SR4 HV and SR4B HV Generators Caterpillar


Insulation - Test

Usage:

3516B 1NW
Insulation resistance checks are conducted for two reasons:

  • Help in finding faults or help in finding weaknesses.

  • Give some indication of the service reliability that can be expected.

------ WARNING! ------

Personal injury or death can result from improper troubleshooting and repair procedures.

The following troubleshooting and repair procedures should only be performed by qualified personnel familiar with this equipment.

----------------------

Refer to Safety Section, "Generator Isolating for Maintenance" for information regarding the procedure to safely isolate the generator.

Recommended Periodic Insulation Tests

Periodically, use a megohmmeter to check the insulation resistance of the generator's main stator winding. The frequency of this test is determined by the generator's environment. Previous megohmmeter readings will also determine the frequency of this test.

Test the main stator windings with a megohmmeter in the following situations:

  • The generator set is started for the first time.

  • The generator set is removed from storage.

  • The generator set is operating in a humid environment. Test every three months.

  • The generator set is not protected from the elements in an enclosed area. Test every three months.

  • The generator set is installed in an enclosed area. This area needs to be low in humidity and this area needs to have steady temperatures. Test every six months.

  • The generator set has not been run under load for three months. Test the generator set weekly. Use space heaters around the generator set if the generator is exposed to a sea water environment or if the humidity is above 75%. Also use space heaters if a test result was below 3 megohms.

Space heaters must be used whenever the generator set is not under load. Space heaters must also be used whenever salt is present or whenever high humidity is present. Using a space heater in this fashion is the only way to maintain megohmmeter readings above one megohm. Use space heaters only when the generator is not running.

Insulation Resistance Tests at Low Voltage

Insulation resistance checks at low voltage are usually made on an armature or these tests are made on portions of an armature. These tests indicate the degree of contamination that is present on the surface of the insulation. Testing insulation resistance at low voltage also reveals contaminated solid insulation. Moisture can contaminate solid insulation and other influences can contaminate solid insulation. These tests will not usually reveal complete ruptures and these tests will not usually reveal uncontaminated ruptures.

Insulation resistance tests are based on determining the current that goes through the insulation and the current that goes across the surface of the insulation. This current is measured when a direct voltage is applied. The amount of current is dependent on the following factors:

  • The amount of voltage

  • The time of application

  • The area of the insulation

  • The thickness of the insulation

  • Temperature conditions during the test

  • Humidity during the test

The insulation resistance test is used in order to determine the condition of the insulation. These tests should be performed prior to more extensive testing.

Contact a Caterpillar dealer or refer to "I.E.E.E. Standard 432-1992" when more extensive tests are required.

Exciter Field (Stator)

  1. Disconnect the exciter leads from the terminals that are located in the terminal box.

  1. Connect the exciter leads to one clamp of a 500 volt megohmmeter. Connect the second megohmmeter's lead to the generator frame.

  1. Apply 500 volts from the megohmmeter. Measure the resistance reading after one minute. The minimum reading should be 1.0 megohm. If the reading is less than 1.0 megohm, refer to the drying procedures in the Maintenance Procedure, "Generator - Dry".

  1. After the megohmmeter has been disconnected, short the exciter field leads to the generator frame. Keep these leads connected to the frame for several minutes. This will allow any voltage that has been built up to be discharged.

Exciter Armature (Rotor)

  1. Disconnect the exciter armature's leads from the rotating rectifiers. Disconnect the generator field leads from the rectifier's positive heat sink. Disconnect the generator field leads from the rectifier's negative heat sink.

  1. Connect the leads of the exciter armature to one clamp of a 500 volt megohmmeter. Connect the remaining lead of the megohmmeter to the shaft.

    Note: Never apply a megohmmeter to rotating rectifiers.

  1. Apply 500 volts for a duration of one minute. Record the reading from the megohmmeter.

  1. This reading must be a minimum of 1.0 megohm. If the reading is less than 1.0 megohm, refer to the drying procedures in the Maintenance Procedure, "Generator - Dry".

