UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Caterpillar


Front Panel Display (MMS System Cabinet)

Usage:

UPS 250 APZ

Description



Illustration 1g01271543
Location of the front panel display
(1) Front panel display


Illustration 2g01254180
(1) LCD display
(2) Soft keys (6)
(3) Emergency power off module
(4) Alarm LED indicator
(5) Notice LED indicator
(6) Normal LED indicator
(7) Key switch

The front panel display is located on the left door of the MMU system cabinet. Refer to Illustration 1 for the location of the display.

The key switch (7) has the following modes: Bypass, On-line and Reset

The LCD panel contains the following components: an LCD display (1), an emergency power off button (3), a key switch (7) and three status indicators (LED) (4), (5), and (6).

The three LED indicators show the status of the UPS. The "Alarm" LED (4) is red when there is an alarm. The "Notice" LED (5) is yellow when there is a notice. The "Normal" LED (6) flashes green when the UPS is on-line. The "Normal" LED is steady when the load is protected.

Removal Procedure for the Panel

Refer to Systems Operation, Testing and Adjusting, RENR9988, "Internal Component Preremoval Steps (MMS System Cabinet)" in order to shut down the system and gain access to internal components.

  1. Disconnect the connector from terminal J1.

  2. Disconnect the backlight power connector from terminal J4.

  3. Disconnect the EPO connector from terminal J7.

  4. Disconnect the APC connector from terminal J2.

  5. Disconnect the EMO connector from terminal J11.

  6. Remove the grounding screw.

  7. Remove the four nuts and the four lock washers that attach the panel to the cabinet door.

  8. Remove the panel from the front of the door.

Note: The LCD is not a separate item for removal and installation.

Installation Procedure for the Panel

  1. Position the panel in the cabinet door from the front.

  2. Attach the panel to the door with four nuts and four lock washers.

  3. Attach the grounding screw.

  4. Attach the EMO connector to terminal J11.

  5. Attach the connector to terminal J1.

  6. Attach the backlight power connector to terminal J4.

  7. Attach the EPO connector to terminal J7.

  8. Attach the APC connector to terminal J2.

Removal Procedure for the Key Switch

Refer to Systems Operation, Testing and Adjusting, RENR9988, "Internal Component Pre-removal Steps (MMS System Cabinet)" in order to shut down the system and gain access to internal components.

  1. Open the left cabinet door in order to gain access to the rear of the key switch.

  2. Remove the wires that are attached to the key switch (7). The wires contain a labeling to the location of the wire. Verify the labeling of the wires with the location of the wire.

  3. Remove the key switch (1).

Installation Procedure for the Key Switch



    Illustration 3g01271679
    Wire connections for the key switch and for the EPO module

  1. Verify orientation of the key switch (7) before installing the key switch.

  2. Attach the wires to the key switch. Verify the labeling of the wires with the location of the wire. Refer to Illustration 3.

Removal Procedure for the Emergency Power Off Module

Refer to Systems Operation, Testing and Adjusting, RENR9988, "Internal Component Pre-removal Steps (MMS System Cabinet)" in order to shut down the system and gain access to internal components.

  1. Open the left cabinet door in order to gain access to the rear of the EPO module (3).

  2. Remove the wires that are attached to the EPO module (3). The wires contain a labeling to the location of the wire. Verify the labeling of the wires with the location of the wire.

  3. Remove the EPO module (3).

Installation Procedure

  1. Check orientation of the EPO module before installing the module.

  2. Install the button face and the clear shield onto the base unit.

  3. Push the module through the front of the door. Set the module in place.

  4. Attach the wires to the module. Verify the labeling of the wires with the location of the wire. Refer to Illustration 3 for wire connections.

Caterpillar Information System:

UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Thermal Switch Terminal Block
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys UPS Shutdown
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Terminal Block (ESS)
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies System Fuses (MMS System Cabinet)
C13 On-highway Engine Connecting Rod Bearing Journal
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Cable Landing (4 Wire Output Cabinet)
3044C Industrial Engine Fuel Shutoff
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Capacitor (4 Wire Output Cabinet)
3044C Industrial Engine After Starting Engine
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Internal Component Preremoval Steps (MMS System Cabinet)
VR6 Or K65-12B Voltage Regulators Require An External Jumper Wire When Used With A Permanent Magnet Generator{4467} VR6 Or K65-12B Voltage Regulators Require An External Jumper Wire When Used With A Permanent Magnet Generator{4467}
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Circuit Breaker (K8)
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys General Information (4 Wire Transformer Cabinet)
TA22-4WD Agricultural Transmission Plate Locations and Film Locations
G3408C and G3412C Engines Accumulator
G3408C and G3412C Engines Accumulator Pressure - Test
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Specifications
G3408C and G3412C Engines Accumulator
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Internal Component Preremoval Steps (4 Wire Transformer Cabinet)
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys 4 Wire Transformer
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies General Purpose Interface PWA (MMS System Cabinet)
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies EPO Reset Switch (MMS System Cabinet)
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Fan Monitor PWA (MMS System Cabinet)
UPS 120, UPS 150, UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Parallel Cabinet Controller PWA
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.