30SI Series and 34SI Series Alternator Caterpillar


T7 Identifying Source of Current Draw - Test

Usage:

769C 01X

  • Make sure that every electrical component is turned OFF. Make sure that the keyswitch is turned OFF. Make sure that the dome lights are OFF.

    1. Clamp a 9U-5795 Current Probe or 225-8266 Ammeter Tool Gp around the main ground cable. Clamp the tool with the positive side away from the battery. Reset the probe (zero) before clamping the probe around the wire. Use the current probe if the draw is above approximately 2 A. Use the Ammeter if the draw is below approximately 2 A.

    1. Monitor the current and remove fuses and breakers one at a time. Check the current after each fuse (breaker) is removed. After removing a fuse (breaker) and observing the current, reinstall the fuse (breaker). Start with the main fuses (circuit breakers) first, and proceed to smaller circuits.

    1. If a removal of a fuse causes the current to drop, then the problem is in that circuit.

      1. Check if any components on the circuit are ON.

      1. If everything is OFF, disconnect electrical components on that circuit one at a time and monitor current.

      1. After all of the components in that circuit have been disconnected, check the current. If the problem still exists, then check the wiring for corrosion or shorts to ground.

    Note: The standard acceptable current draw is 50 mA. A current draw above 50 mA usually indicates a problem. However, some large machines with multiple electronic control modules have a higher acceptable limit. Contact a Caterpillar dealer for more information.

  • Caterpillar Information System:

    30SI Series and 34SI Series Alternator T6 Residual Magnetism Restoration
    30SI Series and 34SI Series Alternator T5 Alternator Current - Test
    30SI Series and 34SI Series Alternator T4 Alternator Drive System - Check
    30SI Series and 34SI Series Alternator T3 Charging System - Test
    3406E and 3456 Generator Set Engines Fuel Quality - Test
    30SI Series and 34SI Series Alternator T2 Electrical System Current - Test
    30SI Series and 34SI Series Alternator T1 Alternator Output - Test
    3508B Engine for 854G Wheel Dozers and 992G Wheel Loaders MID 036 - CID 0277 - FMI 08 Timing Calibration signal abnormal
    3126B Engine for Caterpillar Built Machines Engine Will Not Crank
    3054B Industrial Engine Gear Group (Front) - Install
    3054B Industrial Engine Gear Group (Front) - Remove
    C-9 Engines for Caterpillar Built Machines Pinion Clearance - Adjust
    30SI Series and 34SI Series Alternator T8 Alternator Overcharging - Test
    C-12, C-15 and C-16 Engines for Caterpillar Built Machines Alternator - Charging Problem
    3306B Generator Set Generator Set Installation
    Electronic Modular Control Panel II+ (EMCP II+) for EUI Engines CID 168 FMI 4 Electrical System Voltage Below Normal - Test
    C-9 Engine for TK711, TK721, TK722, TK732, TK741, TK751, and TK752 Track Feller Bunchers Coolant in Engine Oil
    Air Conditioning and Heating R134a for All Caterpillar Machines Refrigerant Condenser
    3126B Marine Engine Coolant Level Sensor - If Equipped
    3126B Marine Engine Engine Oil Pressure Sensor
    3406E and 3456 Generator Set Engines Turbocharger - Inspect
    Customer Communication Module (CCM) for Diesel Engines Parameter Identifiers for EMCP II
    C27 and C32 Engines for Caterpillar Built Machines Aftercooler - Test
    3406E and 3456 Generator Set Engines Engine Valve Lash - Inspect/Adjust
    Back to top
    The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
    CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.