure Gauge - Engine Oil
3524B Engines for 797 and 797B Off-Highway Trucks Charging System
3608 Engine Governor Actuator Linkage - Check
3608 Engine Governor Actuator Oil - Replace
G3304 and G3306 Engines Vacuum Gauge
Inspection and Modification of the 102-7459 Fuel Injection Control Linkage and the 4P-9048 Fuel Injection Control Linkage {1298} Inspection and Modification of the 102-7459 Fuel Injection Control Linkage and the 4P-9048 Fuel Injection Control Linkage {1298}
3034 Engine for Caterpillar Built Machines Camshaft Bearings - Remove
SR500 Generators Varistor - Test
3114, 3116, and 3126 Engines for Caterpillar Built Machines Camshaft - Remove
3034 Engine for Caterpillar Built Machines Camshaft Bearings - Install
SR500 Generators Winding - Test
3608 Engine Cooling System Coolant (DEAC) - Change
Customer Communication Module (CCM) for Diesel Engines Display Description
Customer Communication Module (CCM) for Diesel Engines Engine Number - Program
Uninterruptible Power Supply (UPS) 250 General Information
G3304 and G3306 Engines Air Inlet and Exhaust System
Uninterruptible Power Supply (UPS) 250 Power Sources
C32 Petroleum Generator Sets Emissions Warranty Information