Normally, the initialization occurs when the Main Display Module is replaced. When the Main Display Module is replaced, there will be a new harness code. When a previously used main display module is used as a replacement, the initialization is also necessary. Unexplained diagnostics with the CAT Data Link can occur if the main display module is not initialized correctly.
This procedure causes the initialization process to occur on any Main Display Module. The Main Display Module must be powered up with a valid harness code. This harness code must be unique. The main display module's previous harness code should not be used. For a list of valid harness codes, see the following Harness Code Tables.
Caterpillar Monitoring System Harness Code Tables
The following Harness Code Table is used for Switchgear applications of the 3412 MUI and the 3412 PEEC engines.
Caterpillar Monitoring System     | ||
EPG Harness Codes     | ||
No. (1)     | Harness Code     | Type     |
31     | 0     | Open     |
3     | 1     | Ground     |
12     | 2     | Ground     |
22     | 3     | Ground     |
16     | 4     | Ground     |
6     | 5     | Ground     |
( 1 ) | Main DIsplay Module connector contacts. |
The following Harness Code Table is for the Switchgear Conversion application of the 3500 MUI engines.
Caterpillar Monitoring System     | ||
EPG Harness Codes     | ||
No. (1)     | Harness Codes     | Type     |
31     | 0     | Ground     |
3     | 1     | Open     |
12     | 2     | Open     |
22     | 3     | Open     |
16     | 4     | Ground     |
16     | 5     | Ground     |
( 1 ) | Main Display Module connector contacts. |
The following Harness Code Table is for the Switchgear Conversion application of the 3500B EUI Engines.
Caterpillar Monitoring System     | ||
EPG Harness Codes     | ||
No. (1)     | Harness Code     | Type     |
31     | 0     | Open     |
3     | 1     | Ground     |
12     | 2     | Ground     |
22     | 3     | Ground     |
16     | 4     | Open     |
6     | 5     | Ground     |
( 1 ) | Main Display Module connector contacts |