Digital Voltage Regulator Caterpillar


Instantaneous Trip Shutdown - Troubleshoot

Usage:

SR4B 1BN
Instantaneous trip shutdown is fault 801.

Note: Electromagnetic noise spikes can create an erroneous instantaneous trip. Such spikes are often the result of breaker closure. If the digital voltage regulator or any wiring to the digital voltage regulator is in close proximity to a circuit breaker (particularly a medium voltage breaker), this condition may occur. Uninterrupted power systems (UPS), motor drives, and other equipment that generates electromagnetic interference (EMI) spikes or switches large currents must also be avoided. Install the digital voltage regulator in the generator terminal box or in another location away from the offending equipment.

  1. Check the wiring.

    1. Stop the generator set.

    2. Check the wiring.

      Expected Result: The wiring is correct.

      Results:

      • OK: Go to Step 2.

      • NOT OK: Shorted F1 and F2 wires will cause the instantaneous trip shutdown fault. Megger the exciter stator. See the proper wiring diagram for details. Refer to Testing And Adjusting, "Wiring Diagrams". STOP.

  2. Check the accessory.

    1. Disconnect all accessory wiring from terminals 3, 5, 6, 7, 40, 41, 42, 43, 44, 45, and 50. Remove the serial data link, if installed.

    2. Start the generator set. Operate the generator set with the same conditions that caused the problem previously.

      Expected Result: The generator set operates properly.

      Results:

      • OK: The generator set operates properly. There is a problem with an accessory which has been disconnected. Reconnect one accessory. Operate the generator set again. Continue this process of reconnecting one accessory at a time until the faulty accessory is found. STOP.

      • NOT OK: The generator set does not operate properly. Go to Step 3.

  3. Check the nearby equipment.

    1. Identify nearby equipment that could generate EMI spikes.

    2. Move the digital voltage regulator and the wiring to a temporary location away from the offending equipment and operate the generator again.

      Expected Result: The problem has been resolved.

      Results:

      • OK: The problem has been resolved. Find a new permanent home for the digital voltage regulator away from the offending equipment. Shielded wiring should always be used for rheostat inputs when the regulator and/or rheostat are located off the generator. Connect the shield drain wire to regulator terminal 45. Insulate the wiring shield from touching all other objects, including Earth ground.

      • NOT OK: The digital voltage regulator is being subjected to other sources of EMI. On methods to reduce EMI, refer to Systems Operation, "Customer Options", section Remote Installation Notes.

Caterpillar Information System:

3524B Engine for Caterpillar Built Machines Accessory Drive (Rear) - Install
Electric Protection System Energize-To-Run For Generator Set, Industrial and Marine Diesel Engines Oil Step Speed Calibration
3408E and 3412E Industrial Engines Sensors and Electrical Components
3524B Engine for Caterpillar Built Machines Accessory Drive (Rear) - Remove
3412E, C30 and C32 Marine Engines Electric Starting Motor - Remove and Install
Electric Protection System Energize-To-Run For Generator Set, Industrial and Marine Diesel Engines Crank Terminate Speed Calibration
3508B, 3512B, and 3516B High Displacement Generator Sets Fuel Injector - Inspect/Adjust
3500 and 3500B Engines Fuel System Fuel Filter Differential Pressure - Check
3508B, 3512B, and 3516B High Displacement Generator Sets Engine Oil Filter Differential Pressure - Check
Electric Protection System Energize-To-Run For Generator Set, Industrial and Marine Diesel Engines Overspeed Calibration
3500B Locomotive Engines Air Compressor - Inspect
3508B, 3512B, and 3516B High Displacement Generator Sets Prelube Pump - Inspect
Electric Protection System Energize-To-Run For Generator Set, Industrial and Marine Diesel Engines Magnetic Pickup Test
Electric Protection System Energize-To-Run For Generator Set, Industrial and Marine Diesel Engines Diode Test
Electric Protection System Energize-To-Run For Generator Set, Industrial and Marine Diesel Engines Engine Oil Pressure Switch Test
3600 Diesel Marine Monitoring System Safety Signs and Labels
Electric Protection System Energize-To-Run For Generator Set, Industrial and Marine Diesel Engines Slave Relay Test
3600 Diesel Marine Monitoring System Electrical System
3600 Diesel Marine Monitoring System Before Starting Engine
3600 Diesel Marine Monitoring System Engine Starting
3600 Diesel Marine Monitoring System Model View Illustrations
P16, P20, P25, P28, P40 and P60 Pulverizer Before Operation
3408E and 3412E Engines for Caterpillar Built Machines Crankshaft Rear Seal - Remove
Electric Protection System Energize-To-Run For Generator Set, Industrial and Marine Diesel Engines Water Temperature Contactor Switch Test
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.