  1. Disconnect the megohmmeter. Short the leads of the exciter armature to the generator frame. Keep these leads connected to the frame for several minutes. This will discharge any voltage that has built up.

Generator Field (Rotor)

  1. Connect the positive lead and connect the negative lead to one clamp of a 500 volt megohmmeter. Connect the remaining lead of the megohmmeter to the shaft.

  1. Apply 500 volts for a duration of one minute. Record the reading from the megohmmeter.

  1. This reading must be a minimum of 1.0 megohm. If the reading is less than 1.0 megohm, refer to the drying procedures in the Maintenance Procedure, "Generator - Dry".

  1. After the megohmmeter has been disconnected, short the generator field leads to the generator frame. Keep these leads connected to the frame for several minutes. This will discharge any voltage that has built up.

Generator Armature (Stator)

Table 1
Tools Needed    
Part Number     Part Name     Quantity    
9V6003     Insulation Tester     1    

  1. Disconnect the power connections from the generator terminals. Disconnect the control devices from the generator terminals.

  1. Measure the insulation resistance of each phase separately. While this measurement is being taken, the other two phases should be shorted to ground.

  1. Connect a 1000 volt megohmmeter between one of the phase leads and the generator frame.

  1. Apply 1000 volts for a duration of one minute. Record the reading from the megohmmeter. Correct this reading to 40 °C (104 °F). This reading should not be less than the results of the following formula:

    1. Add 1000 to the rated generator voltage.

    1. Divide this sum by 1000.

    1. The result will be resistance in megohms.

  1. After the megohmmeter has been disconnected, short the generator armature leads to the generator frame. Keep these leads connected to the frame for several minutes. This will discharge any voltage that has built up.

Caterpillar Information System:

3054 and 3056 Industrial and Generator Set Engines Water Outlet Manifold - Install
3054 and 3056 Industrial and Generator Set Engines Water Outlet Manifold - Remove
Generator Set Control Panel for Switchgear Conversion Accessing Diagnostic Information
3408E and 3412E Engines for Caterpillar Built Machines Valve Mechanism Cover Base - Remove and Install
797 Off-Highway Truck Hydraulic System Relief Valve (Hoist)
3408E and 3412E Engines for Caterpillar Built Machines Front Cover - Remove
Generator Set Control Panel for Switchgear Conversion Units Mode
3054 and 3056 Industrial and Generator Set Engines Engine Oil Pump
3054 Engine for Caterpillar Built Machines Crankshaft Pulley - Remove and Install
3608 Engine Engine Oil Pan - Disassemble
Generator Set Control Panel for Switchgear Conversion Tattletale Mode
3054 and 3056 Industrial and Generator Set Engines Engine Oil Cooler - Install
Generator Set Control Panel for Switchgear Conversion Troubleshooting Diagnostic Codes
3054 Engine for Caterpillar Built Machines Cylinder Liner - Remove
3054 Engine for Caterpillar Built Machines Cylinder Liner - Install
Generator Set Control Panel for Switchgear Conversion Initial Troubleshooting Procedure
3054 Engine for Caterpillar Built Machines Engine Oil Filter Base - Remove
Generator Set Control Panel for Switchgear Conversion LH/RH Switch - Troubleshoot
3054 Engine for Caterpillar Built Machines Engine Oil Filter Base - Install
3054 Engine for Caterpillar Built Machines Engine Oil Filter Base - Disassemble
Control Console For CPS361 Pumper, Cement General Information
3054 Engine for Caterpillar Built Machines Engine Oil Filter Base - Assemble
Generator Set Control Panel for Switchgear Conversion Scroll Switch - Troubleshoot
Jacket Water Heaters, Lube Oil Heaters, and Combination Heaters for G3600, 3600, and C280 Engines Electrical System Schematic
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.